APPENDIX 3


B-TYPICAL ARRANGEMENT OF METERING CABINET ON COMPOUND WALL



Type of kWh Metering

Dimensions in cm

A

B

C

D

E

F

G

H

I

Direct Connected Metering
(Up to 125Amps)

60

80

25

20

06

06

80
(Min.)

160
(Max.)

180
(Max.)

CT. Operated Metering
(5A Meter & CT Ratio up to 400/5 Amps)

80

100

30

25

08

08

80
(Min.)

160
(Max.)

180
(Max.)



Description:-

  1. Compound wall

  2. Weather proof (IP 55) metering cabinet

  3. Hinged door with provision for wire sealing & pad locking (hole size: min. 10mm dia.)

  4. Cable (Gland) box

  5. Transparent meter viewing window (min. 5mm thickness, size: 15cm x 15cm).

  6. Protection cover with hinges on top (size: 20cm x 20cm)

  7. Position of incomer breaker

  8. 15 / 10 cm PVC pipe sleeve for service cable.

  9. Conduit/s for earthing conductors (ECC)

  10. 15 / 10 cm PVC pipe sleeve for load cable

Note: - CT operated metering: Provide sealable type VT fuses in sealable enclosure.
- Minimum 2 mtr. clearance shall be maintained between electricity and water service cabinets / points.

APPENDIX 3


C-ARRANGEMENT OF METERING IN MAIN LV PANEL
(Main Incomer Compartment / Section)


A

B

C

D

E

F

G

H

CT Operated kWh Metering Compartment

Meter Viewing Perspex
(Size: 12.5cm x 12.5cm)

Protection Cover with Hinges on Top (Size: 15cm x
15cm)

Sealable Type 3Nos VT Fuse Carriers in Sealable
Enclosure for Data Concentrator

Sealable Type 3Nos VT Fuses in Sealable
Enclosure for kWh Meter

kWh Meter

Pad locking Arrangement (Hole Size: 10mm dia.)

CT’s Shorting Terminal Block in Sealable Enclosure (RS1&RS2 / YS1&YS2
/ BS1&BS2)

Note: - Meter viewing Perspex (min: 5mm thickness) with hinged type protection cover.
- CT operated metering & Data concentrator: Provide sealable type VT fuse carriers in sealable enclosure.

APPENDIX 3




D- TYPICAL ELECTRICAL SERVICES ROOM WITH 1 NO. CUBICLE TYPE LV. SWITCHBOARD / PANEL.

Description:-


  1. LV Switchboard / Panel.

  2. Capacitor Bank.

  3. Sub Main Distribution Board (Sample).

  4. KWh meters.

  5. Non-maintained, minimum 3 Hrs. rated, self contained emergency light.

  6. Light fitting.

  7. Non-combustible door.

Notes:-


  1. All dimensions noted are in meters and not to scale.

  2. Minimum front clearance – 1.5 mtrs.

Rear & side clearance – 0.75 mtrs.

  1. The minimum clear space shown at the sides and rear of the panel is for switchboards with rear access requirements only.

  2. Refer to section 3 of the regulation.

APPENDIX 3




E - TYPICAL ELECTRICAL SERVICE ROOM WITH 1 NO. MDB (MAX. 400 AMPS RATING)

Description:-



  1. Main Meter.

  2. Main Distribution Board.

  3. Capacitor Bank.

  4. PVC/GS trunking.

  5. kWh meters.

  6. Exhaust fan (for non –air conditioned room)

  7. Non-maintained, minimum 3 Hrs. rated, self-contained emergency light

  8. Light Fitting

  9. Non-combustible door (Louvered type for non-air conditioned room)

Notes:-


  1. All dimensions noted are in meters and not to scale

  2. Only minimum dimension permitted for electrical room is shown in the layout. Each electrical room shall be designed to accommodate the MDBs / SMDBs, kWh meters, etc. Prior approval shall be obtained for construction

  3. Refer to section 3 of the regulation.

APPENDIX 3




D- TWO LV PANELS ARRANGEMENT IN LV SWITCH ROOM

Description:-


  1. LV Switchboard / Panel.

  2. Capacitor Bank.

  3. Sub Main Distribution Board (Sample).

  4. KWh meters.

  5. Non-maintained, minimum 3 Hrs. rated, self contained emergency light.

  6. Light fitting.

  7. Non-combustible door.

Notes:-


  1. All dimensions noted are in meters and not to scale.

  2. Minimum front clearance – 1.5 mtrs.

Rear & side clearance – 0.75 mtrs.

  1. The minimum clear space shown at the sides and rear of the panel is for switchboards with rear access requirements only.

  2. Refer to section 3 for the regulation.