PI BaInfi90 1.8.4.9
/pisdk=0
Use the Int
erface’s default setting
This selection has no effect on whether the interface uses the PI SDK. However, you must not choose this option if you want to run the interface in disconnected startup mode.
Enable PI SDK
Select Enable PI SDK to tell the interface to use the PI SDK. Choose this option if the PI Server version is earlier than xor the PI API is earlier than 1.6.0.2, and you want to use extended lengths for the Tag, Descriptor, ExDesc, InstrumentTag, or PointSource point attributes. The maximum lengths for these attributes are
Attribute
Enable the Interface to use
the PI SDK
PI Server earlier than xor PI
API earlier than 1.6.0.2, without the
use of the PI SDK
Tag
1023 255 Descriptor
1023 26
ExDesc
1023 80
InstrumentTag
1023 32
PointSource
1023 1 However, if you want to run the interface in disconnected startup mode, you must not choose this option. The command line equivalent for this option is
/pisdk=1




PI Interface for Bailey Infi90
71
Appendix Cb bTroubleshooting
The interface normally starts as Windows service. It writes informational and error messages to the
PIPC.LOG
file. So, it is important to look at this file to troubleshoot the interface.
Hardware Configuration
When you install the CIU/ICI module, you need to cut the dipshunt in a specific manner in the termination unit of the CIU. In addition, set the dipswitch of U and U on the CIU module. The dipswitch setting determines the many options on running the CIU. Refer to the hardware manual of the CIU for information about how to set the dipswitch and the dipshunt. The Bailey Engineering WorkStation (EWS) hardware manual provides a recommended dipshunt/dipswitch configuration for the CIU module. OSIsoft suggests that the BaInfi90 interface use this same configuration. The serial cable connecting the interface computer and the CIU/ICI is wired straight through on pins 1- 8 and 20. The best way to test the termination hardware, CIU/ICI module setup, and cable configuration of the CIU is to try using the EWS to substitute for the interface computer. If all hardware settings appear correct and connection problems still exist, try switching pins 2 and 3 in the cable by using a null modem connector.