PI BaInfi90 1.8.4.9
Startup Command File
34

bainfi90 Page
The BaInfi90 interface ICU Control for PI ICU has one section. A yellow text box indicates that an invalid value has been entered or that a required value has not been entered.
Baud Rate
The Baud Rate parameter specifies the data rate of the COM port. The only acceptable values are 1200, 2400, 4800, 9600, or 19200 bps. (
/baudrate=#
)
Port
The Port parameter specifies the COM port of the Windows computer for communications to the Bailey CIU. Use a value of 1 for COM, a value of 2 for COM, and soon. (
/port=#
)
CIU #
The CIU# parameter is a user-specified positive number that corresponds to a point’s Location attribute. Each instance of the interface uses the Pointsource and CIU# parameters to identify uniquely its particular list of points to service. (
/CIU#=#
)
CIU Type #
The CIUtype parameter specifies the CIU version number from 1 to 4, inclusive.
(
/CIUtype=#
, Default 3)



PI Interface for Bailey Infi90
35
Debug Level
The Debug Level parameter specifies the interface's debugging level, from 0 to 3, inclusive. When Debug Level is nonzero, the interface prints debugging messages. The higher the debugging level, the more messages the interface prints. (
/debuglevel=#
, Default 0, that is, no debugging)
# of exception calls before delay
This parameter specifies the number of exception calls before delay, from 1 to 100, inclusive.
(
/cnt=#
, Default 20)
Time to delay between calls
This parameter specifies the number of seconds to delay between calls, from 0.1 to 30, inclusive. (
/delay=#
, Default 2)