The performance standards need not describe the actions to betaken when the failure of a
SCE is identified (by whatever means, but this is one of the key processes at the heart of the SMS and so the process used to determine such action must be described An overview of the assurance process for SCEs (section 4.5.4) and a summary of the process by which the design element of initial suitability has been achieved must be given (this is the same requirement as to show that the residual risk related
to each SCE is ALARP section 4.4.6.1). Reliability targets are required in performance standards for components of active systems where their reliability can be measured with sufficient certainty (such that corrective action can confidently betaken if the reliability target is not met. Therefore, reliability targets must be provided in the performance standards for at least the following systems
Flammable
and toxic gas detectors
Fire and smoke detectors
Emergency shutdown valves and blowdown valves
Safety critical process instrumentation
and pressure safety valves
Firewater and gaseous extinguishment systems (to start
TEMPSC (launch and engine start systems and
HVAC (dampers to close and fans to stop.
Example Emergency lighting could be expected to have very high reliability, but each individual light may have a much lower reliability with the overall lighting level target still being achieved and so a target reliability for each light is generally not required. Prescriptive requirements outlined in section 3 should be addressed in this section where necessary.