Bailey created a connection test utility called Talk90. This utility was distributed with the runtime kit in the past, but as of Bailey semAPI 2.0, it is no longer distributed in the runtime kit. It is still distributed with the supervisory control kit.
Running the test utility looks similar to this:
-
1-Establish Point
|
2-Establish Report
|
3-Output Miscellaneous
|
4-Connect Point List
|
5-Disconnect Point List
|
6-Read Value List
|
7-Read Status List
|
8-Read Exceptions
|
10-Output Value
|
11-Output Status
|
12-Module Operation
|
13-Read Block
|
14-Read Next Block
|
15-Read Default Block
|
16-Write Block
|
17-Tune Block
|
18-Delete Block
|
19-ICI Restart
|
20-Read Block Output
|
21-Read Misc Status List
|
22-Read Misc Stat Excep
|
23-Disestablish Point
|
24-Read Excep Report Spec
|
26-Read Problem Report
|
27-Demand Module Status
|
28-Regenerate Specs
|
29-Output General Msg
|
33-Set ICI Status
|
34-Read Work Flag
|
35-Read Value Group
|
36-Disconnect Point Group
|
37-Connect Point Group
|
38-Read Status Group
|
39-Read Misc Status Group
|
40-Output Value Group
|
41-ICI Callup
|
42-ICI Hangup
|
43-Read System Time/Date
|
44-ICI Online/Offline
|
45-Output Misc Group
|
46-Read Ext Prob Report
|
47-Output Status Group
|
100-Connect to ICI
|
101-Disconnect from ICI
|
102-ICI Management
|
103-Quick Commands
|
104-Get Exceptions
|
105-Enet Commands
|
106-Block I/O Commands
|
107-DBUS Commands
|
108-Firmware Commands
|
109-Misc. Module Info
|
110-Decode Error Number
|
|
777-Repeat Last Command
|
888-Next Page
|
999-Exit
|
Option: 100
Logical ICI: 1
Timeout is in seconds.
Timeout: 5
Valid Users:
0 = SHARED
1 = EXCLUSIVE
Type of User: 1
Tagnames: 0 = DO NOT RETURN TAGNAMES, 1 = RETURN TAGNAMES
Tagnames: 0
Option 100 should be used to make sure that at least a connection to the ICI can be made. If the connection is not successful, Bailey should be contacted.
Digital States
For more information regarding Digital States, refer to the Data Archive Manuals.
Digital State Sets
PI digital states are discrete values represented by strings. These strings are organized in PI as digital state sets. Each digital state set is a user-defined list of strings, enumerated from 0 to n to represent different values of discrete data. For more information about PI digital tags and editing digital state sets, see the PI Server manuals.
An interface point that contains discrete data can be stored in PI as a digital tag. A Digital tag associates discrete data with a digital state set, as specified by the user.
A PI tag for the Station Status is normally defined as a digital point. A set should be defined with these states in this order:
-
Manual (unlocked)
-
Auto (unlocked)
-
Cascade (unlocked)
-
Digital Station Failure
-
Manual (locked)
-
Control station bypassed
-
Auto (locked)
-
Cascade (locked)
System Digital State Set
Similar to digital state sets is the system digital state set. This set is used for all tags, regardless of type to indicate the state of a tag at a particular time. For example, if the interface receives bad data from an interface point, it writes the system digital state bad input to PI instead of a value. The system digital state set has many unused states that can be used by the interface and other PI clients. Digital States 193-320 are reserved for OSIsoft applications.
For more information regarding Digital States, refer to the Data Archive Manuals.
System Digital States Written to Tags
During normal operation, the interface may set the status of PI tags to a system digital state under the following circumstances:
-
All tags are set to Intf Shut at interface shutdown, or the state specified in the /stopstat=state parameter.
-
When the interface fails to establish a point in the ICI module, the related PI tags are set to the digital state Configure.
-
When a tag is removed from the interface, the tag status is set to No Data.
-
If there are 10 sequential failures in obtaining exception data from Bailey semAPI, the interface will set all tags to No Data.
-
An input tag is set to Bad Input if Bailey’s BAD QUALITY flag is set or if a digital value is out of range for that tag.
-
An output tag is set to Bad Output if the PI value is a digital state code such as Shutdown or OverRange.