I have a SFD house that is going to have a 60 ampere to 100 ampere up-grade and it has a # 8 Copper armored cable for a grounding electrode conductor going outside to two ground rods and an old copper ground ring (#8 copper) around the house. The electrician says it is good enough and does not want to replace it.
Answer: SPS 316.009 states all electrical power and communication equipment and lines shall be constructed, installed, operated and maintained so as to minimize hazards to life and property. All electrical installations shall conform to the National Electrical Code, incorporated by reference in this chapter, and the requirements specified in this chapter. Article 250.66 permits a #8 copper grounding electrode conductor to be used for a 100 ampere. 250.64(B) states a grounding electrode conductors smaller than 6 AWG shall be protected in RMC, IMC, PVC, RTRC, EMT, or cable armor. The cable armor would need to be suitable for the use. The clamps for this connection must be listed for use in direct contact with earth. NEC 250.52(A)(4) requires a minimum #2 copper. The answer is the #8 grounding electrode conductor in armored cable to the ground rod might be ok if the conditions are right (probably not). And the ground ring if it is being used must be changed to #2 copper. In Wisconsin the 2 ground rods would be sufficient if there were no metal water piping serving the dwelling unit. Code reference: SPS 316.009; 250.66; 250.64(B); 250.52(A)(4)
-
The central vacuum system installer installed a suction outlet in a kitchen at an existing house. The vacuum outlet was adjacent to a kitchen wall receptacle. The circuit he tapped his five foot whip to was one of the 20 amp small appliance branch circuits. When he was told that he can’t tap off of this circuit, he said that the 30 foot vacuum cleaner hose is also serving the kitchen, so this is OK…..is this OK?
Answer: No. 210.52(B)(1) & (2); (1) states the 2 or more small appliance circuits can only serve 210.52(A) receptacles, countertop receptacles as in (C), and a receptacle outlet for the refrigerator, and in (2) no other outlets are allowed except for clock or gas range/appliance. The answer is no and the code section is NEC 210.52(B)(1) & (2).
-
We are wiring a condominium that is basically a duplex. It has two water mains coming in from the street. The service wires to the panels are run under the garage slabs to opposite sides of the building. The inspector says we can’t simply go from each panel to the unit’s individual copper water main. He says we have to connect each water main to each other by running a #4 AWG copper wire between the two units. He also told me that I have to tie both sets of ground rods to the underground metal water pipe. This seems excessive as they come out of their respective panels and the grounding electrode conductors from these panels go to the water pipes. How do I have to do this?
Answer: 250.24(A) (1) through (6) requires a grounding electrode conductor to each service. Even though you said “condo” this indicates a single building. We must assure that the service for the building and the building itself is protected from lightning and surges. If there are two metal water services (in contact with the earth for a minimum of 10 feet) entering the building, then each water service would need to be used as a grounding electrode. Each water service would need to have a grounding electrode conductor connected within 5 feet of where each water service enters the building. This grounding electrode conductor would need to be connected to the grounded service conductor at or ahead of the main disconnect or disconnects. This could be done at a common location or at each disconnecting means per NEC 250.64(D). The supplemental grounding electrode is still required for each service per 250.50 & 250.53(D)(2), which also requires all electrodes to be bonded together. Keep in mind a water grounding electrode is not permitted to supplement another water grounding electrode. The answer is the service and/or both units need to be grounded. More information would be needed to make an accurate assessment. The code references are NEC 250.24(A)(1) through (6); 250.50; 250.53(D)(2) & 250.64(D).
-
Recently a code inspector mentioned to us that building service entrance conductors need to be sized for 100% of the service entrance main circuit breaker rating. Is this correct, or does NEC 240.4 (B) still apply for service entrance conductors? In our particular situation we had an 800A MCB with 2~500 Kcmil conductors per phase. The inspector indicated that we could not use these conductors because the ampacity ratings listed in Table 310.15(B)(16) indicated the conductors were only good for 380 amps, 760 amps total. We were asked to up-size the conductors to 2~600 Kcmil per phase.
Answer: Service entrance conductors are covered in NEC 230 Part IV. 230.42(A) says the ampacity of the service-entrance conductors before the application of any adjustment or correction factors shall not be less than either 230.42(A)(1) or (A)(2). Loads shall be determined in accordance with Part III, IV, or V of Article 220, as applicable. Ampacity shall be determined from 310.15.
(1) The sum of the noncontinuous loads plus 125 percent of continuous loads
Exception: Grounded conductors that are not connected to an overcurrent device shall be permitted to be sized at 100 percent of the continuous and noncontinuous load.
(2) The sum of the noncontinuous load plus the continuous load if the service-entrance conductors terminate in an overcurrent device where both the overcurrent device and its assembly are listed for operation at 100 percent of their rating
230.90 Where Required. Each ungrounded service conductor shall have overload protection.
(A) Ungrounded Conductor. Such protection shall be provided by an overcurrent device in series with each ungrounded service conductor that has a rating or setting not higher than the allowable ampacity of the conductor. A set of fuses shall be considered all the fuses required to protect all the ungrounded conductors of a circuit. Exception No. 2: Fuses and circuit breakers with a rating or setting that complies with 240.4(B) and 240.6 shall be permitted. NEC 240.4(B) says the next higher standard overcurrent device rating (above the ampacity of the conductors being protected) shall be permitted to be used, provided all of the following conditions are met:
(1) The conductors being protected are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads.
(2) The ampacity of the conductors does not correspond with the standard ampere rating of a fuse or a circuit breaker without overload trip adjustments above its rating (but that shall be permitted to have other trip or rating adjustments).
(3) The next higher standard rating selected does not exceed
800 amperes. Answer: The service entrance conductors, if under 800 amperes are permitted to be protected by an overcurrent device that is equal to or the next size higher as permitted by NEC 240.6. Code references are NEC 230.42(A)(1) & (2); NEC 220; 230.90(A) Exception #2; 310.15(B)(16); 240.4(B); 240.6
-
When hooking up a 100 amp mobile home feeder, can I use a 200 amp breaker in the pedestal and use tap rules to the panel?
Answer: Maybe!!! Article 550 covers the installation requirement for feeders to mobile homes, specifically 550.33. NEC 550.33(A) & (B) does not prohibit this “tap” installation, NEC 240.21(B)(5) allows outside feeder taps of unlimited length provided you comply with the 4 conditions which are included with this allowance. These 4 conditions are: (1) conductors are protected from physical damage, (2) the conductors terminate in a single circuit breaker, (3) the overcurrent device is part of the disconnecting means, and (4) the conductors are outside of the building and terminate in the overcurrent device nearest point of entrance to the building.
SPS 316.110 requires us to install products per their listing and installation instructions. Therefore it would require that the lug in which these conductors terminate into the 200 ampere circuit breaker be listed or the size of conductors being used. The 200 amp breaker lugs may not be listed to terminate 100 amp conductors. Code sections are NEC 550.33(A) & (B); 240.21(B)(5) and SPS 316.110
-
A local electrician says he used a Square D panel in the garage with a 100 amp main breaker installed (because it's cheaper to buy them that way), and that it's okay if he protects the panel with a 60 amp breaker back at the main provided that all the wiring is correct. I say incorrect because a home owner buying this house is under the impression there is a 100 amp supply at the detached garage. I hang my hat on SPS 316.110. Who is correct?
Answer: NEC 225 addresses outside branch circuits and feeders. NEC 225 Part II deals with the disconnecting means. 225.31 states there must be a disconnecting means. 225.32, as amended by SPS 316.225 states the disconnecting means must be installed outside or not more than 8 feet inside the garage. NEC 225.36 states the disconnect must be SUSE rated. 225.39 says the feeder or branch-circuit disconnecting means shall have a rating of NOT LESS than the calculated load to be supplied, determined in accordance with Part III or IV of Article 220 for feeders. The feeder starts in the house. I see no violation of the Code using a 60 ampere breaker in the house (which is sized for the load) feeding a 100 ampere main breaker in the garage (where the 100 amp breaker serves as the disconnecting means for the garage). It appears the code is met. There doesn’t appear to be a manufacturer’s problem with protecting a 100 ampere breaker panel with a 60 ampere breaker. Answer – no code violation. Code reference: NEC 225.31; 225.32; SPS 316.225; NEC225.36; NEC 225.39
-
Is it allowable to have a switched receptacle outlet (for a lighting outlet) for a stairway? Does installing a midpoint landing have any bearing on the issue?
Answer: No and No. NEC 210.70(A)(2)(a) requires At least one wall switch–controlled lighting outlet shall be installed in hallways, stairways, attached garages, and detached garages with electric power. A lighting outlet is an outlet intended for the direct connection of a lampholder or luminaire. A switched receptacle would not meet this requirement. The code does not require a receptacle outlet on a typical stair landing. Answer is no a receptacle outlet is not a lighting outlet and the landing has nothing to do with this issue. Code reference 210.70(A)(2)(a) and Article 100 Definitions for Lighting Outlet.
-
We are installing a transformer vault in a large apartment building. The vault will be venting into an areaway made of concrete with a large metal grate over the opening. The inspector says we can’t do that. What is wrong with this installation?
Answer: The answer is direct venting is required without using flues or ducts by SPS 316.450(2) unless the State of Wisconsin grants a variance for such an installation. Areaways are another form of a flue or duct if it is transmitting hazardous gases.
-
Can a meter base be closer than 3 ft. to a window? Our Utility says the meter base must be three feet from a window. I cannot find it in the code.
Answer: It is not addressed in the NEC. NEC 230.9(A) requires service entrance conductors must be kept a minimum of 3 feet from the sides or bottom of a window that is designed to be opened. There is nothing in the NEC that addresses meters or meter enclosures. It appears the NESC (National Electrical Safety Code used by the utilities) and PSC 114 (which applies to Wisconsin utilities) have similar requirements for overhead service laterals, but nothing about meter socket enclosures. If the utility has a rule about meter placement it would be something you could ask for. Answer: there is no restriction in the NEC about the clearance of a meter socket to a window, check with the utility.
-
GFCI protection for personnel required for sump pumps and sewage ejector pumps located outdoors as part of an installation at a dwelling? Some inspectors say GFCI protection is not required because of possible nuisance tripping and the damage such an incident could pose. Section 210.8(A) requires GFCI protection for personnel for all 125-volt, single-phase, 15- and 20-ampere receptacles in location specified in (1) through (8). This includes (3) for Outdoors. Does the NEC require GFCI protection for receptacles (for cord-and-plug connected pumps) or for breakers serving sump pumps and sewage ejector pumps located Outdoors? If the answer is NO, what is the Code justification for the answer?
Answer: SPS 316.300 addresses wiring of private sewage systems. (a) Wiring methods. All effluent pump circuit wiring shall comply with the approved wiring methods as specified in NEC 300 and all of the following requirements:
1. Effluent pumps shall be supplied by a separate branch circuit supplying no other loads.
2. Alarm wiring may not be connected to the pump circuit.
3. All aboveground cables and flexible cords shall be enclosed to protect against physical damage.
4. The neutral conductor may not be common to both alarm and pump circuits.
5. Where the wiring enclosure for the alarm and pump circuit is located outside the pump chamber, any openings into the pump chamber for circuit wiring shall be sealed or plugged to prevent the passage of gas or vapor into the wiring enclosure.
Note: This prohibits use of a multi−wire branch circuit to supply both the alarm and pump.
Note: See NEC 430.102 for location of disconnects.
(b) Ground−fault circuit protection. A single receptacle located at the pump chamber that has an alarm or pump connected to it does not require ground−fault circuit−interrupter protection. The answer is no, the code reference is SPS 316.300(1)(a) & (b).
-
Where can we find a code section that prohibits the attachment of a male plug on the end of a section of NM for a garbage disposal? I have a reference site that points to Table 400.4 which doesn't list NM. Or would it be Article 334 - "closely follow the building surface, "securing and supporting"?
Answer: NEC 422.16(B) allows for plug connection only when connected to flexible cord. Also, SPS 316.110, plugs are only listed for use on flexible cord see Attachment Plugs, Fuseless (AXUT) on page 81 in the 2014 UL White Book. See the Guide Information for AXUT under the heading Terminals which states “Terminals of appliance couplers, appliance and flatiron plugs, attachment plugs, cord connectors and cable taps are intended for use with stranded copper conductors of the type used in flexible cord.” Answer is NEC 422.16(B); SPS 316.110; UL White Book AXUT
-
A 400A service is made up of two 200A main breaker panelboards that are connected together by nipples. Can the service conductors pass through one of the cabinets to supply the other panelboard?
Answer: Maybe, without more information we can only speculate. Here are some thoughts. Per NEC 230.7 says conductors other than service conductors shall not be installed in the same service raceway or service cable. Since the two 200 ampere main breaker panelboards are service equipment the conductors in that enclosure is permitted, but the nipple connecting the two panelboards that the service entrance conductors go through cannot have other conductors installed within.
It is permitted to have service conductors supply each service equipment enclosure per 230.40 Exc. 2. The 200A main circuit breaker in each service panel would comply with 408.36. However, if the service conductors “pass through” the first panelboard bus with feed through lugs, the first panel would not comply with 430.30, the load of the first and second panel would exceed the rating of the first panel. If the service conductors enter and exit the panelboard via dual lugs on the main circuit breaker, proper spacing per 408.55 would be required for the dual conductors. In addition, 230.7 states conductors other than service conductors shall not be installed in the same service raceway or service cable. Since the two 200 ampere main breaker panelboards are service equipment the conductors in that enclosure is permitted, but the nipple connecting the two panelboards that the service entrance conductors go through cannot have other conductors installed within, except for ground conductors and bonding jumpers.
230.40 Number of Service-Entrance Conductor Sets.
Each service drop, set of overhead service conductors, set of underground service conductors, or service lateral shall supply only one set of service-entrance conductors.
Exception No. 2: Where two to six service disconnecting means in separate enclosures are grouped at one location and supply separate loads from one service drop, set of overhead service conductors, set of underground service conductors, or service lateral, one set of service-entrance conductors shall be permitted to supply each or several such service equipment enclosures.
408.36 Overcurrent Protection. In addition to the requirement of 408.30, a panelboard shall be protected by an overcurrent protective device having a rating not greater than that of the panelboard. This overcurrent protective device shall be located within or at any point on the supply side of the panelboard.
408.30 General. All panelboards shall have a rating not less than the minimum feeder capacity required for the load calculated in accordance with Part III, IV, or V of Article
220, as applicable.
408.55 Wire-Bending Space Within an Enclosure Containing a Panelboard. The enclosure for a panelboard shall have the top and bottom wire-bending space sized in accordance with Table 312.6(B) for the largest conductor entering or leaving the enclosure. Side wire-bending space shall be in accordance with Table 312.6(A) for the largest conductor to be terminated in that space.
Answer is maybe, more information is needed.
-
Can I use 1/2-inch flexible metal conduit to fish in receptacle outlets in an existing building? I used 12-AWG THWN wire with fittings on the outside of the flex and I only put two wires in each run. Now I was told I have to pull in a ground wire. Is this right?
Answer: Yes, you can use flexible metal conduit to fish a circuit in 348.10, 348.30(A) Exception No. 1. You can use it as the equipment grounding conductor in accordance with 250.118(5) if it is 6 feet or less and 20 amperes per 348.60. Likely the inspector was correct as it likely exceeds 6 feet and or 20 amperes. Answer is yes for fishing and probably for EGC. Code references are 348.10; 348.30(A) Exception No. 1; and 348.60.
-
Can I use Type NM cable to connect recessed fluorescent fixtures in a suspended lay-in ceiling in a retail store? Section 334.30(B)(2) seems to permit this. This is very confusing to many of us on the job.
Answer: Maybe, 334.10 & SPS 316.334 & 334.30(B)(2); if the store is a type III, IV or V construction, [types of construction must be marked on the building’s approved plans or approval letter.] SPS deletes the 334.12(A)(2) prohibition. Then NEC 334.30(B)(2) would need to be met where it states you need less than 4.5’ from last point of support to the equipment. Without more information on the installation, the answer is maybe and the code references are NEC 334.10; SPS 316.334 and NEC 334.30(B)(2).
-
We are installing string lights in the entrance and lobby areas of a 14,000 seat auditorium. The inspector rejected the job saying the website says these are festoon lights. They are listed and the engineer says that if they are approved outdoors, they are ok for indoor use. Who is right?
Answer: So far the inspector is right, but this is still a work in progress. The lights are listed in the manufacturer’s website as festoon lighting. NEC 100 Definitions: Festoon Lighting. A string of outdoor lights that is suspended between two points. NEC 225.6(B) declares Overhead conductors for festoon lighting shall not be smaller than 12 AWG unless the conductors are supported by messenger wires. In all spans exceeding 40 ft., the conductors shall be supported by messenger wire. The messenger wire shall be supported by strain insulators. Conductors or messenger wires shall not be attached to any fire escape, downspout, or plumbing equipment. The statement is if it ok outdoors it must ok indoors. What about the USE cable without the dual rating? Cannot be used indoors. So far the manufacturer has not produced documentation that this product is approved for indoor use. It appears this time the inspector is correct. NEC 100; NEC 225.6(B); SPS 316.110.
-
If I have a raceway under a building, or encased in concrete on an outside wall beneath grade on an exterior wall, would I have to seal the raceway where it enters the building? If so, would I have to seal each end?
Answer: Yes, 300.5(G) requires it to be done at one or both ends.
-
Can I install a receptacle for the basin in a bathroom near the floor as long as it is within 3’ of the basin? The basin is a free-standing type and does not have a countertop associated with it.
Answer: NEC 210.52(D) is the Code section where we find this answer. This section of the NEC was revised in the 2008 version to include language which requires the receptacle to be no more than 12” below the countertop surface. In this situation with no countertop, this measurement would be taken from the top rim of the sink, so depending on your definition of “near the floor”, your installation may or may not meet the Code requirement of being within 12” of the countertop, we are thinking your receptacle will most likely be too low to meet this requirement!!! Code reference is NEC 210.52(D).
-
When changing a service from the house to the detached garage, how is the service on the detached garage to be grounded? How is the grounding handled at the house where this will now be a subpanel? The home has a copper water line supplying water to the home.
Answer: Article 250.24 (A) p. 104, 250.32(A)(B) p.109, 250.50 p. 111, 250.52 p. 111, 250.53 p. 112 & SPS 316.250. Article 250.24 (A) requires a grounding electrode conductor to be installed at detached garage. Article 250.24(A)(1) requires the connection for the grounding electrode to be made at any accessible point from the load side of the service drop or service lateral to and including the terminal or bus to which the grounded service conductor is connected at the service disconnecting means. Article 250.50 requires any of the electrodes present to be bonded together for a complete system. Where none of the grounding electrodes exist then one or more of the electrodes specified in Article 250.52(A)(4) through (A)(8) shall be installed. SPS 316.250 requires an additional electrode to be installed. For the sub panel at the house Article 250.32(A) requires buildings of structures supplied by feeders or branch circuits to have a grounding electrode or grounding electrode system installed according to Part III of Article 250. The grounding electrode conductor shall be connected according to 250.32 (B) or (C). 250.32(B)(1) requires the equipment grounding conductor to be run with the supply conductors and be connected to the building or structure disconnecting means and to the grounding electrodes. The equipment grounding conductor shall be used for grounding and bonding of equipment, structures or frames required to be grounded or bonded and shall be sized according to 250.122. Any installed grounded conductor shall not be connected to the equipment grounding conductor or to the grounding electrodes. Answer: Reverse what you do when you go from a house to an outbuilding. Code references are NEC 250.24; 250.50 and 250.32.
-