Ges v-series – Single Phase Input, Single Phase Output



Download 315.62 Kb.
Page5/5
Date09.06.2018
Size315.62 Kb.
#54211
1   2   3   4   5

BATTERY REPLACEMENT





  1. Your battery should run anywhere from 3-5 years before it needs to be replaced.

  2. Please follow the instructions below for easy, trouble free, battery replacement.

  3. Turn the UPS off (follow procedure previously mentioned)

  4. Unplug the UPS from utility power source and disconnect all connected loads.

  5. Disconnect AC power cord from unit.

  6. Turn unit upside down and using a phillips screw driver, unscrew the four (4) screws holding the top of the unit to the bottom. Put screws in a safe place for reconnection.

  7. Holding the top together firmly with the bottom, turn the entire unit right side up.

  8. Carefully lift top cover off and place it to the side. The connecting wires and electronics will be exposed. Be careful not to touch any inner components when changing the battery.

  9. Remove the two (2) connecting wires from the battery.

  10. Y
    Caution:

    Do not dispose of battery in a fire. Do not attempt to open the battery. When replacing the battery use tools with insulated handles and remove watches, rings, etc…

    ou can now easily remove the battery from the unit



  1. Place your new battery in the same position, direction and reconnect the wires. The red wire to the positive (+) pole and black wire to the negative (-) pole.

  2. Reverse steps 5, 4 and 3 (in that order) to reassemble the unit.

  3. Follow start-up instructions in order to properly reconnect your equipment.
  1. TROUBLESHOOTING


Please follow the guidelines below for common problems:


  • Check UPS input plug and wiring.

  • Check UPS input voltage.

Please prepare the information as follows for service personnel:




  • UPS model number and serial number

  • Description of problem(s) in detail.



    1. General Problems





Problems

Possible causes

Solution

UPS has no reaction while AC power is connected

Breaker at back panel open

No AC input

UPS fault

Battery failure



Replace Fuse / Switch breaker on

Check AC power

Call for service

Call service center to replace batteries



UPS has no reaction while AC power is connected, yet starts after pushing power on / off switch

Breaker at back panel open

No AC input

UPS AC detecting circuit fail


Switch breaker
Check AC power

Call for service

UPS goes into back-up mode while connected to AC power

Utility voltage or frequency abnormal

UPS AC detecting circuit failure



Check AC power

Call for service



Battery can not provide normal back-up power in the event of a blackout

Battery deteriorated

Batteries not fully charged

Battery charger damaged


Charge batteries and reset

If that doesn’t work call for service



After AC connected to UPS, alarm sounds short and fast beeps and UPS shuts down

Abnormal utility power

Check input power
  1. SPECIFICATIONS


V-SERIES

MODEL NO.

GES-325V

GES-425V

GES-525V

GES-625V

GENERAL

MAXIMUM CAPACITY

350VA / 210W

425VA / 255W

525VA / 315W

625VA / 375W

UPC ORDER CODE

825433 20000

825433 20100

825433 20200

825433 20300

INPUT

NOMINAL VOLTAGE

120VAC (optional 220VAC)

VOLTAGE RANGE

+ / - 25%

FREQUENCY RANGE

50 or 60 Hz (+ / - 5%)

OUTPUT

NOMINAL VOLTAGE

120VAC

VOLTAGE REGULATION

+ / - 13% of nominal

CURRENT

2.7A

3.54A

4.36A

5.2A

FREQUENCY

50 / 60Hz (Auto Detected)

WAVEFORM (ON BATTERY)

PWM (Pulse Width Modulated) or Modified Sine Wave

POWER FACTOR

< 0.6

CREST FACTOR

3:1 (on battery)

TRANSFER TIME

2 - 4 ms (Typical)

OUTLETS

3

3

3

3



BATTERY

BATTERY TYPE

SEALED LEAD ACID - MAINTENANCE FREE

QUANTITY

1

1

1

1

VOLTAGE

12VDC

RECHARGE TIME

4 HOURS; RECOVERY = 90%, TYPICALLY

BACKUP POWER TIME

FULL LOAD

 22 MIN.

 20 MIN.

 17 MIN.

 15 MIN.

HALF LOAD

 40 MIN.

 30 MIN.

 25 MIN.

 22 MIN.

PENTIUM & 17" MON

 15 MIN.

 15 MIN.

 15 MIN.

 15 MIN.

PROTECTION

OUTPUT SHORT

YES

ABNORMAL VOLTAGE

YES

MODEM OR NETWORK

SINGLE LINE (2 wire RJ-11) / NETWORK (UTP, RJ-45) COMPATIBLE JACKS

I/O NOISE PROTECTION

COMMON & NORMAL MODE NOISE SUPPRESSION

I/O SPIKE & TRANSIENT PROTECTION

YES

INTERFACE

COMMUNICATION

RS-232

LED DISPLAY

Normal / Back-up / Low Battery

AUDIBLE ALARMS

On Battery, Low Battery, Overload, Fault


ENVIRONMENT

OPERATING TEMPERATURE

0 - 40°C (32 - 104°F)

HUMIDITY

0% ~ 90% (Non-Condensing)

AUDIBLE NOISE

 40 dBA AT 1 METER FROM UNIT

SAFETY APPROVAL

SAFETY

cUL, UL1778, CSA C22.2

EMI / RFI

FCC CLASS B

SURGE / TRANSIENT

IEEE C62.41 CAT.A

PHYSICAL DATA

WxDxH mm (in.)

97 x 320 x 135 (3.8 x 12.6 x 5.3)

WEIGHT in kg (lbs)

5.8 (12.8)

5.8 (12.8)

6.2 (13.7)

6.5 (14.3)

RACK-MOUNT MODELS

MODEL NO.

Available Consult Manufacturer

UPC Order Code




WxDxH mm (in.)




WEIGHT in kg (lbs)



  1. CONTACT INFORMATION




    1. Additional Purchases or Upgrades



Always On UPS Systems Inc.

Bldg 1 – 150 Campion Road,

Kelowna, BC, Canada, V1X 7S8

Phone: (250) 491-9777 Ext 451

Fax: (250) 491-9775

Email: sales@alwayson.com

Website: www.alwayson.com

    1. QA / Warranty Questions



Always“On UPS Systems Inc.

Bldg 1 – 150 Campion Road,

Kelowna, BC, Canada, V1X 7S8

Phone: (250) 491-9777 Ext 209

Fax: (250) 491-9775

Email: qa@alwayson.com

Website: www.alwayson.com

    1. Software Questions



Always“On UPS Systems Inc.

Bldg 1 – 150 Campion Road,

Kelowna, BC, Canada, V1X 7S8

Phone: (250) 491-9777 Ext 204

Fax: (250) 491-9775

Email: webmaster@alwayson.com



Website: www.alwayson.com



Download 315.62 Kb.

Share with your friends:
1   2   3   4   5




The database is protected by copyright ©ininet.org 2024
send message

    Main page