On substances that deplete the ozone layer


Annex to chapter 2 - safety standards and regulations



Download 1.63 Mb.
Page19/51
Date20.10.2016
Size1.63 Mb.
#6027
1   ...   15   16   17   18   19   20   21   22   ...   51



Annex to chapter 2 - safety standards and regulations


With the introduction and potentially wide use of refrigerants that are flammable, have higher toxicity and/or operate at notably higher pressures than the conventional ODS refrigerants or alternative non-flammable HFC refrigerants, consideration of safety matters has become more important. Accordingly, more attention is presently being paid to the requirements of safety standards and regulations that directly relate to refrigerants that exhibit these characteristics. This section summarises the main implications.

Safety classification of refrigerants
The most widely used classification of substances under the UN, where so-called dangerous goods receive a classification according to their main hazards.

Within the RAC industry, a different classification scheme is applied, where most refrigerants are assigned a safety classification, which is a function of toxicity and flammability. The classification scheme is adopted by such standards as, ISO 817 and draft EN 378. An overview of this was given in section 2.1.4, see also Table 2-2.

The toxicity classification is based on whether toxicity has or has not been identified at concentrations of less than 400 ppm by volume, based on data used to determine the threshold limit value – time weighted average (TLV-TWA) or consistent indices. There are two toxicity classes:


  • Class A: no chronic toxicity effects have been observed below 400 ppm

  • Class B: chronic toxicity effects have been observed below 400 ppm

The flammability classification depends upon whether or not the substances can be ignited in standardised tests, and if so, what the lower flammability limit (LFL) and the heat of combustion are. There are three flammability classes (values according to ISO 817):

  • Class 1: do not show flame propagation when tested in air at 60°C and standard atmospheric pressure

  • Class 2L: as Class 2 but with a (laminar) burning velocity of less than 0.10 m/s

  • Class 2: exhibit flame propagation when tested at 60°C and atmospheric pressure, but have a LFL higher than 3.5% by volume, and have a heat of combustion of less than 19,000 kJ/kg

  • Class 3: exhibit flame propagation when tested at 60°C and atmospheric pressure, but have an LFL at or less than 3.5% by volume, or have a heat of combustion that is equal to or greater than 19,000 kJ/kg

Class 2L is now included in ISO 817, ISO 5149 and proposed for inclusion in EN 378. It is primarily intended to differentiate between HFC-152a and the remainder of class 2 refrigerants (such as R-717, HFC-32 and HFC-1234yf), which tend to be more difficult to ignite and is less likely to evolve overpressures that could cause damage.

Typically, a “higher” the classification – that is toxicity Class B instead of Class A, and flammability Class 3 instead of Class 1 – means that the refrigerating system has more onerous design requirements associated with it, in order to handle the higher risk presented by the refrigerant.



Lower Flammability Limit

The lower flammability limit (LFL) of flammable refrigerants is typically applied as a constraint to the amount of refrigerant that can be released into a room or enclosure, as it represents the smallest quantity that, when in the presence of an active source of ignition, could sustain a flame.



Acute Toxicity Exposure Limit

The acute toxicity exposure limit (ATEL) of any refrigerant may also applied as a constraint to the amount of refrigerant that can be released into a room or enclosure, as it represents the smallest quantity that could impose adverse toxicological effects onto occupants.



Practical Limit

There is a further safety measure for the application of refrigerants, termed the practical concentration limit (PL). This represents the highest concentrations level in an occupied space which will not result in any escape impairing (i.e., acute) effects. Thus, it is principally, the lowest “dangerous” concentration of a refrigerant, with a safety factor applied. The estimation of PL is based on the lowest of the following:



  • Acute toxicity exposure limit (ATEL), based on mortality (in terms of LC50) and/or cardiac sensitisation, and/or anaesthetic or central nervous system (CNS) effects

  • Oxygen deprivation limit (ODL)

  • 20% of the lower flammability limit (or 25% in ASHRAE 34)

For class A1 (and A2L) and class B refrigerants, the PL is normally based on the ATEL, whereas for A2 and A3 refrigerants it is normally dictated by the LFL. For some refrigerants the PL is based on historical use experience.

Relevant safety standards

Unlike conventional refrigerants, almost all of the low GWP refrigerants have safety characteristics, which demand greater attention, such as flammability, toxicity and higher operating pressures. Safety standards (and industry codes of practice) provide guidance to offset the additional risks posed by the more hazardous characteristics of the substances.



Safety standards are generated internationally (e.g., ISO, IEC), regionally (e.g., EN) and nationally. Often there are parallels or alignment between standards of similar scope across these different levels, although individual countries elect to adopt alternative requirements than those at international level. The main international and regional standards that affect design and construction of systems as a function of refrigerant selection are listed in Table A2-1 and the scope according to the sections in this report is identified.

Table A2-1: Scope of different international and regional safety standards for AC&R systems

Chapter/Sector

IEC 60335-2-24

IEC 60335-2-40

IEC 60335-2-89

ISO 5149

ISO 13043

EN 378

3 / Domestic refrigeration

×
















4 / Commercial refrigeration







×

×




×

5 / Industrial systems










×




×

6 / Transport refrigeration










[×]




×

7 / Air-to-air air conditioners
and heat pumps




×




×




×

8 / Water heating heat pumps




×




×




×

9 / Chillers




×




×




×

10 / Vehicle air conditioning













×




The three important characteristics that differ amongst refrigerants that have a strong influence over the design and construction requirements are pressure, flammability and toxicity. Typically, the more severe these characteristics (i.e., higher pressure, higher flammability, higher toxicity), the more onerous the requirements are. In principle, these more onerous requirements are intended to offset the potentially worse consequences arising from the more severe characteristics. Table A2-2 provides a summary of the main measures that may require attention when adopting such refrigerants

Table A2-2: Main measures to be considered for substances with greater pressure, toxicity and/or flammability

Greater pressure

Greater toxicity

Greater flammability

Thicker materials/higher pressure rating for pipes and components

Additional use of pressure relief devices and/or pressure limiting devices

Higher competencies for workers involved in construction of components and assemblies


Stricter limits on the quantity of refrigerant in occupied spaces

Limited use in more densely populated areas

Use of gas detection, alarms and emergency ventilation

Provision of personal protective equipment



Stricter limits on the quantity of refrigerant in occupied spaces

Use of gas detection, alarms and emergency ventilation

Prohibition of items that could act as sources of ignition

Warnings/signage



One critical issue within the various standards, particularly for flammable and higher toxicity refrigerants is the allowable and maximum refrigerant charge. Depending upon the type of occupancy, different approaches are used to determine such values. Table A2-3 provides some indicative charge limits (per refrigerant circuit) based on ISO 5149:2014 for selected situations and a number of commonly discussed refrigerants.

Although these safety standards cover requirements for flammable refrigerants, it is important to highlight that in many countries specific standards for equipment using flammable gases are available and are generally linked to legislation. For example, in Europe products which are placed on the market (except for those that are exempt) and that use flammable gases (including refrigerants) must meet the essential health safety requirements (EHSRs) of the Atex product directive (94/9/EC). By following the Atex harmonized standards, there is a presumption of conformity. Since none of the AC&R safety standards are harmonized to Atex, safety standards such as EN 1127-1 can be used for the evaluation of flammability safety; provided that AC&R equipment meets the requirements of such standards then deviations from the AC&R standards is acceptable if equivalent safety is demonstrated (for example, where larger refrigerant charges are needed.) In addition to meeting the EHSRs, the general approach prescribed by flammable gas standards and regulations is summarised:



  • Identification of explosion hazards and determination of the likelihood of occurrence of a hazardous atmosphere;

  • Identification of ignition hazards and determination of the likelihood of occurrence of potential ignition sources;

  • Estimation of the possible effects of an explosion in case of ignition;

  • Evaluation of the risk and whether the intended level of protection has been achieved;

  • Consideration of and application of measures to reduce of the risks

Table A2-3 provides the result of calculations for determination of allowable and maximum charge sizes (per refrigerant circuit) for a selection of commonly discussed refrigerants.

Table A2-3: Summary of PL and charge size limits for selected refrigerant and occupancies according to ISO 5149



Refrigerant Class

Example Refrigerant

Practical Limit (g/m3)

Allowable Charge in a 15 m2 Occupied Space (comfort) (kg)

Allowable Charge in a 15 m2 Occupied Space (general)* (kg)

Max. Charge in an Occupied Space (Occupancy A)

Max Charge in Open Air or Machinery Room

Max Charge for a Ventilated Enclosure

A1

HCFC-22

300

11.3

11.3

PL×RVᵟ

no limit

no limit

HFC-134a

250

9.4

9.4

R-404A

520

19.5

19.5

R-407C

310

11.6

11.6

R-410A

440

16.5

16.5

R-744

100

3.8

3.8

A2L

HFC-32

61

1.3 – 4.9

2.3

12 (60‡)

no limit

60

HFC-1234yf

58

1.2 – 4.5

2.2

11 (56‡)

no limit

56

HFC-1234ze

61

1.3-4.8

2.3

12 (59‡)

no limit

59

A2

HFC-152a

27

0.5 – 1.7

1.0

3.4

no limit

17

A3

HC-600a

11

0.1 – 0.4

0.3

1.5

no limit

5.6

HC-290

8

0.1 – 0.4

0.3

1.5

no limit

4.9

HC-1270

8

0.1 – 0.3

0.3

1.5

no limit

6.0

B2L

R-717

0.35

0.01

0.01

4.5

no limit

23

ᵟ For systems with multiple indoor heat exchangers a higher charge may be allowed depending on circumstances; ‡ For systems with multiple indoor heat exchangers; † Depending upon installation conditions; * 2.5 m high room

Note: Allowable and maximum charges are per individual refrigerant circuit

Note: The values provided within this table are indicative and determination of refrigerant charge size limits for particular types of systems and installation locations requires the use of the standard and the values within this table should not be taken as a substitute.



Download 1.63 Mb.

Share with your friends:
1   ...   15   16   17   18   19   20   21   22   ...   51




The database is protected by copyright ©ininet.org 2024
send message

    Main page