INSTALLATIONOPEN SYSTEMS MANAGER INSTALLATION - 10
WBPEEUI350001B0
®
2. Attach the MAU transceiver at a marked location on the thick Ethernet cable (cable is marked every 2.5 meters) if using a coaxial tap connection. Several types of cable tap kits are available. Follow the instructions provided with the kit being used. For MAU transceivers
with BNC connectors, terminate the coaxial cable with a BNC connector at the desired cable marking and connect it to the MAU transceiver. Attach the other end of the AUI drop cable to the MAU transceiver (Figure
3-8
).
3. Effectively ground the trunk coaxial cable shielding by permanently connecting it to earth ground atone end of the cable or atone point along the cable.
POWER WIRINGThere are two terminals (E and Eon the NTSM01 termination unit for connecting 24 VDC power and IO common. To install 24 VDC power wiring. Crimp quick-connect connectors to both ends of two 14
AWG insulated wires. Attach one wire to a 24 VDC quick-connect tab on the system power bus bar. Attach the other end of the wire to the E1
quick-connect tab on the termination unit. Attach the other wire to an IO common quick-connect tab on the system power bus bar. Attach the other end of the wire to the E quick-connect tab on the termination unit.