ConocoPhillips Company Loss of Cogeneration Units 102210-1 #144138 6
Sequence of Events:
TIME EVENT
1043 Air Liquide shutdown of Unit 120 1044
SPP A Turbine shutdown
on high basket temperature 1100 Steam Curtailment Implemented as 600# Steam sags to 400#
1113
CWS Level 1 – Excessive Flaring
1200 600#
Steam recovers to 450-500#
1319 A Turbine running with COENS > 600# Steam
1357 A Turbine shutdown by generator trip
1411 Steam
Injection Air Purge Activated 1412
SPP C Turbine shutdown – flameout
1427
SPP B Turbine shutdown on high basket temperature
1430
Refinery Flare Smoking 1437
CWS Level 2 – Smoke visible offsite U depressurizing to flare