PI Interface to the Baily System
3
Dig Station Failure
4
Manual Lock
5
Bypassed
6
Auto Lock
7
Cascade Lock
Digital Read
(N90 point type These points should be defined as a digital point in the PI Server. The Bailey digital report is packed in a byte. After checking bit 7 for quality, the interface extracts bit 0 and puts it in the PI point. The first digital state of the PI point's digital state set determines what digital state string will show on the system.
Analog Report
(N90 point type This is one of the point types for writing from the PI Server to the Bailey Net / Infi90. Bailey analog values should be either Float or Int type points in the PI Server. Bailey real points are in the range -E to E. If the PI point's value is a system digital state code (such as
SHUTDOWN
or
OVER RANGE
), the output is set to bad quality and the value 0 is sent to Bailey. If the PI point is defined as a digital point type, the interface sends the digital state offset as an analog value to
Bailey.
Digital Report
(N90 point type This is another point type for writing from the PI System to Bailey. A digital output can be configured as Float, Int, or Digital point in the PI Server. A bad quality status is sent to Bailey when the snapshot value is a system digital state value. Also, for digital points, the interface sends a bad quality status if the snapshot value is out of the range of the point's digital state set.
For PI Float points, a status of 1 is sent to Bailey if the PI value is greater than 0. A status of 0 is sent fora valueless than or equal to 0. For PI Int points, the status byte is set equal to the integer value.
For PI Digital points, the status byte is set to the digital state offset.
Module Status


PI Point Configuration
32
(N90 point type A module status should be defined as a digital point in the PI Server. Only the module mode (bits 7-6 of the first status byte) is saved by the Interface. The four states of the Module status are Configure Failed Error Execute
Thus, the user should set the PI digital point's digital state set to a digital state set that contains the following states:
Value
Module Status