Engineering specifications



Download 198.81 Kb.
Page8/8
Date02.02.2017
Size198.81 Kb.
#15270
1   2   3   4   5   6   7   8

WATER FLOW SWITCHES





      1. Flow switches shall be integral, mechanical, non-coded, non-accumulative retard type.




      1. Flow switches shall have an alarm transmission time delay that is conveniently adjustable from 0 to 60 seconds. Initial settings shall be 30 or 45 seconds.




      1. Flow switches shall be located a minimum of 1 ft (0.3 m) from a fitting that changes the direction of the flow and a minimum of 3 ft (0.9 m) from a valve.



    1. SPRINKLER AND STANDPIPE VALVE SUPERVISORY SWITCHES





      1. Each sprinkler system water supply control valve riser, or zone control valve, and each standpipe system riser control valve shall be equipped with a supervisory switch. Standpipe hose valves, and test and drain valves shall not be equipped with supervisory switches.




      1. Each Post Indicator Valve (PIV) or main gate valve shall be equipped with a supervisory switch.




      1. The switch shall be mounted so as not to interfere with the normal operation of the valve and adjusted to operate within 2 revolutions toward the closed position of the valve control, or when the stem has moved no more than one-fifth of the distance from its normal position.




      1. The mechanism shall be contained in a weatherproof aluminum housing that shall provide a 3/4 in. tapped conduit entrance and incorporate the necessary facilities for attachment to the valves.




      1. Switch housing to be finished in red baked enamel.




      1. The entire installed assembly shall be tamper proof and arranged to cause switch operation if the housing cover is removed or if the unit is removed from its mounting.




      1. Valve supervisory switches shall be provided and connected under this section and installed by mechanical contractor.


    1. COLOR TOUCHSCREEN REMOTE LCD ANNUNCIATOR





      1. The remote annunciator shall provide a 4.3” color touchscreen LCD display that is identical to the control panel user interface. The annunciator shall be capable of displaying a custom background image when the system status is normal.




      1. The annunciator shall provide; a local sounder; discrete status LEDs for Alarm, Priority 2, Supervisory, Trouble, Alarm Silenced and AC power indications; and three programmable LEDs with associated control switches with provisions for custom labels. A lamp test feature shall be available from the display menu.




      1. The remote annunciator shall provide access to all system status information, controls, diagnostics, and reports that are available on the control unit user interface. Protected access shall be provided to the following operator control functions and diagnostics; Alarm, Priority 2, Supervisory and Trouble Acknowledge; Alarm Silence; and System Reset; Hardware Reset; Point Disable/Enable; Annunciator Sounder Silence, Clear History Logs; Panel Setup; and System Diagnostics. Protection against unauthorized use shall be provided via a passcode, keyswitch, or both.




      1. The annunciator shall have the capability to support up to two languages with the ability to toggle between languages using one of the programmable control switches on the annunciator.




      1. The annunciator shall connect to a two-wire Remote Unit Interface (RUI). The two-wire RUI connection shall be capable of distances of up to 2,500 feet (762 meters).




      1. The system shall support up to 6 remote color touchscreen LCD annunciators.


PART 4 SYSTEM ARRANGEMENT





    1. SAPPHIRE FIRE SUPPRESSION SYSTEM




      1. SAPPHIRE fire suppression system shall be of the engineered, permanently piped, fixed nozzle type with all pertinent components.




      1. All agent storage tank(s) shall be centrally located as vertical, free-standing with wall mounted retaining brackets. Where multiple cylinders are required for the same hazard, a common manifold shall be employed.




      1. On multiple cylinder arrangements (discharging into a common hazard), one cylinder shall be designated as the pilot cylinder and employ the restorable electric actuator, and mechanical manual actuator, or both. All remaining cylinders shall be pneumatically operated from the SAPPHIRE agent.




      1. Manifolded cylinders shall employ a flexible discharge hose to facilitate installation and system maintenance. Each cylinder on a manifold shall also include an agent check valve installed to the manifold inlet.



    1. FLOW CALCULATIONS





      1. Computerized verification of flow calculations shall be submitted for each SAPPHIRE fire suppression system and include the following data as a minimum:




        1. Quantity of agent per nozzle




        1. Nozzle orifice diameters




        1. Pressure at nozzle (psi)




        1. Nozzle body nominal pipe size (inch)




        1. Number and size of cylinders




        1. Total agent




        1. Pipe size per pipe section




        1. Pipe schedule per pipe section




        1. Number, size and type of fitting per pipe section




        1. Actual length per pipe section (feet)




        1. Equivalent length per pipe section (feet)




        1. Discharge time (seconds)

PART 5 EQUIPMENT AND MATERIAL (MECHANICAL)





    1. PIPE MATERIAL – SAPPHIRE SYSTEM




      1. System piping shall be of non-combustible materials having physical and chemical characteristics such that its integrity under stress can be predicted with reliability.




      1. Piping materials shall be Schedule 40 black iron, galvanized, chrome-plated, or stainless steel pipe conforming to ASTM A-53 or ASTM A-106.




      1. Under no conditions shall ordinary cast iron pipe or fitting be utilized.




      1. Piping joints shall be suitable for the design conditions and shall be selected with consideration of joint tightness and mechanical strength.




      1. As a minimum, fittings shall be black, 300 lb class fittings conforming to ANSI B-16.3.




      1. All piping shall comply with NFPA 2001.




      1. Piping shall be installed in accordance with good commercial practice to the appropriate codes, securely supported with UL Listed hangers and arranged with close attention to the design layout since deviations may alter the design flow performance as calculated.




      1. Piping shall be bracketed within 12 in. (305 mm) of all discharge nozzles.




      1. All piping shall be reamed, blown clear and swabbed with appropriate solvent to remove mill varnish and cutting oils before assembly.




      1. Pipe unions are acceptable.




      1. Reducing bushings and reducing fittings are allowed when reducing pipe size.




      1. Dead end pipe lines to be provided with a capped nipple, 2 in. (51 mm) long.




      1. Vertical drops on end of line are acceptable.




      1. Assembly of all joints shall conform to the appropriate standards. Threaded pipe joints shall utilize Teflon tape applied to the male threads only.



    1. EXTINGUISHING AGENT





      1. The SAPPHIRE fire suppression agent shall be 3M Novec 1230 Fire Protection Fluid manufactured by 3M Company, St. Paul, MN or their approved supplier.




      1. Agent shall not contain any Hydrofluorocarbons (HFC).



    1. SAPPHIRE STORAGE CYLINDERS





      1. The clean agent shall be stored in SAPPHIRE Clean Agent storage tanks. Tanks shall be super- pressurized with dry nitrogen to an operating pressure of 360 psi at 70 °F (24.8 bar at 21 °C). Tanks shall be of high-strength low alloy steel construction and conforming to NFPA 2001.




      1. Tanks (master) shall be actuated by either a resettable electric actuator or by pneumatic means from a nitrogen cartridge located in the releasing device. Explosive devices shall not be permitted.




      1. Each tank shall have a pressure gauge and low pressure switch (optional) to provide visual and electrical supervision of the container pressure. The low-pressure switch shall be wired to the control panel to provide audible and visual "Trouble/Supervisory" alarms in the event the container pressure drops below 290 psi (20.0 bar). The pressure gauge shall be color coded to provide an easy, visual indication of container pressure.




      1. Tanks shall have a pressure relief provision that automatically operates when the internal nominal pressure is between 710 and 790 psi (50.0 and 54.5 bar).



    1. TANK BRACKET





      1. Each tank assembly shall be furnished with at least one mounting bracket consisting of a nut, bolt and two bracket straps. The back channel must be supplied by others.




      1. Tank brackets shall be UL listed and/or FM approved for use with the SAPPHIRE fire suppression system.

    1. VALVE ACTUATORS





      1. Electric valve actuators shall be of steel body, stainless steel actuation pin and brass swivel connections to allow removal of actuators for maintenance or testing.




      1. Operation of actuators shall not require replacement of components. NO ELECTRO-EXPLOSIVE DEVICES may be used to actuate the valve assembly.




      1. Electric actuators shall be continuous duty type for 24 VDC operation.




      1. Actuation devices shall be UL listed and/or FM approved for use with the SAPPHIRE fire suppression system.



    1. DISCHARGE HOSE/CHECK VALVE





      1. When manifolding, all cylinder assemblies shall include a flexible discharge hose and check valve for connection to the manifold inlet.




      1. All hose/check valves shall be UL listed and/or FM approved for use with the SAPPHIRE valve.



    1. DISCHARGE NOZZLES





      1. Discharge nozzles shall be of one piece construction and sized to provide flow rates in accordance with system design flow calculations.




      1. The orifice size shall be determined by a computerized UL listed flow calculation program.




      1. Orifice(s) shall be machined in the nozzle body to provide a horizontal discharge pattern based upon the approved coverage arrangements.




      1. Nozzles shall be permanently marked with the manufacturer's part number. The nozzles shall be threaded directly to the discharge piping without the use of special adapters.




      1. Nozzles shall be UL listed.



    1. SYSTEM CHECKOUT AND TESTING





      1. The completed installation shall be inspected by factory authorized and trained personnel. The entire system shall be checked out, inspected, and functionally tested by qualified, trained personnel, in accordance with the manufacturer’s recommendation procedures and NFPA standards.




      1. Inspection shall be performed in the presence of the owner's representative, architect's or engineer's representative, insuring authority and/or the local AHJ.




      1. All mechanical and electrical components shall be tested according to the manufacturer's recommended procedure to verify system integrity.




      1. Inspection shall include a complete checkout of the detection/control system and certification of cylinder pressure. A written report shall be filed with the owner.




      1. As-built drawings shall be provided by the contractor (2 copies) indicating the installation details. All routing of piping, electrical conduit and accessories shall be noted.




      1. Equipment installation and maintenance manuals shall be provided in addition to the as-built drawings.




      1. Prior to final acceptance, the contractor shall provide operational training in all concepts of the system to the owner's key personnel. Training shall consist of:




        1. Control system operation

        2. Trouble procedures

        3. Abort procedures

        4. Emergency procedures

        5. Safety requirements

        6. Demonstration of the system (excluding SAPPHIRE release)

      1. The quantity of agent shall reflect the actual design quantity of SAPPHIRE agent.

PART 6 WARRANTY




    1. WARRANTY




      1. Environmental: The manufacturer shall offer a 20-year warranty covering regulations banning or restricting use of the SAPPHIRE agent due to environmental issues.




      1. Components/System: Limited one year warranty shall be offered for defects in workmanship and material.


Note: The converted metric values in this document are provided for dimensional reference only and do not reflect an actual measurement.
3M, NOVEC, and National Electrical Code are trademarks of their respective owners.
ANSUL, SAPPHIRE, AUTOPULSE and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.

Download 198.81 Kb.

Share with your friends:
1   2   3   4   5   6   7   8




The database is protected by copyright ©ininet.org 2024
send message

    Main page