Open Systems ManagerDipswitch Dipswitch Pole Options Selected 1 2 3 4 5 6 7 8 UMB1 0 1 1 1 0 1 1 1 9600 baud rate, ports 1 and 2. LMB2 0 0 0 0 0 0 Diagnostics disabled. LLB3 1 0 1 1 1 1 SCSI port enabled, SCSI address = 3, SCSI parity checking enabled. UUB0 0 0 0 1 0 0 ROM checksumming enabled, ports 0 and 1 data characteristics 8 data bits, 1 stop bit, no parity, modem password disabled, port addressing mode disabled, checksumming option disabled. NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF. Table 3-5. INICT03 Jumper Settings Jumper Setting Options Selected J1 open RS-232-C diagnostic port options. J2 4-3 1 Mbit SRAM device (128 x 8). J4 open Machine fault timer disabled. Must be open for normal operation. J5 30V Opens the path of -30 VDC in older Network 90 systems. Must beset as shown.