Niagara Browser Access Guide
microsoft visio tutorial
2–9
Binary output commands
Commands to binary output (two-state) objects provide control of such things such as lights, fans, or any load with two-states: inactive and active (off on).
In total, six different binary commands maybe possible, with default names of:

Active—On or Start at the manual level.

Inactive—Off or Stop at the manual level.

Auto—Clears any previously issued command at the manual level. Control falls back to the next-highest priority command (that is either active or inactive).

Emergency Active—On or Start at the emergency (highest) priority level.

Emergency Inactive—Off or Stop at the emergency (highest) priority level.

Emergency Auto—Clears any previously issued command at the emergency level. Control falls back to the next-highest priority command (that is either active or inactive).
Analog output commands
Analog control commands are used for things like establishing a setpoint or manually positioning a damper or valve.
In total, four different commands maybe possible, with default names of: