Note: - CT operated metering: Provide sealable type VT fuses in sealable enclosure.
- Minimum 2 mtr. clearance shall be maintained between electricity and water service cabinets / points.
APPENDIX3
C-ARRANGEMENT OF METERING IN MAIN LV PANEL (Main Incomer Compartment / Section)
Note: - Meter viewing Perspex (min: 5mm thickness) with hinged type protection cover.
- CT operated metering & Data concentrator: Provide sealable type VT fuse carriers in sealable enclosure.
APPENDIX3
D- TYPICAL ELECTRICAL SERVICES ROOM WITH 1 NO. CUBICLE TYPE LV. SWITCHBOARD / PANEL.
All dimensions noted are in meters and not to scale.
Minimum front clearance – 1.5 mtrs.
Rear & side clearance – 0.75 mtrs.
The minimum clear space shown at the sides and rear of the panel is for switchboards with rear access requirements only.
Refer to section 3 of the regulation.
APPENDIX3
E - TYPICAL ELECTRICAL SERVICE ROOM WITH 1 NO. MDB (MAX. 400 AMPS RATING)
Only minimum dimension permitted for electrical room is shown in the layout. Each electrical room shall be designed to accommodate the MDBs / SMDBs, kWh meters, etc. Prior approval shall be obtained for construction
All dimensions noted are in meters and not to scale.
Minimum front clearance – 1.5 mtrs.
Rear & side clearance – 0.75 mtrs.
The minimum clear space shown at the sides and rear of the panel is for switchboards with rear access requirements only.