Oil Tanker Construction


Ventilation and gas-freeing



Download 1.08 Mb.
Page33/60
Date16.12.2020
Size1.08 Mb.
#54495
1   ...   29   30   31   32   33   34   35   36   ...   60
155646687-Oil-Tanker-Construction-Rules

Ventilation and gas-freeing

  • Where flammable liquids with a flash point of 60 °C or below are carried, the in- and outlet openings of venting systems are to be fitted with approved flame arresters.
  • Vents for the discharge of large volumes of air or gas during cargo and ballast handling operations are to be designed in accordance with the following principles:
  • Depending on the height of the vents, these shall allow the free flow of vapour mixtures or achieve a minimum velocity of 30 m/s.
  • The vapour mixtures are to be discharged vertically upwards.
  • The clear section of vents shall be designed in accordance with the maximum loading rate taking into account a gas evolution factor of 1.25.