To comply to this Rule always ensure that



Download 1.17 Mb.
View original pdf
Page5/9
Date17.04.2022
Size1.17 Mb.
#58629
1   2   3   4   5   6   7   8   9
03 LSR Isolation
Switching Procedures :
Verify Isolation before work begins and use the specified life
protecting equipment

No person shall undertake any repairs, maintenance, alterations, cleaning or testing on HV APPARATUS until such parts of that APPARATUS area) Switched off from all points of supply, made DEAD and proven DEAD
b) ISOLATED and all steps taken to secure with SAFETY PADLOCKS from all points of supply. The keys for the SAFETY PADLOCKS shall be placed in a KEY SAFE or another APPROVED security method shall be used.
c) Connected to EARTH at all points of disconnection from HV supplies to such APPARATUS or between such points and the points of work or testing.
d) Screened where necessary to prevent DANGER and DANGER NOTICES attached.
e) Released for work by the issue of an ELECTRICAL PERMIT-TO-WORK to a CEP who shall be accompanied by another CEP during the progress of the work.
OR Released for testing by the issue of a SANCTION-FOR-TEST to an AEP who shall be accompanied by another AEP or CEP during the progress of the testing. f) And the person receiving the ELECTRICAL PERMIT-TO-WORK or SANCTION-FOR-
TEST is made fully aware of the nature and extent of the work or testing to be done.
g) Any work on LIVE HV conductors or insulators shall be carried out under the LIVE LINE WORKING Rules in Section 8.0 or LIVE LINE WASHING Rules in Section
9.0.

Download 1.17 Mb.

Share with your friends:
1   2   3   4   5   6   7   8   9




The database is protected by copyright ©ininet.org 2024
send message

    Main page