1-4, Avesto Dan Ta-WPS Office
Transformator tanlaymiz:
TDNS-16000\35-74 Y1
S= 16000 kVA
Un=35kV
VN=38.5 kV
NN=10,5; 6.3kV
Pxx=58 kVt
Rk.z.= 280kVt
Uk.z.= 10 % ot Unom = 3.67kV
Ik.z.= 0,45% ot Inom = 0.76 A
= 16000/1.7*35 = 269 A
Avariya holatida qolishi mumkin bo’lgan transformator yuklamaning oshib ketishiga tekshirib ko’riladi, 2 darajali iste’molchilarni uchishini nazarga olgan holda
1,4SHT Sp 1,4*16000 19100,8 22400 19100,8
Transformator avariya holatidagi tekshirishni o’tdi.
Tamomila ikkita transformator tanlaymiz TDNS -16000kVA.



  1. SBSH-250MN ta’minlash

Iste’molchining quvvati katta bo’lganligi sababli PTPga bitta burg’illash uskunasini ulashga qaror qildik.


= (0,5 * 386*4)/ 0.7 = 1103 kVA
Bu yerda:
kc.gr – guruhning talab koeffitsienti.
Bizda PTP da bitta iste’molchi bo’lganligi sababli uning talab koeffitsientini olamiz.
Rnomi -guruhdagi iste’molchining nominal quvvati, kVt
cos - iste’molchilarning o’rtacha quvvati koeffitsient
cos = 0.7
Barcha SBSH-250MN ta’minlash uchun transformator tanlaymiz:


TMN-1600/6(0,4)


2) Suv chiqarish qurilmasi uchun (vodootlivnaya ustanovka)
= (0,8 * 100)/0.6 = 133 kVA
Barcha suv chiqarish qurilmasi uchun transformator tanlaymiz
TMH-160/6(10)/0,4



  1. Mexanik xizmat ko’rsatish qurilmasi uchun (mexanicheskaya masterskaya)

= (0,3 * 200)/0.7 = 85,7 kVA
Mexanik xizmat ko’rsatish sexi uchun transformator tanlaymiz


TM-160/6(10)/0,4.