PI BaInfi90 1.8.4.9
RMSC Read
N90 point type 19 The conversion is the same as for the other analog point types. RMSC is function code 68. Note that the CIU cannot be in monitor mode if the user wishes to read
RMSC points. See section Troubleshooting for details.
4-byte Analog Read
N90 point type 21 This point type is supported by the CIU04 only. It is handled like other analog point types except that the precision is higher (about 7 significant digits) and the range is larger (E to E.
4-byte Analog Report
N90 point type 22 This point type is supported by the CIU04 only. This is one of the point types for writing from the PI Server to the Bailey control system. Analog values should be either PI Float or Int points. The range is from -E to E. The output is set to bad quality if the PI value is a system digital state code (such as SHUTDOWN or OVER RANGE.
Bailey Database Conversion
The Bailey MCS and OIS Operator Console configuration contains much of the information needed for the PI Point database. The MCS or OIS can be configured from DBASE files on a personal computer. The same files can be used to create text files for use with PICONFIG or comma separated value (CSV) files for use with PI Tag Configurator. Start by entering DBASE and creating anew database with several of the same fields as the
MCSTAG.dbf or
OISTAG.dbf file. The PI attributes listed below can be extracted.


PI Point Configuration
30

Tag
The field name in the MCS or OIS database is TAGNAME. The MCS or OIS field is 14 characters long.
Descriptor
The field name in the MCS or OIS database is TAGDESC. The MCS or OIS field is 32 characters long.
EngUnits
The field name in the MCS or OIS database is EUDESC.
Zero
The field name in the MCS or OIS database is VAL.
Span
The field name in the MCS or OIS database is SPAN.
Location2
For CIU04's, this is 256 times the MCS or OIS field LOOP (also known as ring) plus the
MCS or OIS field PCU. For other CIU's, this is the field PCU.