Open Systems Manager
Installation and Configuration instruction for information on the Ethernet diagnostic utilities.
7. If the problem cannot be isolated and the INOSM01 manager continues to fail to startup, call service.


TROUBLESHOOTING
LOW BATTERY ON STARTUP - 4
WBPEEUI350001B0
®
LOW BATTERY ON STARTUP
If the INESM01 Ethernet Server Module battery has a low charge, it will not startup automatically on power up. To correct the problem. Pull the INDDM01 module out of the module mounting unit so that it is disconnected from power. Apply power to the INESM01 module fora minimum of hours by inserting it into its module mounting unit slot. After 4 hours, fully insert the INDDM01 module into the module mounting unit so that it is powered and push the reset pushbutton on the INESM01 module. When prompted on the monitor, press
-
- .
NOTE: If the module continues to boot repeatedly instead of showing the correct prompt that there is a hardware failure, replace the
INESM01 module. In setup, change Display Type to the EGA or VGA option.
6. Press to exit setup and boot the system. If the system does not startup, there is a hardware failure.
Replace the INESM01 module.