The PW-200 series UPS system is connected between mains and critical loads , such as computer systems , telecommunication systems, computerized instruments etc.
The advantages of using UPS:
The UPS has its own internal voltage and frequency regulator circuits which ensure that its output is maintained within close tolerances independent of voltage and frequency variations on the mains power lines.
Increased noise rejection:
By rectifying the input ac power to dc power, and then converting it back to ac, any electrical noise that may present on the input mains supply line is effectively isolated from the UPS output, therefore the critical load sees only clean power.
Power blackout protection:
If the mains power fails, the UPS continues to power the critical load from its battery source, leaving the load immune from power disturbances.
1.1 System Description
Features :
On-line technology with pure sine wave output.
Inverter employs modern PWM and IGBT technology for optimum performance and reliability.
Microprocessor controlled UPS.
Static Switch (STS) for increased system availability.
LCD (Liquid Crystal Display) display for metering, messages, alarms & diagnostics.
Alarm history ( Memory for max. 256 alarms. )
Automatic battery testing (period is user programmable).
Built-in Maintenance Bypass function with interlock.
Emergency Power Off (from user's EPO contacts)
Dry alarm contacts for: Mains failure, Low Battery, Load on Bypass.
RS-232 communications of all system data .
RS-485 communications (optional).
Shutdown software for all popular operating systems.
High quality maintenance-free lead-acid type batteries.
High nonlinear load capacity, special for computers.
Complies with all major European safety and EMC standards.
Accessories :
Optional UPS monitoring software (RUPS, RUPSII, UPSILON) SNMP devices, compatible to any operating system.
Remote Monitoring Panel (RMP) with LCD : You can observe the UPS status and parameters without using a computer at a remote location up to 200 meters away ( via RS485 interface).
UPS Port Sharer available
Increased battery charger option for extended back up time.
PW-200 Series Uninterruptible Power Supplies (UPS) are advanced true On-Line Sine wave devices with static transfer switch which provide reliable, regulated, transient-free AC power to sensitive equipment.
Since the UPS is a true On-Line system, conditioned power is provided continuously to the connected equipments. Unlike standby power systems, the UPS is constantly regulating and filtering the output power. When incoming power is interrupted, the UPS protects the computers instantaneously without any transfer time.
The PW-200 Series has high non-linear load capability (i.e. Crest Ratio 3:1) and this is suitable for powering special loads such as switching power supplies or highly capacitive inputs like computers.
Figure 1.1: PW-200 UPS Block Diagram
The system's static transfer switch (STS) provides by-pass power as its standby source. During an overload condition, the S.T.S will switch the customer's load over to the bypass line with no interruption. The S.T.S will transfer back to the inverter automatically when the overload condition has been cleared. If the inverter fails internally, the unit switches to bypass within a few milliseconds.
Rectifier : The first stage of the UPS. It supplies the DC bus voltage, which is necessary for operating the inverter by rectifying line voltage.
Inverter : It is made by utilizing the latest technology of power transistor (IGBT) and pulse width modulation (PWM). Inverter converts dc bus voltage into an alternative voltage like line voltage. And provides this voltage and frequency being fixed. An isolation transformer is integrated in the inverter.
Static Transfer Switch (static by-pass) : Static transfer switch is an electronically controlled switching circuit checked by main controller board. In case of inverter overload or any other faults, STS transfers the critical load to the mains without any interruption.
Maintenance Bypass Switch : This mechanical transfer switch consists of a manually operated make before break switch. When the UPS is switched off due to failure or maintenance, it feeds critical loads from mains. Transfer to Maintenance Bypass is "smooth" (no break).
Battery Group : It keeps dc voltage, which is necessary for the inverter , as a reservoir dc power supply in case of mains failure. Autonomy time is defined by the user.
Battery Charger : It produces a well regulated dc voltage suitable for charging the UPS batteries. Charging characteristic is according to DIN 41773 (IU). To ensure maximum battery life, charger current limit may be adjusted according to battery capacity.
1.2 Technical Specifications
|
PW-206
|
PW-207
|
PW-210
|
PW-215
|
PW-220
|
PW-230
|
Power
|
6 kVA
|
7,5 kVA
|
10 kVA
|
15 kVA
|
20 kVA
|
30 kVA
|
Power Factor
|
0,8
|
0,8
|
0,8
|
0,8
|
0,8
|
0,8
|
Automatic Battery Test
|
O
|
O
|
O
|
|
|
|
Alarm Relays
|
|
|
|
|
|
|
RS 232
|
|
|
|
|
|
|
RS 485 (optional)
|
|
|
|
|
|
|
INPUT
|
Input Voltage
|
400 VAC 3Ph + N
|
Input Voltage Tolerance
|
+ 15% , -15%
|
By-pass Voltage
|
230 VAC 10%
|
Input Current
|
12 A
|
15 A
|
20A
|
29 A
|
40 A
|
60 A
|
Input Frequency
|
50 Hz. 5%
|
RFI Level
|
EN50091-2
|
OUTPUT
|
Nominal Output Power
|
4.8 kW
|
6 kW
|
8 kW
|
12 kW
|
16 kW
|
24 kW
|
Output Voltage
|
230 VAC
|
Output Voltage Tolerance
|
1%
|
Output Frequency
|
50 Hz.
|
Output Frequency Tolerance
|
Line Synchronized 50Hz 1%, 2%, 3%, 4% (user programmable)
|
Free Running 0.05%
|
Efficiency (100% Load)
|
> 90 %
|
Crest Factor
|
3:1
|
Overload capacity
|
100% - 125% Load 10 min.
125% - 150% Load 60 sec.
>1000% 20mS (from by-pass)
|
Total Harmonic Distortion
|
THD < 3%
|
BATTERY
|
Batteries
|
20 x 12V
|
20 x 12V
|
20 x 12V
|
16 x 12V
|
26 x 12V
|
26 x 12V
|
Floating Charge Voltage
|
270 Vdc
|
270 Vdc
|
270 Vdc
|
216 Vdc
|
351 Vdc
|
351 Vdc
|
End of Discharge Voltage
|
200 Vdc
|
200 Vdc
|
200 Vdc
|
160 Vdc
|
260 Vdc
|
260 Vdc
|
Autonomy Time
|
User Defined
|
Max. Charging Current
|
2,5 A
|
5 A
|
5 A
|
7,5 A
|
10 A
|
10 A
| ENVIRONMENT |
Operating Temperature
|
0 - 40 oC
|
Acoustic Noise
|
<45dBA
|
<45dBA
|
<45dBA
|
<55dBA
|
<57dBA
|
<57dBA
|
Dimension (HxWxD mm)
|
710x265x740
|
1145x485x675
|
1360x550x855
|
Relative Humidity (max.)
|
0-95 % (non condensing)
|
Standards
|
EN-50091-1,2,3 ISO-9001 CE Certified