Procedure:
|
DOMESTIC COLD WATER TANK MAINTENANCE RECORD SHEET
|
Frequency:
|
Annually
|
Acceptance date:
|
Oct’12
|
File & Form Ref:
|
C - LEG07 [page 5 of 6]
|
Next review date:
|
Oct’14
|
Occupant Susceptibility Category:
|
Sample Required:
|
Where from:
|
Count above which action required:
|
Required action:
|
VERY HIGH
(Renal Dialysis, Cancer, AIDS, Respiratory Illness, Imuno-compromised, Elderly)
|
LEGIONELLA
(species and numbers)
|
Representative outlets as agreed with the consultant (specify)
|
>20
|
a) If limited outlets or count 20-40 = Re-sample at once, and disinfect if repeated again.
b) If more than 20% of outlets or counts 40+ disinfect at once, and review procedures.
|
TVC, E.coli, coliforms
|
Representative outlets as agreed with the consultant (specify)
|
TVC = >100
E.coli = >0
Coliforms = >0
|
a) If limited outlets give TVC counts of 100-500 then re-sample at once. If similar results from second sample then disinfect tank and system.
b) If more than 20% of outlets give TVC counts 100+ disinfect at once, and review procedures.
c) If TVC results give counts >500 sample the mains cold water unit a clear result is achieved. Then sample the cold water storage tanks, if these results are clean then no further action. If the results are returned positive then clean the cold water storage tank.
d) If any outlet returns E.coli or coliforms of >0 disinfect.
|
SIGNIFICANT
(All other Healthcare areas)
|
LEGIONELLA
(species and numbers)
|
1 MCW
1 of each Tank
2 TCW taps
2 DHWS taps
|
>100
>1000
|
Re-sample. Disinfect if fail.
Disinfect at once and review systems.
|
TVC, E.coli, coliforms
|
1 MCW
1 of each Tank
2 TCW taps
2 DHWS taps
|
TVC = >100
E.coli = >0
Coliforms = >0
|
a) If limited outlets give TVC counts of >100 = Re-sample at once, and disinfect if repeated again.
b) If more than 40% of outlets give TVC counts 100+ disinfect at once, and review procedures.
c) If TVC results give counts >500 sample the mains cold water unit a clear result is achieved. Then sample the cold water storage tanks, if these results are clean then no further action. If the results are returned positive then clean the cold water storage tank.
d) If any outlet returns E.coli or coliforms of >0 disinfect.
|