TROUBLESHOOTINGGENERAL TROUBLESHOOTING
WBPEEUI350001B0 5 - 3
c.
Verify that the adapter board jumpers are set correctly.
Refer to Table
3-3
for adapter board jumper settings.
d. Verify that the INESM01 jumpers are set correctly.
Refer to Table
3-2
for INESM01 jumper settings.
e.
Check the ribbon cable connections from the INDDM01
module to the INESM01 module. There should be two cable connections from the INDDM01 module to the INESM01
module: one from the hard disk drive and one from the floppy disk drive (Figure
3-4
).
f.
Check the ribbon cable connection from the INSCS01
module to the SCSI adapter board on the INESM01 mod- ule.
g. Check the ribbon cable connection from the faceplate of the INSCS01 module to the faceplate of the IMMPI01
module.
5. Check the IMMPI01 and INICT03 modules installation.
a. Check the ribbon cable connection from the IMMPI01
module to the INICT03 module.
b. Check the NTMP01 termination unit installation and cable connection to the IMMPI01 module.
c.
Verify that the security key on the NTMP01 termination unit is correctly installed. Refer to the appropriate application programming interface user manual for information on the security key.
d. Verify that the INICT03 dipswitches, jumpers and dip- shunt are set correctly. e.
Check the module mounting unit setup of the I/O
expander bus for the INICI03 interface (refer to the INICI03
instruction for information on isolating the IO expander bus. If the INOSM01 manager
installation checks out, use the
Ethernet diagnostic utilities to examine the Ethernet server database and status (refer to the
INFI-NET Ethernet ServerShare with your friends: