Message
|
16-May-06 17:29:06
Citect 1> One of the required Failover Synchronization points was not loaded.
Error = 0: The Active ID synchronization point was not loaded.
The input PI tag was not loaded
|
Cause
|
The Active ID tag is not configured properly.
|
Resolution
|
Check validity of point attributes. For example, make sure Location1 attribute is valid for the interface. All failover tags must have the same PointSource and Location1 attributes. Modify point attributes as necessary and restart the interface.
|
|
Message
|
16-May-06 17:38:06
Citect 1> One of the required Failover Synchronization points was not loaded.
Error = 0: The Heartbeat point for this copy of the interface was not loaded.
The input PI tag was not loaded
|
Cause
|
The Heartbeat tag is not configured properly.
|
Resolution
|
Check validity of point attributes. For example, make sure Location1 attribute is valid for the interface. All failover tags must have the same PointSource and Location1 attributes. Modify point attributes as necessary and restart the interface.
|
|
Message
|
17-May-06 09:06:03
Citect > The Uniint FailOver ID (/UFO_ID) must be a positive integer.
|
Cause
|
The UFO_ID parameter has not been assigned a positive integer value.
|
Resolution
|
Change and verify the parameter to a positive integer and restart the interface.
|
|
Message
|
17-May-06 09:06:03
Citect 1> The Failover ID parameter (/UFO_ID) was found but the ID for the redundant copy was not found
|
Cause
|
The /UFO_OtherID parameter is not defined or has not been assigned a positive integer value.
|
Resolution
|
Change and verify the /UFO_OtherID parameter to a positive integer and restart the interface.
|