Air Conditioning Laboratory Project 99. 10



Download 1.59 Mb.
Page9/15
Date05.05.2018
Size1.59 Mb.
#48379
1   ...   5   6   7   8   9   10   11   12   ...   15

Rate of Heat removal



(eq. 4)


Power input


(eq. 5)
Procedure:


  1. Measure the temperature and pressure each of the four states described in the

background.

  1. Measure the mass flow rate of refrigerant (read from the indicator on the sensor).

  2. OPTIONAL: Read the voltage and current from the fan motor and the power given by the Power Clamp.

Analysis:




  1. Determine the specific enthalpy h at each of the four states using the refrigerant tables in the back of your thermodynamics text.

  2. Using the answers from (1):

  1. Use eq. 4 to determine the rate of heat removal from the refrigerated space.

  2. Use eq. 5 to determine the power input to the compressor.

  3. Use eq. 4 to determine the rate of heat rejection from the refrigerant to the environment.

  1. Determine the coefficient of performance of the refrigerator and the heat pump using equations 2 and 3 respectively.

  2. OPTIONAL: Compare the power calculated in 2b to the power obtained by reading

voltage and current from the motor of the fan and to the power read from the Power Clamp.