Bailey Infi90 Interface to the PI System 29
The Infi90 Interface does not use the InstrumentTag attribute.
ExDescThe Infi90 Interface does not use the ExDesc (Extended Descriptor) attribute.
Scan The Infi90 Interface does not use the Scan attribute. Thus, a user cannot remove a point from the Interface simply by setting its Scan attribute to 0. This behavior is different from that of the vast majority of OSIsoft interfaces.
ShutdownThe Shutdown attribute is 1 (true) by default. The default behavior of the PI Shutdown
subsystem is to write the SHUTDOWNdigital state to all PI points when PI is started. The timestamp that is used for the
SHUTDOWNevents is retrieved from a file that is updated by the Snapshot Subsystem. The timestamp is usually updated every 15 minutes, which means that the timestamp for the
SHUTDOWNevents will be accurate to within 15 minutes in the event of a power failure. For additional
information on shutdown events, refer to PI Server manuals.
SHUTDOWNevents can be disabled from being written to PI when PI is restarted by setting the Shutdown attribute to 0 for each point. Alternatively, the default behavior of the PI Shutdown Subsystem
can be changed to write Share with your friends: