Safety Critical Element Management Manual


SCE group IC009SCE group title



Download 494.83 Kb.
View original pdf
Page42/54
Date16.09.2023
Size494.83 Kb.
#62078
1   ...   38   39   40   41   42   43   44   45   ...   54
Shell EP 2009.9009 SCE Management Manual
POSITION PAPER 130[shell verification]
SCE group IC009
SCE group title Flare Tip Ignition Systems
Flare Tip Ignition systems to ensure that gas from the flare system does not accumulate and cause a hazard to the
Facility, following planned or emergency depressurisation.
To ensure that gas from the flare system does not accumulate and cause a hazard to the Facility,
following planned or emergency depressurisation.
At system level
SCE group DS001
SCE group title Fire and Gas Detection Fire and Gas Detection
Systems for detection of flammable or toxic gas, or fires.
To detect all flammable gas accumulations, oil mist accumulations, the presence of toxic gases (including asphixiants and narcotics) and all fires and initiate an executive action Flammable Gas Detection System comprising:
o all types of detectors fitted, which may include
Catalytic detectors, Infra-Red Point Detectors,
Infra-Red Beam Detectors and Acoustic Leak
Detectors o gas in service water detection o HVAC gas detection o flammable gas detection functions on main and any additional Fire and Gas panels and outputs to end elements Manual Alarm Call points (MACs) System comprising:
o GPA Call points positioned at various locations around the installation o manual alarm functions on main and any additional Fire and Gas panels and outputs to end elements Oil Mist Detection (OMD) System comprising:
o oil mist detector heads, normally located in areas where oil mists present a risk of fire and explosion o oil mist detection alarm functions on main and additional Fire and Gas panels and outputs to end elements HS Detection System comprising:
o HS detectors, alarm functions on main and additional Fire and Gas panels o outputs to Facility alarm systems including flashing warning beacons and local sounder devices initiated by HS detection.
At system level


Appendix 3 - Guidance on SCE groups and minimum performance assurance levels