Bailey Infi90 Interface to the PI System 27
PI Point ConfigurationThe PI point is the basic building block for controlling data flow to and from the PI Server. A single point is configured for each measurement value that needs to be archived.
PI Point AttributesEvery
two minutes, the Infi90 Interface checks the PI Server for changes to PI points whose PointSource is associated with the Interface. The Interface automatically incorporates these changes into its point list. The point attributes below define how to configure a PI point for use with the Infi90 Interface. The Location parameter determines whether a PI point is an input point (for reading a Bailey Net90/Infi90 value into the PI Server) or an output point (for sending a PI Server value to the Bailey Net90/Infi90).
TagA tag is a label or name fora point. Any tag name can be used in accordance with the normal PI point naming conventions. PI System documentation often uses the terms
tag and
point synonymously.
LengthFor OSIsoft interfaces
that are UniInt-based, the length of the Tag attribute field is limited by the version of the PI API and the version of the PI Server. However, the
Infi90 Interface is not UniInt-based. Thus, this Interface limits the length of tagnames to be 80 characters, independent of the version of the PI API or the version of the PI Server.
PI API
PI Server
Maximum Length
Share with your friends: