3.3.6 Investigation and evaluation of current status of electromagnetic environment


In order to understand the current status of power frequency electric field, power frequency magnetic field intensity and radio interference level of surrounding environment of the project area, the construction unit entrusted Research Institute of Bureau of Geology for Nuclear Industry of Jiangxi Province to carry out measurement of current status of electromagnetic field intensity, radio interference level and noise environment of sensitive points passing the line. From August 6, 2012 to August 7, 2012, the monitoring unit carried out monitoring work to measure the current status of power frequency electric field intensity, magnetic field intensity and radio interference level around the proposed project. See Table 3-2-15 for climate condition during monitoring.

Table 3-2-15 List of climate conditions during monitoring period



Climate

Weather

Fine

Temperature

26°C-36°C

Relative humidity

53.7%-60.5%

Atmosphere

101.3kPa-101.5kPa

Wind speed

0.8m/s

(1) Measurement method

HJ/T10.2-1996 Guideline on Management of Radioactive Environmental Protection Electromagnetic Radiation Monitoring Instruments and Methods

GB/T7349-2002 Methods of Measurement of Radio Interference from High Voltage Overhead Power Transmission Line and Substation

(2) Measurement instrument

PMM8053B Power frequency electromagnetic field meter (Used for measuring power frequency electromagnetic field):

Probe: EHP50C

Manufacturer: Italy PMM.S.r.L Company

Measurement range: Electric field 0.01V/m-100kV/m

Magnetic field intensity 1nT-10mT

Verification Unit: SIMT

Certificate No.: 2011F33-10-000912

Valid period: 2012.7.25-2013.7.24

PMM9010 Field strength meter (used for measuring radio interference)

Manufacturer: Italy PMM Company

Frequency range: 10Hz-30MHz

Measurement range: 0dB-120dB

Verification unit: SIMT

Certificate No.: 001WJ51102

Valid period: July 25, 2012-July 24, 2013

(3) Layout of monitoring point

Lay the monitoring point along the sensitive points.

(4) Measurement result of 110kV Maozao Line relocation and modification project of Sanqingshan Airport

See Table 3-2-16 and Table 3-2-17 for measurement result of current status of power frequency electromagnetic field and radio interference environment of monitoring point:

Table 3-2-16 Measurement result of power frequency electromagnetic field environment of 110kV Maoze Line relocation and modification project of Sanqingshan Airport



No.

Description of Monitoring Point

Power frequency electric field intensity

(V/m)


Power frequency magnetic field intensity (µT)

Remarks

D1

Liaojia

45.91

0.039




D2

Xiaonantang

89.78

0.085




D3

Gaojiashan

20.17

0.025




D4

Houmentang

25.84

0.023




D5

Maopeng

26.02

0.034




D6

Gaobeiqiu

19.09

0.028




D7

Zhoujia

243.9

0.105

Influenced by 110kV line nearby

Limit value of the standard

4000

100




Table 3-2-17 Measurement result of current status of radio interference environment of 110kV Maozao Line relocation and modification project of Sanqingshan Airport

No.

Description of Monitoring Point

Frequency (MHz)

Radio

[dB(μV/m)]



Remarks

W1

Liaojia

0.5

26.6




W2

Xiaonantang

0.5

23.1




W3

Gaojiashan

0.5

20.8




W4

Houmentang

0.5

15.7




W5

Maopeng

0.5

14.2




W6

Gaobeiqiu

0.5

15.5




W7

Zhoujia

0.5

38.7

Influenced by 110kV line nearby

110kV voltage class

radio interference limit value



0.5

46




According to Table 3-2-16 and Table 3-2-17, the monitoring value of current status of power frequency electric field intensity and power frequency magnetic field intensity of each measurement point are respectively 19.09V/m-243.9V/m and 0.023µT-0.105µT; radio interference level at frequency of 0.5MHz is 14.2dB (μV/m) -38.7dB (μV/m). Electromagnetic field of all monitoring point satisfies the recommended value of Technical Regulations on Environmental Impact Assessment of Electromagnetic Radiation Produced by 500 KV Ultrahigh Voltage Transmission and Transfer Power Engineering (HJ/T24-1998): power frequency electric field intensity of 4000V/m and power frequency magnetic field intensity of 0.1mT; Radio interference level of monitoring point satisfies the regulation of Limits of Radio Interference from AC High Voltage Overhead Power Transmission Lines (GB15707-1995) at frequency of 0.5MHz: 110kV voltage class is 46dB (μV/m). The current status of power frequency electric field intensity, power frequency magnetic field intensity and radio interference level environmental quality of sensitive points along the area are good.

(5) Measurement result of 110kV Wangzao Line relocation and modification project of Sanqingshan Airport

See Table 3-2-18 and Table 3-2-19 for measurement result of current status of power frequency electromagnetic field and radio interference environment of monitoring point.

Table 3-2-18 Measurement result of current status of power frequency electromagnetic field environment of 110kV Maozao Line relocation and modification project of Sanqingshan Airport



No.

Description of Monitoring Point

Power frequency electric field intensity

(V/m)


Power frequency magnetic field intensity (µT)

Remarks

D1

Liaojia

45.91

0.039




D2

Xiaonantang

89.78

0.085




D3

Gaojiashan

20.17

0.025




D4

Houmentang

25.84

0.023




D5

Maopeng

26.02

0.034




D6

Gaobeiqiu

19.09

0.028




D7

Zhoujia

243.9

0.105

Influenced by 110kV line nearby

Limit value of the standard

4000

100




Table 3-2-19 Measurement result of current status of radio interference environment of 110kVMaozao Line relocation and modification project of Sanqingshan Airport

No.

Description of Monitoring Point

Frequency (MHz)

Radio [dB(μV/m)]

Remarks

W1

Liaojia

0.5

26.6




W2

Xiaonantang

0.5

23.1




W3

Gaojiashan

0.5

20.8




W4

Houmentang

0.5

15.7




W5

Maopeng

0.5

14.2




W6

Gaobeiqiu

0.5

15.5




W7

Zhoujia

0.5

38.7

Influenced by 110kV line nearby

110kV voltage class

radio interference limit value



0.5

46




According to Table 3-2-18 and Table 3-2-19, the monitoring value of current status of power frequency electric field intensity and power frequency magnetic field intensity of each measurement point are respectively 19.09V/m-243.9V/m and 0.023µT-0.105µT; radio interference level at frequency of 0.5MHz is 14.2dB (μV/m) -38.7dB (μV/m). Electromagnetic field of all monitoring point satisfies the recommended value of Technical Regulations on Environmental Impact Assessment of Electromagnetic Radiation Produced by 500 KV Ultrahigh Voltage Transmission and Transfer Power Engineering (HJ/T24-1998): power frequency electric field intensity of 4000V/m and power frequency magnetic field intensity of 0.1mT; Radio interference level of monitoring point satisfies the regulation of Limits of Radio Interference from AC High Voltage Overhead Power Transmission Lines (GB15707-1995) at frequency of 0.5MHz: 110kV voltage class is 46dB (μV/m). The current status of power frequency electric field intensity, power frequency magnetic field intensity and radio interference level environmental quality of sensitive points along the area are good.

(6) Measurement result of 10kV line newly built project from Maojialing Substation to Airport

See Table 3-2-20 and Table 3-2-21 for current status of power frequency electromagnetic field and radio interference environment of monitoring point:

Table 3-2-20 Measurement result of current status of power frequency electromagnetic field environment of 10 kV line newly established project from Maojialing Substation to Airport



No.

Description of Monitoring Point

Power frequency electric field intensity

(V/m)


Power frequency magnetic field intensity (µT)

Remarks

D1

Caijiatianpeng

203.5

0.449

Influenced by 110kV line nearby

D2

Xiaonantang

89.78

0.085




D3

Zhoutian

36.49

0.034




Table 3-2-21 Measurement result of current status of radio interference environment of 10 kV line newly established project from Maojialing Substation to Airport

No.

Description of Monitoring Point

Frequency

(MHz)


Radio

[dB(μV/m)]



Remarks

W1

Caijiatianpeng

0.5

38.9

Influenced by 110kV line nearby

W2

Xiaonantang

0.5

23.1




W3

Zhoutian

0.5

35.5




According to Table 3-2-20 and Table 3-2-21, the monitoring value of current status of power frequency electric field intensity and power frequency magnetic field intensity of each measurement point are respectively 36.49V/m-203.50V/m and 0.034µT-0.449µT; radio interference level at frequency of 0.5MHz is 23.1dB (μV/m) -38.9dB (μV/m). The current status of power frequency electric field intensity, power frequency magnetic field intensity and radio interference level environmental quality of sensitive points along the area are good.

(7) Measurement result of 10kV line newly built project from Zaotou Substation to Airport

See Table 3-2-21 and Table 3-2-22 for measurement result of current status of power frequency electromagnetic field and radio interference environment of monitoring point:

Table 3-2-21 Measurement result of current status of power frequency electromagnetic field environment of 10 kV line newly established project from Zaotou Substation to Airport



No.

Description of Monitoring Point

Power frequency electric field intensity

(V/m)


Power frequency magnetic field intensity (µT)

Remarks

D1

Flag pole top

188.5

0.314

Influenced by 110kV line nearby

D2

Shanggao

173.1

0.402

Influenced by 110kV line nearby

D3

Shigu

23.03

0.027




D4

Xiaojia

25.45

0.023




D5

Xujia of Tashui Village

28.42

0.029




Table 3-2-22 Measurement result of current status of radio interference environment of 10 kV line newly established project from Zaotou Substation to Airport

No.

Description of Monitoring Point

Frequency

(MHz)


Radio

[dB(μV/m)]



Remarks

W1

Flag pole top

0.5

38.9

Influenced by 110kV line nearby

W2

Shanggao

0.5

33.5

Influenced by 110kV line nearby

W3

Shigu

0.5

20.9




W4

Xiaojia

0.5

17.3




W5

Xujia of Tashui Village

0.5

21.2




According to Table 3-2-21 and Table 3-2-22, the monitoring value of current status of power frequency electric field intensity and power frequency magnetic field intensity of each measurement point are respectively 23.03V/m-188.5V/m and 0.023µT-0.402µT; radio interference level at frequency of 0.5MHz is 17.3dB (μV/m)-38.9dB (μV/m). The current status of power frequency electric field intensity, power frequency magnetic field intensity and radio interference level environmental quality of sensitive points along the area are good.