Control Valves Basics - Sizing & Selection
FMD3x00 98 DB Initialize (5), configuration-and-evaluation-software-pi-9045582-en-gb, configuration-and-evaluation-software-pi-9045582-en-gb, Document, colour present
Lift (open)
Change %
Flowrate
Change %
30%
5
GPM
10%
60%
40%
8
GPM


10%
60%
50%
12.8
GPM These types of valves are commonly used for pressure control applications and are most suitable for applications where a high variation in pressure drop is expected.
Quick opening valve characteristics
A quick opening valve plug produces a large increase inflow fora small initial change in stem travel. Near maximum flow is reached at a relatively low percentage of maximum stem lift. Quick opening plugs are normally utilized in two position “On-Off” applications but maybe used in some linear valve applications. This is possible because of its initial linear characteristic at a low percentage of stem travel. The slope of this linear region is very steep which produces a higher initial gain than the linear plug but also increases the potential instability of the control valve.