Open Systems Manager
INSTALLATION
OPEN SYSTEMS MANAGER INSTALLATION
WBPEEUI350001B0 3 - 9
Type Base Installation (Thick Ethernet)
The NTSM01 termination unit has an attachment unit interface (AUI) connection for Type Base cable. This connection requires a medium attachment unit (MAU) transceiver to attach a trunk coaxial cable to an AUI drop cable. The MAU
transceiver can have a coaxial tap connection or a BNC connector, provided the constant impedance of the BNC connector on the MAU transceiver is 50 ohms. The MAU transceiver to coaxial cable connection should be as short as possible (less than 30 millimeters (1.2 inches) so that the connection does not significantly disturb transmission line characteristics.
One-watt coaxial cable terminators with the characteristic impedance of the coaxial cable (50 ohms) should be installed to minimize reflections from the ends of cables.
The trunk coaxial cable shielding should be effectively grounded to earth ground. Effectively grounded means that the earth ground connection has a sufficiently low impedance and sufficient ampacity to prevent the buildup of hazardous voltages. Make a permanent connection to earth ground via the ground lug on one of the terminators atone end of the cable. A single ground return lug on a segment connector located in the center of the cable transmission system maybe used to satisfy this requirement. To install. Attach one end of a drop cable to the AUI connector (P) on the TSM termination unit (Figure
3-8
). Tighten the screws on the AUI connector to secure it to the termination unit.
Figure 3-8. Attaching Trunk Coaxial Cable
to MAU Transceiver
TO
ETHERNET
NETWORK
TO
AUI PORT
ON NTSM01
TERMINATION
UNIT
MALE
FEMALE
MAU
TRANSCEIVER
THICK
ETHERNET
CABLE
T00579A
COAXIAL
TAP
CONNECTION


INSTALLATION
OPEN SYSTEMS MANAGER INSTALLATION - 10
WBPEEUI350001B0
®
2. Attach the MAU transceiver at a marked location on the thick Ethernet cable (cable is marked every 2.5 meters) if using a coaxial tap connection. Several types of cable tap kits are available. Follow the instructions provided with the kit being used. For MAU transceivers with BNC connectors, terminate the coaxial cable with a BNC connector at the desired cable marking and connect it to the MAU transceiver. Attach the other end of the AUI drop cable to the MAU transceiver (Figure
3-8
).
3. Effectively ground the trunk coaxial cable shielding by permanently connecting it to earth ground atone end of the cable or atone point along the cable.
POWER WIRING
There are two terminals (E and Eon the NTSM01 termination unit for connecting 24 VDC power and IO common. To install 24 VDC power wiring. Crimp quick-connect connectors to both ends of two 14
AWG insulated wires. Attach one wire to a 24 VDC quick-connect tab on the system power bus bar. Attach the other end of the wire to the E1
quick-connect tab on the termination unit. Attach the other wire to an IO common quick-connect tab on the system power bus bar. Attach the other end of the wire to the E quick-connect tab on the termination unit.