23 09 23 DIRECT DIGITAL CONTROL SYSTEM FOR HVAC 3
PART 1: GENERAL 3
1.1 WORK INCLUDED 3
1.2 SYSTEM DESCRIPTION 3
1.3 APPROVED MANUFACTURERS 5
1.4 QUALITY ASSURANCE 5
1.5 REFERENCE STANDARDS 5
1.6 SUBMITTALS 6
1.7 WARRANTY 7
1.8 RELATED WORK IN OTHER SECTIONS 7
PART 2: PRODUCTS 7
2.1 OPERATOR’S WORKSTATION 7
2.2 WEB INTERFACE 15
2.3 BUILDING CONTROLLER 17
2.4 CENTRAL PLANT AND AIR HANDLER APPLICATION CONTROLLERS 21
2.5 EXPANDABLE CENTRAL PLANT APPLICATION CONTROLLERS 23
2.6 TERMINAL UNIT APPLICATION CONTROLLERS (Heat Pumps, AC Units, Fan-Coils) 25
2.7 WIRELESS MS/TP TRANSCEIVER 26
1.Wireless MS/TP Transceiver shall meet BACnet Addendum q of ANSI/ASHRAE 135-2008 requirements. 26
2.Support multiple BACnet Application Specific Controllers (B-ASC) to a Transceiver MS/TP trunk. 26
3.Support multi-transceiver mesh wireless network topology 26
4.Wireless MS/TP Transceiver shall, at a minimum, support MS/TP BACnet LAN types. They shall communicate directly through this BACnet LAN at 9.6, 19.2, 38.4 and 76.8 Kbps, as a B-ASC BACnet device. 26
5.Standard BACnet object types supported shall include, as a minimum, Analog Value, Binary Value, Device, File, and Program Object Types. 26
6.All proprietary object types, if used in the system, shall be thoroughly documented and provided as part of the submittal data. All necessary tools shall be supplied for working with proprietary information. 26
1.Include a 32 Bit processor 26
2.Include two selectable internal antennae with perpendicular orientation 26
3.Support external antenna using industry standard SMA connector type 26
4.Support connection to 2.4 GHz (IEEE Std 802.15.4-2003 compliant) Wireless Wall Sensors (Battery powered). 26
5.Meet the requirements of Listed Underwriters Laboratory for Open Energy Management Equipment (PAZX) under the UL Standard for Safety 916. 26
6.Meet the requirements of EMC Directive (European CE Mark) EN 60950. 26
7.Meet the requirements for FCC Part 15, Class B. 27
8.Meet the requirements for EU Wireless: EN300328-1 2.4 GHz Spread Spectrum, EN301489-1:2000 Standard. 27
9.Be powered by 24VAC power. 27
1.All configuration and point data shall be stored on board transceiver in Flash Memory. 27
2.No batteries shall be needed to retain configuration data. 27
3.Configuration of Wireless MS/TP Transceiver shall be completely modifiable in the field over installed BACnet LANs or remotely using modem interface. 27
4.Wireless MS/TP communication shall be encrypted to 128 bit AES encryption standard. 27
1.Support up to Fifty (50) wireless wall sensors simultaneously. 27
2.Wireless wall sensors shall operate in the 2.4 GHz (IEEE Std 802.15.4-2003 compliant) radio frequency 27
3.Support temperature, temperature and humidity, and temperature, setpoint and after-hours override wireless wall sensor types. 27
4.Wireless communication shall be encrypted to 128 bit AES encryption standard 27
1.Wireless wall sensor shall use solid-state sensor(s) and shall be packaged in aesthetically pleasing enclosure. 27
2.Sensor shall provide override function, warmer/cooler dial for set point adjustment. Override time shall be stored in controller and be adjustable on a zone-by-zone basis. Adjustment range for warmer/cooler lever shall also be stored in EEPROM on controller. 27
3.There shall be a mechanical means the lock the wall sensor to the base to prevent theft and vandalism 27
4.The wireless range in open air shall meet or exceed 300 ft. The strength of the wireless signal must be indicated at the wireless sensor to aid in placement and trouble shooting. 27
5.The receiver shall have a wireless communications received light that indicates the proper communication is occurring. 27
6.The wireless wall sensor and receiver must be paired in an addressable mean to facilitate easy replacement and reassignment. 27
7.Temperature shall be accurate to +/- 0.5 degree Celsius from 12–30 degrees Celsius. 27
8.Humidity sensor shall be accurate to +/-3% RH from 11-89% RH. 27
9.Shall run on two AA Lithium batteries; providing a minimum battery life of 5 years. Low battery power shall be indicated on the unit via an LED and also readable as a BACnet Object. 27
10.Shall use 2.4 GHz radio frequency (IEEE Std 802.15.4-2003 compliant) 28
11.Wireless communication shall be encrypted to 128 bit AES encryption standard. 28
2.8 VAV BOX CONTROLLERS—SINGLE DUCT 28
2.9 TOUCH SCREEN COMMUNICATING THERMOSTAT 29
2.10 AUXILIARY CONTROL DEVICES 30
2.11 ELECTRONIC ACTUATORS AND VALVES (insert as required, sample requirements follow) 32
2.12 ENCLOSURES 38
PART 3: EXECUTION 39
3.1 EXAMINATION 39
3.2 INSTALLATION (GENERAL) 39
3.3 LOCATION AND INSTALLATION OF COMPONENTS 39
3.4 INTERLOCKING AND CONTROL WIRING 39
3.5 DDC OBJECT TYPE SUMMARY 40
3.6 FIELD SERVICES 40
3.7 AS-BUILT DOCUMENTATION REQUIRED 40
3.8 TRAINING 40
3.9 DEMONSTRATION 41
23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 42
Part 1: GENERAL 42
The Bidder shall be regularly engaged in the design, installation and maintenance of BAS systems and shall have demonstrated technical expertise and experience in the design, installation and maintenance of BAS systems similar in size and complexity to this project. Bidders shall provide a list of at least 10 projects, similar in size and scope to this project completed within the past 3 years.