Pi bailey Sem api interface Manual


Testing Connection to ICI



Download 2.52 Mb.
Page10/43
Date01.09.2022
Size2.52 Mb.
#59441
1   ...   6   7   8   9   10   11   12   13   ...   43
PI BaSemAPI Manual
PI BASemAPI, UniInt Interface User Manual

Testing Connection to ICI


Bailey created a connection test utility called Talk90. This utility was distributed with the runtime kit in the past, but as of Bailey semAPI 2.0, it is no longer distributed in the runtime kit. It is still distributed with the supervisory control kit.
Running the test utility looks similar to this:

1-Establish Point

2-Establish Report

3-Output Miscellaneous

4-Connect Point List

5-Disconnect Point List

6-Read Value List

7-Read Status List

8-Read Exceptions

10-Output Value

11-Output Status

12-Module Operation

13-Read Block

14-Read Next Block

15-Read Default Block

16-Write Block

17-Tune Block

18-Delete Block

19-ICI Restart

20-Read Block Output

21-Read Misc Status List

22-Read Misc Stat Excep

23-Disestablish Point

24-Read Excep Report Spec

26-Read Problem Report

27-Demand Module Status

28-Regenerate Specs

29-Output General Msg

33-Set ICI Status

34-Read Work Flag

35-Read Value Group

36-Disconnect Point Group

37-Connect Point Group

38-Read Status Group

39-Read Misc Status Group

40-Output Value Group

41-ICI Callup

42-ICI Hangup

43-Read System Time/Date

44-ICI Online/Offline

45-Output Misc Group

46-Read Ext Prob Report

47-Output Status Group

100-Connect to ICI

101-Disconnect from ICI

102-ICI Management

103-Quick Commands

104-Get Exceptions

105-Enet Commands

106-Block I/O Commands

107-DBUS Commands

108-Firmware Commands

109-Misc. Module Info

110-Decode Error Number




777-Repeat Last Command

888-Next Page

999-Exit


Option: 100
Logical ICI: 1
Timeout is in seconds.
Timeout: 5
Valid Users:
0 = SHARED
1 = EXCLUSIVE
Type of User: 1
Tagnames: 0 = DO NOT RETURN TAGNAMES, 1 = RETURN TAGNAMES
Tagnames: 0
Option 100 should be used to make sure that at least a connection to the ICI can be made. If the connection is not successful, Bailey should be contacted.

Digital States


For more information regarding Digital States, refer to the Data Archive Manuals.
Digital State Sets

PI digital states are discrete values represented by strings. These strings are organized in PI as digital state sets. Each digital state set is a user-defined list of strings, enumerated from 0 to n to represent different values of discrete data. For more information about PI digital tags and editing digital state sets, see the PI Server manuals.
An interface point that contains discrete data can be stored in PI as a digital tag. A Digital tag associates discrete data with a digital state set, as specified by the user.
A PI tag for the Station Status is normally defined as a digital point. A set should be defined with these states in this order:

  • Manual (unlocked)

  • Auto (unlocked)

  • Cascade (unlocked)

  • Digital Station Failure

  • Manual (locked)

  • Control station bypassed

  • Auto (locked)

  • Cascade (locked)
System Digital State Set

Similar to digital state sets is the system digital state set. This set is used for all tags, regardless of type to indicate the state of a tag at a particular time. For example, if the interface receives bad data from an interface point, it writes the system digital state bad input to PI instead of a value. The system digital state set has many unused states that can be used by the interface and other PI clients. Digital States 193-320 are reserved for OSIsoft applications.
For more information regarding Digital States, refer to the Data Archive Manuals.