Open Systems Manager (Front Cover)



Download 0.88 Mb.
View original pdf
Page52/88
Date24.01.2022
Size0.88 Mb.
#58120
1   ...   48   49   50   51   52   53   54   55   ...   88
Open Systems Manager
Dipswitch
Dipswitch Pole
Options Selected
1
2
3
4
5
6
7
8
UMB1 0
1 1
1 0
1 1
1 9600 baud rate, ports 1 and 2.
LMB2 0
0 0
0 0
0 Diagnostics disabled.
LLB3 1
0 1
1 1
1 SCSI port enabled, SCSI address = 3, SCSI parity checking enabled.
UUB0 0
0 0
1 0
0 ROM checksumming enabled, ports 0 and 1 data characteristics 8 data bits, 1 stop bit, no parity, modem password disabled, port addressing mode disabled, checksumming option disabled.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table 3-5. INICT03 Jumper Settings
Jumper Setting
Options
Selected
J1
open
RS-232-C diagnostic port options.
J2 4-3 1 Mbit SRAM device (128 x 8).
J4
open
Machine fault timer disabled. Must be open for normal operation.
J5 30V
Opens the path of -30 VDC in older Network 90 systems. Must beset as shown.


INSTALLATION
SYSTEM START-UP
WBPEEUI350001B0 3 - 19