Mounting Requirements The INOSM01 manager requires six adjacent module mounting unit (MMU) slots for mounting. Figure 3-1 shows the order in which the interface modules mount in the module mounting unit. Three of the mounting spaces on the two field termination panels are required for mounting termination units. Server Module Termination Unit Installation One of three sets of jumpers on the server module termination unit require setting before installation. These jumpers (J, J2 and J) setup operation for the type of cable being used on the Ethernet network. All other jumpers are reserved for future use and should be open. Set the NTSM01 jumper blocks required for the cable type that is being used. Table lists NTSM01 jumper settings and connector pinouts. Short a jumper to select an option. Figure shows the server module termination unit circuit board layout.
INSTALLATION OPEN SYSTEMS MANAGER INSTALLATION WBPEEUI350001B0 3 - 3 Figure 3-1. INOSM01 Module Mounting Sequence Bailey S HD L1 L2 STOP KEYBD RESET Bailey 1 Bailey 1 Bailey Bailey Bailey T00569A IMMPI01 INICT03 INNIS01 INSCS01 INESM01