Safety Critical Element Management Manual


Safety Critical Element Management Manual



Download 494.83 Kb.
View original pdf
Page44/54
Date16.09.2023
Size494.83 Kb.
#62078
1   ...   40   41   42   43   44   45   46   47   ...   54
Shell EP 2009.9009 SCE Management Manual
POSITION PAPER 130[shell verification]
Safety Critical Element Management Manual
EP 2009-9009
Restricted
44
SCE group listing (continued)
SCE goal
Typical equipment types
Description
Minimum level
SCE group PS005
SCE group title Fire Water Ring Main and Other Distribution Systems
Firewater ring main distribution system from the fire pump discharge to the end-users.
To distribute sufficient firewater to all firewater systems Firewater tank Pipework (including supports) from the
1st manual isolation valve downstream of fire pump discharge to the end-user activation valve Deluge set inlet isolation valve Helideck monitor manual isolation valve Sprinkler system manual isolation valve Fire hydrant isolation valve Fire hose isolation valve Low ring main pressure switches Fire main pressure control valves
At system/area level
SCE group PS006
SCE group title Passive Fire Protection
Passive fire protection to maintain structural integrity in the event of a fire.
To limit the effect of afire on structure, plant, safety systems and personnel Passive Fire protection coatings or barriers protecting critical structure, plant and safety systems. At area level
SCE group PS007
SCE group title Gaseous Fire Protection Systems
Gaseous fire protection
Systems for extinguishing fires in an equipment enclosure.
To mitigate the effects of afire and to prevent escalation of fires in enclosed areas CO
2
system for switch room
At system level
SCE group PS008
SCE group title Fine Water Spray (FWS) Systems
Fine water spray systems for extinguishing fires in an equipment enclosure.
To mitigate the effects of afire and to prevent escalation of fires in enclosed areas, e.g. diesel engine enclosures.
Protection to generators turbines
At system level
SCE group PS010
SCE group title Power Management System
Power management system to control the operation of critical electrical switchgear through shedding of noncritical loads.
To maintain the stability of the main power generating system by load sharing and shedding.
Electrical network monitoring and control systems
At system level