Bailey Infi90 Interface to the PI System 43
Baud RateThe Baud Rate parameter specifies the data rate of the COM port. The only acceptable values are 1200, 2400, 4800, 9600, or 19200 bps.
(-baudrate=#)PortThe Port parameter specifies the COM port of the Windows computer for communications to the Bailey CIU. Use a value of 1 for COM, a value of 2 for COM, and soon.
(-port=#)CIU #The CIU# parameter is a user-specified positive number that corresponds to a point’s Location attribute. Each instance of the Interface uses the Pointsource and CIU# parameters to identify uniquely its particular list of points to service.
(-CIU#=#)CIU Type #The CIUtype parameter specifies the CIU version number from 1 to 4, inclusive.
(-CIUtype=#, Default 3)
Debug LevelThe Debug Level
parameter specifies the Interface's
debugging level, from 0 to 3, inclusive. When Debug Level is nonzero, the Interface prints debugging messages.
The higher the debugging level, the more messages the Interface prints.
(-debuglevel=#, Default 0 (no debugging))# of exception calls before delay Startup Command File44
This parameter specifies the number of exception calls before delay, from 1 to 100, inclusive.
(-cnt=#, Default 20)Time to delay between callsThis parameter specifies the number of seconds to delay between calls, from 0.1 to 30, inclusive.
(-delay=#, Default 2)Enable Output PointsSelect whether or not to enable Output Points. Enable enables them, 0 – Disable disables them.
(-outputflag=#, Default 1)Enable exception screeningCheck this box to enable CIU exception reporting screening.
Share with your friends: