Error and Informational Messages


A string NameID is pre-pended to error messages written to the message log. Name is a nonconfigurable identifier that is no longer than 9 characters. ID is a configurable identifier that is no longer than 9 characters and is specified using the /id parameter on the startup command-line.

Message Logs


The location of the message log depends upon the platform on which the interface is running. See the UniInt Interface User Manual for more information.

Messages are written to [PIHOME]\dat\pipc.log at the following times.

When the interface starts many informational messages are written to the log. These include the version of the interface, the version of UniInt, the commandline parameters used, and the number of points.

As the interface loads points, messages are sent to the log if there are any problems with the configuration of the points.



If the UniInt /dbUniInt parameter is found in the command-line, then various informational messages are written to the log file.

Fatal Errors


Message

No value specified after /id=

Meaning

Interface expects value following /id= command line parameter.




Message

Invalid value for /id= parameter (1-99)

Meaning

The value of the interface identifier has a valid range of 1 to 99.




Message

Citect username not specified for host xxxxx

Meaning

A remote Citect node has been specified with the /cihost parameter but no corresponding /ciuser parameter was found.




Message

Citect password not specified for host xxxxx

Meaning

A remote Citect node has been specified with the /cihost parameter but no corresponding /cipass parameter was found.

Serious Errors


Message

dev_service_input_list() ERROR : Citect list handle == NULL

Meaning

Attempt to read from invalid Citect list. Indicates corrupted memory. Contact OSIsoft Tech Support.




Message

dev_service_output_list() ERROR : Citect output list handle == NULL

Meaning

Attempt to read from invalid Citect list. Indicates corrupted memory. Contact OSIsoft Tech Support.




Message

ctListRead() returned error : xxxxx

Meaning

Error reading from Citect point list. Citect error message should be appended to this message.




Message

PI Tag xxxxx (CiTag yyyyy) has invalid Citect handle

Meaning

Attempt to read from invalid Citect point. Indicates corrupted memory. Contact OSIsoft Tech Support.




Message

PI Tag xxxxx (CiTag yyyyy) ERROR : xxxxx

Meaning

Error reading from Citect point list. Citect error message should be appended to this message.

Point Errors


Message

Failed to get the timestamp from the citect server. 

Interface will use the time from the interface node.



Meaning

Collection of Citect timestamp from the Citect server failed. This is supported only with version 7.20 and above of Citect.




Message

PI Tag[] location2 value out of range : point refused

Meaning

PI point attribute location2 value is out of range.




Message

PI Tag xxxxx (CiTag yyyyy) Error : Invalid data type to write to Citect

Meaning

Mismatch in data type when writing value to Citect point




Message

Unable to create [scan list xx |output list | event list] : xxxxxx

Meaning

Error creating Citect tag list. Citect error message should be appended to this message.




Message

Error : PI tag xxxxx (1234) (CiTag yyyyy) to scan list xx > xxxxxx

Meaning

Error adding Citect tag to Citect tag list. Citect error message should be appended to this message. Normally caused where the Citect tag listed in InstrumentTag attribute of the PI point is incorrect (Citect tag not found).

Warnings


Message

Invalid character in /id= parameter – tags will not be filtered using /id

Meaning

If the /id parameter is not a value between 1 and 99 then the tags will not be filtered by interface identifier. The /id parameter will be used in the log files.




Message

Cannot find ‘xxxxx’ state – ‘Bad Input’ will be used instead

Meaning

The digital state specified by the /stopstat parameter was not found in the system digital state set.




Message

Cannot connect to remote Citect host: xxxxx

Meaning

Unable to connect to the specified Citect host node. The interface will attempt to connect periodically.




Message

Cannot connect to local Citect host

Meaning

Unable to connect to the local Citect host node. The interface will attempt to connect periodically.




Message

All the Citect Lists are in error. The interface will reconnect to the Citect Server every # seconds.

Meaning

The connection to the Citect node was lost. The interface will attempt to reconnect periodically.