/stopstat=”Intf Shut” The entire parameter is enclosed within double quotes when there is a space in digstate.
/to=# Optional
Default:
/to=90 Maximum: /to=240
This parameter specifies the ICI module watchdog timer. If the interface stops communicating with the ICI module for a period longer than the specified watchdog timer, the ICI module will go off-line, setting all the output points (PI to Bailey) to bad quality. For systems using PI values in the Bailey control loops, the watchdog timer will prevent the old value from being used in the control loop. Also, do not set the watchdog timer to 0 if the interface is set up as failover primary interface. Otherwise, the secondary interface will not pick up data collection when the primary interface stops communicating with the ICI module. See the Failover Operation section for details.
/ts=0'>/ts=# Optional
Default:
/ts=0
This parameter controls the time synchronization behavior between Bailey and PI systems. Note that the interface cannot change the PI system time. Also, if the interface is linked to a Data Acquisition version of semAPI, the interface cannot set the time on the Bailey System. The time master of the loop is determined by the time accuracy factor on each node. Hence, the time accuracy must be set to 15 or greater on the CIU module through the CIU utilities by connecting a terminal to the CIU termination unit. See the CIU manual for details on how to use the CIU utilities.
/ts=0 disables time synchronization
/ts=1 sets PI time as the master time
Default = 0 (disabled)
Minimum = 0
Maximum = 1
Sample blysem.bat File
The interface takes a number of optional parameters to control its operation. These parameters may be specified in the interface command file blysem#.bat for use on Windows.
The following is an example file for use on Windows: