Bailey Infi90 Interface to the PI System 33
RMSC Read(N90 point type The conversion is the same as the other analog point types. RMSC is function code 68. Note that the CIU cannot be in monitor mode if the user wishes to read RMSC points. Seethe Troubleshooting section for details.
4-byte Analog Read(N90 point type This point type is supported by the CIU04 only. It is handled like other analog point types except that the precision is higher (about 7 significant digits) and the range is larger (E to 3.4E38).
4-byte Analog Report(N90 point type This point type is supported by the CIU04 only. This is one of the point types for writing from the PI Server to the Bailey control system. Analog values should be either PI Float or Int points. The range is from -E to E. The output is set to bad quality if the PI value is a system digital state code (such as
SHUTDOWNor
OVER RANGE).
Bailey Database ConversionThe Bailey MCS and OIS Operator Console configuration contains much of the information needed for the PI Point database. The MCS
or OIS can be configured from DBASE files on a personal computer. The same files can be used to create
text files for use with PICONFIG or comma separated value (CSV)
files for use with PI Tag Configurator.
Start by entering DBASE and creating anew database with several
of the same fields as the or
OISTAG.dbffile. The following PI attributes can be extracted.
TagThe field name
in the MCS or OIS database is TAGNAME. The MCS or OIS field is 14 characters long.
DescriptorThe field name in the MCS or OIS database is
TAGDESC. The MCS or OIS field is 32 characters long.