• Emergency Set—Set an output state at the emergency priority level. A secondary popup provides a selection list of defined-states that you pick from. • Emergency Auto—Clears any previously set output state at the emergency level. Control falls back to the state set at the next-highest priority level. Figure 2-9 Example multi-state command dialog. Override control commands Override commands maybe available to set values for analog, binary, and multi-state outputs fora duration that you specify, in minutes. This timed override occurs at a pre-programmed priority level. For analog or multi-state overrides, these commands are available: