A.N. Tombazis and Associates | Athens Greece (38°02’ , 23°80’ , 70 m)

CLIMATE

annual avg. temp. [°C]

18.9



month. avg. max temp. [°C]

23.6

month. avg. min temp. [°C]

15.5

heating degree days [Kday]

1.388

cooling degree days [Kday]

271

design indoor temp. H [°C]

18

design indoor temp. C [°C]

27

INFORMATION ON BUILDINGY AND USE

occupancy

office



number of occupants

50

utilisation

8am-6pm

completion

1995

refurbishment

-

number of floors

3

total floor area [m²]

1.000

total conditioned area [m²]

600

total volume [m³]

1.296

area-to-volume ratio [m-1]

0.7

BUILDING ENVELOPE

shading system

exterior fabric blinds, automatic operation, shading factor 0.5

U-values [W/(m²K)]

exterior wall: 0.25 | window: 2.7 | roof: 0.27 | avg. value of building: 0.26

window

2-pane glazing | g-value: 0.7 | area: 53 m² | window-façade-ratio: 15-81 %

CONCEPT COOLING

air-to-air heat pump (a-a-HP) | ambient air (AA) | electricity (E) | free (f)

mechanical (m) | mechanical ventilation (MV) | night-time ventilation (NV-f)

split units (SP)



environmental heat sink

AA

energy carrier

E

cooling system

a-a-HP, SU

power of system [kWtherm]

37

distribution system

air

VENTILATION CONEPT

operable windows

yes

night ventilation

f+m

mechanical ventilation

yes

air-change rate [h-1]

no info

dehumidification of air

no

pre-cooling of air

yes

THERMAL COMFORT PERFORMANCE IN SUMMER

year(s) of monitoring

2008-09

en15251_gre

gre_08_en15251_

year of evaluation

2008-09

number of rooms

6

interval of measurements

60 min

ambient air temperature

at building

design temperature [°C]

27

adaptive, class II (up)a

97

adaptive, class II (low)b

90

avg. room temperature [°C]c

23-27

temp. drift day [K]c

0.8-2.2

POE

yes

humidity comfort, class II

82

MONITORING RESULTS AND BUILDING SIGNATURE

COOLING



gre_08

useful energy [kWhtherm/m²a]

19.5

final energy [kWhend/m²a]

18.8

primary energy kWhprim/m²a]

47.0

HEATING

useful energy [kWhtherm/m²a]

21.5

final energy [kWhend/m²a]

29.2

primary energy kWhprim/m²a]

73.0

VENTILATION

final energy [kWhend/m²a]

1.2

primary energy kWhprim/m²a]

3.0

LIGHTING

final energy [kWhend/m²a]

2.7

primary energy kWhprim/m²a]

6.8

APPLIANCES/PLUG LOADS

final energy [kWhend/m²a]

27.8

TOTAL BUILDING

final energy [kWhend/m²a]

51.9

primary energy kWhprim/m²a]

129.8

onsite generation of energy

no

(a) upper comfort boundaries, (b) lower comfort boundaries, (c) during occupancy



ASA Holding Company | Bucharest Romania (44°43’ , 26°9’ , 55 m)

CLIMATE

annual avg. temp. [°C]

10.5



month. avg. max temp. [°C]

17.3

month. avg. min temp. [°C]

7.4

heating degree days [Kday]

2.699

cooling degree days [Kday]

132

design indoor temp. H [°C]

18

design indoor temp. C [°C]

26

INFORMATION ON BUILDINGY AND USE

occupancy

office

asa east-1

number of occupants

24

utilisation

8am-5pm

completion

1940

refurbishment

-

number of floors

4

total floor area [m²]

634

total conditioned area [m²]

292

total volume [m³]

1.952

area-to-volume ratio [m-1]

0.32

BUILDING ENVELOPE

shading system

exterior wood blinds, manual operation, shading factor 0.3

U-values [W/(m²K)]

exterior wall: 0.82 | window: 2.5 | roof: 0.65 | avg. value of building: 0.94

window

2 single pane glazing | g-value: 0.42 | area: 48 m² | window-façade-ratio: 30-40 %

CONCEPT COOLING

ambient air (AA) | free (f) | electricity (E) | night-time ventilation (NV-f)



split unit (SU) |


environmental heat sink

AA

energy carrier

E

cooling system

NV-f, SU

power of system [kWtherm]

-

distribution system

air

VENTILATION CONEPT

operable windows

yes

night ventilation

yes

mechanical ventilation

no

air-change rate [h-1]

-

dehumidification of air

no

pre-cooling of air

no

THERMAL COMFORT PERFORMANCE IN SUMMER

year(s) of monitoring

2008-09

en15251_rom

rom_08_en15251_

year of evaluation

2008-09

number of rooms

3

interval of measurements

5 min

ambient air temperature

public WSa

design temperature [°C]

26

adaptive, class II (up)b

96 %

adaptive, class II (low)c

100 %

avg. room temperature [°C]d

26-28

temp. drift day [K]d

1.0-2.5

POE

no

humidity comfort, class II

99 %

MONITORING RESULTS AND BUILDING SIGNATURE

COOLING



rom_08

useful energy [kWhtherm/m²a]

28.3

final energy [kWhend/m²a]

11.3

primary energy kWhprim/m²a]

28.3

HEATING

useful energy [kWhtherm/m²a]

n.n.

final energy [kWhend/m²a]

149.6

primary energy kWhprim/m²a]

164.5

VENTILATION

final energy [kWhend/m²a]

1.6

primary energy kWhprim/m²a]

4.1

LIGHTING

final energy [kWhend/m²a]

2.6

primary energy kWhprim/m²a]

6.5

APPLIANCES/PLUG LOADS

final energy [kWhend/m²a]

16.8

TOTAL BUILDING

final energy [kWhend/m²a]

165.1

primary energy kWhprim/m²a]

203.4

onsite generation of energy

no

(a) public weather station, (b) upper comfort boundaries, (c) lower comfort boundaries, (d) during occupancy

Public Building | Porretta Terme Italy (44°16’ , 10°97’ , 349 m)

CLIMATE

annual avg. temp. [°C]

12.3



month. avg. max temp. [°C]

22.6

month. avg. min temp. [°C]

1.2

heating degree days [Kday]

2.648

cooling degree days [Kday]

122

design indoor temp. H [°C]

20

design indoor temp. C [°C]

25

INFORMATION ON BUILDINGY AND USE

occupancy civic center + office

hpim1786

number of occupants

20

utilisation

8am-12pm

completion

1970

refurbishment

2007

number of floors

2

total floor area [m²]

752

total conditioned area [m²]

580

total volume [m³]

1.930

area-to-volume ratio [m-1]

0.6

BUILDING ENVELOPE

shading system

exterior roller blinds, manual operation, shading factor 0.15

U-values [W/(m²K)]

exterior wall: 0.34 | window: 1.4 | roof: 0.35 | avg. value of building: 0.44

window

2-pane low-e glazing | g-value: 0.6 | area: 54 m² | window-façade-ratio: 9-16 %

CONCEPT COOLING

ambient air (AA) | borehole heat exchanger (BHEX) | convector (CV)

electricity (E) | free (f) | ground (GR) | heat pump (HP) | heat recovery (HR)

mechanical (m) | mechanical ventilation (MV) | night-time ventilation (NV) photovoltaic (PV)




environmental heat sink

AA, GR

energy carrier

E

cooling system

NV, HP

power of system [kWtherm]

64

distribution system

coils, CV

VENTILATION CONEPT

operable windows

yes

night ventilation

f+m

mechanical ventilation

yes

air-change rate [h-1]

1

dehumidification of air

no

pre-cooling of air

no

THERMAL COMFORT PERFORMANCE IN SUMMER

year(s) of monitoring

2008-09

en15251_ita

ita_08_en15251_

year of evaluation

2008-09

number of rooms

3

interval of measurements

15 min

ambient air temperature

public WSa

design temperature [°C]

25

adaptive, class II (up)b

100 %

adaptive, class II (low)c

88 %

avg. room temperature [°C]d

24.5-27.0

temp. drift day [K]d

0.5-1.5

POE

yes

humidity comfort, class II

68 %

MONITORING RESULTS AND BUILDING SIGNATURE

COOLING



ita_08

useful energy [kWhtherm/m²a]

30.5

final energy [kWhend/m²a]

25.0

primary energy kWhprim/m²a]

62.5

HEATING

useful energy [kWhtherm/m²a]

88.2

final energy [kWhend/m²a]

64.1

primary energy kWhprim/m²a]

160.3

VENTILATION

final energy [kWhend/m²a]

5.5

primary energy kWhprim/m²a]

13.8

LIGHTING

final energy [kWhend/m²a]

1.8

primary energy kWhprim/m²a]

4.5

APPLIANCES/PLUG LOADS

final energy [kWhend/m²a]

0.9

TOTAL BUILDING

final energy [kWhend/m²a]

97.1

primary energy kWhprim/m²a]

242.8

onsite generation of energy

no

(a) public weather station, (b) upper comfort boundaries, (c) lower comfort boundaries, (d) during occupancy

Touborg Boulevard | Copenhagen Denmark (55°67’ , 12°67’ , 24 m)

CLIMATE

annual avg. temp. [°C]

7.7



month. avg. max temp. [°C]

16.4
month. avg. min temp. [°C]

-1
heating degree days [Kday]

2.906
cooling degree days [Kday]

-
design indoor temp. H [°C]

20
design indoor temp. C [°C]

25
INFORMATION ON BUILDINGY AND USE

occupancy

office

north east facade

number of occupants

1.700
utilisation

8am-6pm
completion

2002
refurbishment

-
number of floors

5
total floor area [m²]

21.199
total conditioned area [m²]

18.726
total volume [m³]

71.533
area-to-volume ratio [m-1]

0.3
BUILDING ENVELOPE

shading system

interior venetian blinds, manual operation, shading factor n.n.

U-values [W/(m²K)]

exterior wall: 0.2 | window: 1.12 | roof: 0.2 | avg. value of building: n.n.

window


2-pane glazing | g-value: n.n. | area: 302 m² | window-façade-ratio: 30-60 %

CONCEPT COOLING

ambient air (AA) | compression chiller (CC) | cooling panels (CP) | electricity (E) heat recovery (HR) | mechanical ventilation (MV)
environmental heat sink

AA
energy carrier

E
cooling system

chiller
power of system [kWtherm]

955
distribution system

coils + CP


VENTILATION CONEPT
operable windows

no
night ventilation

no
mechanical ventilation

yes
air-change rate [h-1]

1.4
dehumidification of air

no
pre-cooling of air

yes
THERMAL COMFORT PERFORMANCE IN SUMMER

year(s) of monitoring

2008

iso7730_den

den_08_iso7730_

year of evaluation

2008

number of rooms



3

interval of measurements

15 min

ambient air temperature



at building

design temperature [°C]

25

PMV, class II (up)a



92 %

PMV, class II (low)b

89 %

avg. room temperature [°C]c



23-25.5
temp. drift day [K]c

0.8-1.5
POE

yes
humidity comfort, class II

97 %
MONITORING RESULTS AND BUILDING SIGNATURE (period 10/07 to 04/08)



COOLING



den_08
useful energy [kWhtherm/m²a]

-
final energy [kWhend/m²a]

-
primary energy kWhprim/m²a]

8
HEATING


useful energy [kWhtherm/m²a]

-
final energy [kWhend/m²a]

-
primary energy kWhprim/m²a]

76.8
VENTILATION


final energy [kWhend/m²a]

-
primary energy kWhprim/m²a]

5.5
LIGHTING
final energy [kWhend/m²a]

-
primary energy kWhprim/m²a]

-
APPLIANCES/PLUG LOADS
final energy [kWhend/m²a]

-
TOTAL BUILDING


final energy [kWhend/m²a]

-
primary energy kWhprim/m²a]

150.6
onsite generation of energy

no
(a) upper comfort boundaries, (b) lower comfort boundaries, (c) during occupancy


YIT Centre Turku | Turku Finland (55°67’ , 12°67’ , 24 m)

CLIMATE

annual avg. temp. [°C]

5



month. avg. max temp. [°C]

-
month. avg. min temp. [°C]

-
heating degree days [Kday]

4.115
cooling degree days [Kday]

194
design indoor temp. H [°C]

21
design indoor temp. C [°C]

25
INFORMATION ON BUILDINGY AND USE

occupancy

office

web_yit_turku_3_fi

number of occupants

135
utilisation

8am-5pm
completion

2005
refurbishment

-
number of floors

5
total floor area [m²]

6.900
total conditioned area [m²]

6.900
total volume [m³]

34.000
area-to-volume ratio [m-1]

n.n.
BUILDING ENVELOPE

shading system

exterior venetian blinds, automatic operation, shading factor n.n.

U-values [W/(m²K)]

exterior wall: 0.22 | window: 1.1 | roof: 0.14 | avg. value of building: n.n.

window


n.n. | g-value: 0.38 | area: n.n. | window-façade-ratio: n.n.

CONCEPT COOLING

ambient air (AA) | air handling unit (AHU) | cooling panels (CP) | electricity (E) heat recovery (HR) | mechanical ventilation (MV)

environmental heat sink

-
energy carrier

-
cooling system

district cool
power of system [kWtherm]

345
distribution system

air, CP
VENTILATION CONEPT
operable windows

yes
night ventilation

no
mechanical ventilation

yes
air-change rate [h-1]

2.2
dehumidification of air

no
pre-cooling of air

yes
THERMAL COMFORT PERFORMANCE IN SUMMER

year(s) of monitoring

2008

iso7730_fin

fin_08_iso7730_

year of evaluation

2008

number of rooms



12

interval of measurements

n.n.

ambient air temperature



n.n.

design temperature [°C]

25

PMV, class II (up)a



100 %

PMV, class II (low)b

71 %

avg. room temperature [°C]c



21-22
temp. drift day [K]c

0.5-1.2
POE

yes
humidity comfort, class II

96 %
MONITORING RESULTS AND BUILDING SIGNATURE



COOLING



fin_08

useful energy [kWhtherm/m²a]

19.8
final energy [kWhend/m²a]

20.8
primary energy kWhprim/m²a]

-
HEATING
useful energy [kWhtherm/m²a]

51.9
final energy [kWhend/m²a]

54.5
primary energy kWhprim/m²a]

-
VENTILATION


final energy [kWhend/m²a]

-
primary energy kWhprim/m²a]

-
LIGHTING
final energy [kWhend/m²a]

-
primary energy kWhprim/m²a]

-
APPLIANCES/PLUG LOADS
final energy [kWhend/m²a]

-
TOTAL BUILDING


final energy [kWhend/m²a]

161.5
primary energy kWhprim/m²a]

215.5
onsite generation of energy

no
(a) upper comfort boundaries, (b) lower comfort boundaries, (c) during occupancy


University of La Rochelle | La Rochelle France (46°15’ , -1°15’ , 5 m)

CLIMATE

annual avg. temp. [°C]

12.8



month. avg. max temp. [°C]

19.6
month. avg. min temp. [°C]

4.4
heating degree days [Kday]

2278
cooling degree days [Kday]

-
design indoor temp. H [°C]

19
design indoor temp. C [°C]

26
INFORMATION ON BUILDINGY AND USE

occupancy

university

number of occupants

15+1500
utilisation

8am-6pm
completion

2003
refurbishment

-
number of floors

3
total floor area [m²]

3.900
total conditioned area [m²]

3.900
total volume [m³]

18.600
area-to-volume ratio [m-1]

0.1
BUILDING ENVELOPE

shading system

interior blinds, manual operation, shading factor n.n.

U-values [W/(m²K)]

exterior wall: 0.43 | window: 2.2 | roof: 0.36 | avg. value of building: 0.75

window


2-pane low-e glazing | g-value: 0.44 | area: 880 m² | window-façade-ratio: 42 %

CONCEPT COOLING

ambient air (AA) | free (f) | mechanical ventilation (MV)

night-time ventilation (NV)

environmental heat sink

AA
energy carrier

-
cooling system

NV-f
power of system [kWtherm]

-
distribution system

-
VENTILATION CONEPT


operable windows

yes
night ventilation

f
mechanical ventilation

yes
air-change rate [h-1]

1.0
dehumidification of air

no
pre-cooling of air

no
THERMAL COMFORT PERFORMANCE IN SUMMER

year(s) of monitoring

2008-09

en15251_fra

fra_08_en15251_

year of evaluation

2008-09

number of rooms



9

interval of measurements

60 min

ambient air temperature



at building

design temperature [°C]

26

adaptive, class II (up)a



96 %

adaptive, class II (low)b

38 %

avg. room temperature [°C]c



22-25.5
temp. drift day [K]c

0.5-1.5
POE

yes
humidity comfort, class II

44 %
MONITORING RESULTS AND BUILDING SIGNATURE (period 10/07 to 04/08)



COOLING


fra_08
useful energy [kWhtherm/m²a]

0
final energy [kWhend/m²a]

0
primary energy kWhprim/m²a]

0
HEATING


useful energy [kWhtherm/m²a]

74.3
final energy [kWhend/m²a]

85.3
primary energy kWhprim/m²a]

97.6
VENTILATION


final energy [kWhend/m²a]

n.n.
primary energy kWhprim/m²a]

n.n.
LIGHTING
final energy [kWhend/m²a]

n.n.
primary energy kWhprim/m²a]

n.n.
APPLIANCES/PLUG LOADS
final energy [kWhend/m²a]

n.n.
TOTAL BUILDING


final energy [kWhend/m²a]

n.n.
primary energy kWhprim/m²a]

n.n.
onsite generation of energy

no
(a) upper comfort boundaries, (b) lower comfort boundaries, (c) during occupancy


Home Office Nebrich | Prague, Czech Republic (50°0' , 14°34’ , 269 m)

CLIMATE

annual avg. temp. [°C]

10



month. avg. max temp. [°C]

18.9
month. avg. min temp. [°C]

1.6
heating degree days [Kday]

3.677
cooling degree days [Kday]

19
design indoor temp. H [°C]

20
design indoor temp. C [°C]

26
INFORMATION ON BUILDINGY AND USE

occupancy

tenement

p1010431

number of occupants

4
utilisation

9am-6pm
completion

2005
refurbishment

-
number of floors

2
total floor area [m²]

230
total conditioned area [m²]

230
total volume [m³]

562
area-to-volume ratio [m-1]

0.4
BUILDING ENVELOPE

shading system

interior blinds, manual operation, shading factor n.n.

U-values [W/(m²K)]

exterior wall: 0.2 | window: 1.4 | roof: 0.15 | avg. value of building: n.n.

window


2-pane glazing | g-value: 0.4 | area: 54 m² | window-façade-ratio: 20-80 %

CONCEPT COOLING

ambient air (AA) | electricity (E) | free (f) | night-time ventilation (NV)

environmental heat sink

AA
energy carrier

E
cooling system

NV-f, fans
power of system [kWtherm]

-
distribution system

air
VENTILATION CONEPT
operable windows

yes
night ventilation

f
mechanical ventilation

no
air-change rate [h-1]

0.5
dehumidification of air

no
pre-cooling of air

no
THERMAL COMFORT PERFORMANCE IN SUMMER

year(s) of monitoring

2008

en15251_cze

cze_08_en15251_

year of evaluation

2008

number of rooms



1

interval of measurements

1 min

ambient air temperature



at building

design temperature [°C]

26

adaptive, class II (up)a



97 %

adaptive, class II (low)b

96 %

avg. room temperature [°C]c



23-26
temp. drift day [K]c

1.0-2.8
POE

no
humidity comfort, class IId

-
MONITORING RESULTS AND BUILDING SIGNATURE (period 10/07 to 04/08)



COOLING


No monitoring data on humidity.



cze_08

useful energy [kWhtherm/m²a]

0
final energy [kWhend/m²a]

0
primary energy kWhprim/m²a]

0
HEATING
useful energy [kWhtherm/m²a]

56.0
final energy [kWhend/m²a]

68.0
primary energy kWhprim/m²a]

170.0
VENTILATION


final energy [kWhend/m²a]

0
primary energy kWhprim/m²a]

0
LIGHTING
final energy [kWhend/m²a]

4.6
primary energy kWhprim/m²a]

11.5.
APPLIANCES/PLUG LOADS
final energy [kWhend/m²a]

n.n.
TOTAL BUILDING


final energy [kWhend/m²a]

72.6
primary energy kWhprim/m²a]

181.5
onsite generation of energy

no
(a) upper comfort boundaries, (b) lower comfort boundaries, (c) during occupancy, (d) not measured




Directory: fileadmin
fileadmin -> The Collapse of the gdr and the Reunification of Germany
fileadmin -> Filmskript zur Sendung „From Georgia to Virginia“ Sendereihe: The East Coast of the usa
fileadmin -> Comparative Politics Central Europe Mgr. Juraj Marušiak, PhD. course coordinator
fileadmin -> Annex 1 to the Interim Report
fileadmin -> Review of projects and contributions on statistical methods for spatial disaggregation and for integration of various kinds of geographical information and geo-referenced survey data
fileadmin -> An overview of land evaluation and land use planning at fao
fileadmin -> Contact information
fileadmin -> Review of the literature
fileadmin -> Sigchi extended Abstracts Sample Adapted to mamn25
fileadmin -> Communication and Information Sector Knowledge Societies Division

Download 0.72 Mb.

Share with your friends:
1   ...   11   12   13   14   15   16   17   18   19




The database is protected by copyright ©ininet.org 2024
send message

    Main page