User Requirements Template for a Supervisory Control and Data Acquisition (scada) Process Control System notes for use of the User Requirements Template


II.4.Exclusions and Future Considerations



Download 396.6 Kb.
Page4/9
Date31.01.2017
Size396.6 Kb.
#13752
1   2   3   4   5   6   7   8   9

II.4.Exclusions and Future Considerations


The S88.01 standard and the utilized hardware/software platform provide extensive capabilities within a batch environment. has elected to limit the initial implementation of select batch capabilities, favoring a high level of manual process interaction by operating personnel, supported by Standard Operation Procedure (SOP) driven paper system(s). This initial operating philosophy does not imply that future enhancement(s) will not take greater advantage of the capabilities provided by the PCS, but does significantly impact functions commonly associated with a S88.01 batch facility.

The PCS functionality is limited as follows:



  • Implemented procedures pertain exclusively to CIP and SIP functions. All other sequential functionality required is implemented at the unit phase level. Manufacturing operations will be performed by manually initiating equipment phases as required. Additionally, prior to initiating a phase, the operator may be required to manually perform any set-up required such as: verifying/placing all process unit valves in automatic mode, verifying/placing all control modules are in automatic mode, etc.

  • It is ’s intent to continue development of various facility procedures, beyond those initially provided at PCS startup. It is the intent that phases developed for the
    project be suitable for use in these future procedure development activities. Where feasible, procedures and operations are designed and implemented as a library of phase “building blocks”, even though a given phase may not be utilized in a procedure at the time of PCS startup. It is understood that the phase library at PCS startup, may not include all phases necessary to support continued procedure development, without the need for development of additional phases.

In lieu of PCS implementation, SOP driven, manual paper system(s), are used to perform the following functions:

  • Tracking process equipment “fitness for use” for a specific function (such as “Clean”, “Sterile”, “Full”, “Empty”, etc.), as well as equipment sterility expiration. When a PCS phase/procedure is initiated by an operator, it is the operator’s responsibility, supported via manual paper systems, to ensure the subject process equipment is suitable for the PCS phase or procedure application. The PCS ensures that the subject process equipment is available and not currently in-use by another phase/procedure. The PCS equipment model only maintains process unit statuses of “In-Use” or “Available”. Additional statuses or states pertaining to a unit’s fitness for use are not required.

  • Material tracking, including all batch/lot material and intermediate product genealogy tracking.

  • Batch/lot tracking, including batch/lot reporting. PCS-generated “electronic tickets” and automated batch reports are not required. Additionally, PCS is not required to maintain or track unique batch identifiers. Lot Identifiers and Product Codes are manually input to the PCS at appropriate process intervals and utilized for historical data record retention as key fields.


III.0OPERATIONAL REQUIREMENTS

III.1.Functions

III.1.1.Process Monitoring

III.1.1.1.Real-Time Data Collection and Dissemination


The
collects process data, as transmitted from process instrumentation, and makes the process data available for any or all of the following:

  • Basic Data Processing (i.e., conversion to digital data in engineering units),

  • Process Alarm Detection and Alarm Management,

  • Processing to accomplish control strategies,

  • Display to PCS users, and

  • Historical data collection.

Data from other sources (user inputs, recipes, tunable parameters, intelligent devices, etc.) are combined with process data into a single logical database that defines, in real time, the known state of the process. Control strategy algorithms produce process control outputs that are also combined into the logical database to complete the process state definition.

Design of PCS data collection features shall consider all of the following:



Factor

Description

Required immediacy

Response time for value display and alarming, historical data collection frequency, and control processing requirements should dictate the minimum acceptable data collection and transfer rates.

Required precision

Insignificant digits should not be presented to users, historically collected, or considered in data processing.

Data consistency

In some component systems, communication delays may introduce transient and/or scan-based differences in data values. Data collection design must prevent inconsistent display, control response, and historical collection of alarm and other threshold events. The design must also avoid other data collection and communication mechanisms that could result in sustained inaccuracies between display data, historical data, and control processing data.

Future expansion and/or enhancement

Hardware, software, and communications design should provide capacity for future expansion and potential changes to control and/or display strategies.

Fault tolerance

The PCS must be designed to prevent any individual failure from jeopardizing personnel safety and/or product quality. Where PCS features are instrumental in protecting personnel and/or product quality and/or major processing equipment, a Failure Modes and Effects Analysis (or comparable risk assessment) is required.


III.1.1.2.Basic Data Processing


All data monitored by the PCS shall be immediately converted to standard engineering units prior to use in any comparison or control logic. This conversion should also include normalization of discrete data values (e.g., so that “1” always represents the “alarm” state for a discrete input alarm and the “open” state for a valve). Process control outputs should undergo similar conversions immediately prior to transmittal.

III.1.1.3.Process Alarm Detection


Process alarm detection functionality compares data values against range and alarm limits. Range errors and alarms should be propagated, as appropriate, to subsequent data processing logic. All non-discrete dynamic system inputs automatically monitored by the PCS should be subjected to both range checking and appropriate alarm checking.

All non-discrete manual system inputs should also be subjected to range checking. Out-of-range manual data entries should be rejected (with an appropriate message explaining why the value was rejected) and/or treated as a process alarm (i.e., annunciated and subjected to alarm management functions), as appropriate. All manual entries, including rejected entries, should be recorded in PCS event logs, if practicable.


III.1.2.Alarm Management

III.1.2.1.Alarm Configuration


The PCS must provide for configuration of alarms to detect unexpected process excursions for operator notification and /or response. Two basic types of alarms must be supported by the PCS, process alarms and equipment alarms. Process alarms differ from equipment alarms in that their parameters such as, setpoint, time delay, deadband, etc must be modifiable during progression of a batch process on a per step basis from the phase logic. Equipment alarm parameters are tuned to meet the specific equipment requirements and once set, are only modified if physical changes occur to the equipment. Both types are subjected to the alarm management requirements described in this section.

The “Locally Controlled Packaged Equipment” section discusses the operator interface with vendor provided control system(s) on packaged equipment. Alarms originating within these vendor provided control system(s), but displayed on PCS screens, are also subject to the alarm management requirements as described within this section.

The system shall provide for process alarm priorities, a minimum of five levels, which are selectable during configuration. At least one of the priority levels will represent alarms that affect the quality of the batch (GMP alarm level). Other alarm priorities will be assigned to equipment protection, personnel safety and operator information.

The S88 concept of process units, grouped in plant cells and areas will allow for alarm enable/disable of those groupings (e.g. during maintenance, shutdown etc.). Additionally, it will also be possible to suppress temporarily (override), with proper authority, an individual alarm caused by a defective device. Operator alarm override actions will be recorded by the system and will automatically be reset at the beginning of each controller resident phase.

The system shall support the following configuration parameters for each alarm


  • Type of Alarm – Absolute alarm, Offset from Setpoint, Percent Offset from Setpoint.

  • Alarm Setpoints for low-low, low, high and high-high severity levels

  • Alarm Priority – minimum of five levels definable during configuration

  • Alarm Delay - time delay of alarm conditions to eliminate alarms associated with momentary measurement spikes (e.g., an alarm condition must exist for 5 seconds before activating an alarm).

  • Alarm Deadband – the ability to configure an alarm to turn on at one value and clear at another Ramp setpoints and configure alarms as setpoint +/- tolerance. This helps minimize nuisance alarms associated with normal control loop setpoint changes.

  • Pause Enable – Configurable ability for alarm activation to cause running batch logic to pause. Note alarm point must be directly associated with a process unit.

III.1.2.2.Alarm Acknowledgement


Operators must be logged on to the PCS and have the proper authority as enforced by PCS security to acknowledge alarms. The PCS shall record in the operator action log all acknowledgement activities. The operator’s electronic signature, the action taken, date and time must be recorded with each acknowledgement. The PCS shall support two means for operators to acknowledge alarms, on an individual basis, and on a group basis. The group shall be all current unacknowledged alarms displayed on the alarm list. Note that group acknowledgement shall result in an entry in the operator action log for each individual alarm.

III.1.2.3.Alarm Output devices


The system shall support the following output devices. System configuration shall allow for changes in alarm states to activate any combination of the devices:

  • Console screen (visual)

  • Console screen (audible)

  • Control room or plant floor flashing light and/or horn

  • Alarm printer

  • Annunciator panels

III.1.3.Basic Control

III.1.3.1.Concept


Basic control consists of algorithms performed on monitored data values (including process control inputs, user inputs, tunable parameters, and constants) to determine the state of process control outputs. Included in basic control are normal control module algorithms (valve control, pump control, feedback loop control, etc.) and interlocking.

Basic control is intended to be completely independent of the intended use of the process equipment. This provides the flexibility to permit manual operations that may:



  • Not have been anticipated during the process and/or control system design,

  • Require some level of operator protection (alarms, interlocks, etc.),

  • Require documented evidence of what was done, and/or

  • Require some level of automation (input scaling, closed-loop control, etc.).

III.1.3.2.Control Modules


A control module is a regulating device, a state-oriented device, or a combination of regulating and state oriented devices that is operated as a single device. Examples of control modules include block valves, modulating valves, PID controllers, fixed-speed motors, and variable speed motors. Design of PCS control modules shall consider all of the following:

Factor

Description

Commonality and consistency

All control modules should be instantiated from a limited number of control module classes. Uncommon control module attributes (e.g., reverse-acting limit switch) should be transparent to PCS users where appropriate.

Class attributes

Each control module class should have a specific and well-defined set of attributes. Typical attributes include:

  • Setpoint (open, close, 50%, etc.),

  • State (open, closed, etc.),

  • Requested Mode (manual, automatic, etc.)

  • Mode (manual, automatic, etc.), and

  • Fault (failed to start, deviation from setpoint, etc.).

Control request management

Control modules should be designed to seamlessly accept, and respond appropriately to, mode, state, and setpoint requests from:

  • User interface(s) (including local control stations),

  • Supervisory processes (e.g., phases), and

  • Interlocks.

Control module interfaces should, where possible, clearly identify the current state, the current mode, and the source of active control. Invalid user inputs should, where possible, produce a message identifying the reason the input will not be processed.

Bumpless transfer

Control module mode changes should not cause an immediate corresponding change in control module state, setpoint, or output.

Fault annunciation and response

Every unexpected combination of I/O states (and/or values) should result in a specific failure alarm (e.g., “valve uuu-XV-iiii failed to open”). Control module fault response should be designed to mitigate risk to personnel, product, and equipment.

Harmony with supervisory control

Control modules may be subordinate to supervisory objects including complex modules (e.g., header or dispensing system) and phases. Mode changes and faults in subordinate control modules shall either:

  • Propagate the mode or fault to the supervisory object, or

  • Override the subordinate mode and/or fault monitoring and comprehensively replace it with mode and/or fault monitoring by the supervisory object.

Data utilization

All relevant data (I/O, user requests, parameters, etc.) shall be appropriately considered by the control module algorithms. For example, if a block valve includes both an Open limit switch and a Closed limit switch, the state of both switches should be considered in determining the actual state of the valve.

Harmony with simulation

Where applicable and possible, installed simulation activation and I/O forcing shall be obvious from all impacted user interfaces and reports.


III.1.3.3.Interlocks


Interlocks modify control module states in response to process conditions in order to protect personnel, process equipment, and/or product. Design of PCS interlocks shall consider all of the following:

Factor

Description

Product independence

Interlock functionality should not consider current product processing requirements. In general, interlocks should only be applied for personnel protection, equipment protection, and/or prevention of product contamination.

Harmony with supervisory control

Control modules may be subordinate to supervisory objects including complex modules (e.g., header or dispensing system) and phases. Interlocks in subordinate control modules shall either:

  • Propagate the interlock to the supervisory object, or

  • Disable (fault) the supervisory object, or

  • Override the subordinate interlock and replace it with a complimentary interlock and/or fault monitoring by the supervisory object.

Overrides

The ability to manually override interlocks, if available, shall be reserved for engineering and maintenance users.

Display

Control module interfaces should, where possible, clearly identify whether or not a control module interlock is active. The specific cause of the interlock should be either displayed as part of the control module interface and/or readily accessible from the control module interface.

Record of interlock events

Historical data collection must include a record of interlock-related events (activation, clearing, overrides, etc.). Reports that include a list of alarms and events should include interlock-related events.


III.1.3.4.Complex Modules


Complex modules include control modules with subordinate control modules and equipment modules with subordinate equipment modules and/or control modules. Common complex modules include:

  • Header valve groups (where the complex module setpoint identifies a transfer source, a transfer destination, or a source-destination pair)

  • Batch dispense stations (including a flow control valve, a totalizer, and one or more block valves)

  • Temperature control module (where media routing valves are controlled based on a desired vessel jacket state or temperature setpoint)

NOTE: Complex Modules are differentiated from Equipment Phases which are controlled through the Batch Manager interface. A complex module is an independent object that can be utilized with and/or without the Batch Manager. PCS design need only include complex modules if routine non-automatic production is anticipated and manual equipment phase control is too cumbersome for this routine non-automatic production.

Design of PCS complex modules shall consider all of the following:



Factor

Description

Commonality and consistency

All complex modules should be instantiated from a limited number of complex module classes. Uncommon complex module attributes (e.g., extra routing valves) should be transparent to PCS users where appropriate.

Class attributes

Each complex module class should have a specific and well-defined set of attributes. Typical attributes include:

  • Setpoint (Vxxxx-Vyyyy, charge, jacket control, etc.),

  • State (Vxxxx-Vyyyy, charge, jacket control, etc.),

  • Requested Mode (manual, automatic, etc.)

  • Mode (manual, automatic, etc.), and

  • Fault (failed to start, deviation from setpoint, etc.).

Control request management

Complex modules should be designed to seamlessly accept, and respond appropriately to, mode, state, and setpoint requests from:

  • User interface(s) (including local control stations),

  • Supervisory processes (e.g., phases), and

  • Interlocks.

Complex module interfaces should, where possible, clearly identify the current state, the current mode, and the source of active control. Invalid user inputs should, where possible, produce a message identifying the reason the input will not be processed.

Bumpless transfer

Complex module mode changes should not cause an immediate corresponding change in complex module state, setpoint, or output.

Fault annunciation and response

Every unexpected combination of control module states (and/or values) should result in a specific failure alarm (e.g., “valve uuu-XV-iiii failed to open”). Complex module fault response should be designed to mitigate risk to personnel, product quality, and process equipment.

Harmony with supervisory phases

Mode changes and faults in complex modules that are subordinate to a phase shall either:

  • Propagate the mode or fault to the phase, or

  • Override the subordinate mode and/or fault monitoring and comprehensively replace it with mode and/or fault monitoring at the phase level.

Harmony with simulation

Where applicable and possible, installed simulation activation and I/O forcing shall be obvious from all impacted user interfaces and reports.


III.1.4.Equipment Phase Control

III.1.4.1.Concept


Equipment phases provide all of the recipe-driven processing functionality of the PCS. Each equipment phase provides a strategic combination of regulatory and sequential control intended to exploit a specific processing capability of the equipment. The following principles should guide the identification of equipment phases:

  • Equipment phases should be based on process equipment capability and should in no way be product-specific,

  • Equipment phases should operate autonomously, except as necessary to coordinate material transfers or other multi-unit activities,

  • Equipment phases should not share control modules with other equipment phases except where necessitated by process equipment design, and

  • Shared equipment phases and shared control modules should not unnecessarily restrict or otherwise interfere with parallel activities.

III.1.4.2.Normal Operation


Once initiated, an equipment phase typically initiates appropriate monitoring (e.g., fault detection) and proceeds through an orderly sequence of steps. The quantity and identity of steps should be sufficient to clearly distinguish the equipment phase progress and to support orderly restart logic.

If general, successful equipment phase operation should not be contingent upon:



  • The execution of previous equipment phases, or

  • The execution of parallel equipment phases (except as needed for product transfers), or

  • The execution of subsequent equipment phases, or

  • The anticipated state or status of uncontrolled equipment.

III.1.4.3.Exception Handling


Equipment phase exception handling should respond, as appropriate, to controlled equipment alarms, interlocks, and faults, unexpected process deviations, invalid parameter values, communication faults, and user intervention commands. Exception handling should be sufficiently “exception-specific” in order to provide the least intrusive response that still provides adequate personnel, equipment, and product protection. For example, a product temperature deviation should not necessarily disable automatic temperature control.

Equipment phase exception handling should be sufficiently robust that:



  • Direct and immediate actions are taken to ameliorate any condition that jeopardizes personnel, equipment, or product,

  • Exception handling actions are appropriate to both the type of exception and the progress of the equipment phase sequence at the time of the exception,

  • Equipment phase execution is not interrupted by minor anomalies that are unlikely to jeopardize personnel, equipment, or product (though operator notification of all anomalies is generally required),

  • The response of concurrently executing equipment phases is appropriately impacted to preserve the integrity of a Unit Operation,

  • The equipment phase, and associated Unit Operation, can be restarted by an operator with a minimum of extraordinary manual restart preparations (e.g., by simply commanding the Unit Operation to restart), and

  • Restarting an equipment phase, and associated Unit Operation, should automatically resume manufacturing operations without unnecessarily repeating steps or extending execution times (e.g., by unnecessarily resetting totalizers, counters and timers).


III.1.5.Batch Management


The
automation solution includes both the PCS and a batch management system. The PCS shall be implemented within the framework of the Instrument Society of America (ISA) standards S88.01, Standard for Batch Models and Terminology, and draft standard dS95.01, Standard for Enterprise – Control System Integration Models and Terminology. The use of these standards supports application of industry standard software packages and provides for flexibility and modularity required by the business and automation objectives. The S88.01 control activity model defines the following activities

  • Production Planning and Scheduling

  • Information Management

  • Recipe Management

  • Process Management.

  • Unit Supervision and

  • Process Control

The focus of this PCS is the Process Control activities defined by the S88 Standard. This section defines the interface requirements for the PCS to the Unit Supervision, Process Management and Recipe Management activities implemented by the Batch Management System as well as the required operator interfaces to these control activities. The Batch Manager Interface (BMI) is required to:



  • Provide an operator interface for manual control of batch state transitions

  • Report status for equipment procedural logic elements used as a part of recipe execution

  • Provide download and upload capability for recipe parameters

  • Provide for PCS ad hoc event reporting to the Batch Manager.

III.1.6.Historical Data Collection and Retention

III.1.6.1.Historical Data Values


Key process and production data values shall be collected and retained in a historical database. Since these data are important electronic records, the PCS should employ appropriate provisions for secure data collection and retention (e.g., automatic daily backup, disaster recover provisions, long-term data archiving and restoration procedures, etc). Existing site database facilities, capabilities, and procedures should be exploited, if possible. Historical data shall be accessible for display in historical trends and, as applicable, reports.

III.1.6.2.Alarms and Events


Process alarm and event data shall be accumulated in a historical database. Each record shall include a date/time stamp, Batch/Lot identifier and the source process unit as the primary keys for data retrieval. Since these data are important electronic records, the PCS should employ appropriate provisions for secure data collection and retention (e.g., automatic daily backup, disaster recover provisions, long-term data archiving and restoration procedures, etc). Existing site database facilities, capabilities, and procedures should be exploited, if possible. Historical alarm and event data shall be accessible for inclusion in onscreen displays and, as applicable, reports.

III.1.7.Other Monitoring and Control Features

III.1.7.1.Locally Controlled Packaged Equipment


Select process equipment is packaged in a stand-alone configuration that includes sufficient local control capability to perform the intended functionality. These packaged systems are designed to include the necessary interface capability to permit communication with the PCS. It is the responsibility of the System Integrator to coordinate with the packaged equipment vendor(s) to determine the appropriate PCS control strategy, general interface requirements, etc. Where practicable, PCS interface to packaged equipment should follow S88 paradigms (e.g., by treating the packaged equipment operation as an equipment phase).

III.1.7.2.Resource Management


Modes, states, statuses, and other attributes of all process resources (including process units, bulk material supplies, logical modules such as totalizers, etc.) should be clearly defined and appropriately managed. User interfaces to these process resources should provide for attribute monitoring and, with appropriate security, manual adjustment. Managed resource attributes (e.g., bulk material supply “Ready” status and process unit “Clean” status) should be considered in Basic Control interlocks and Equipment Phase exception handling, as appropriate.

III.1.7.3.Engineering Parameters


In general, hard-coded values related to both Basic Control and Equipment Phase Control should be scrupulously avoided. Instead, tunable variables and/or constants should be identified, initialized, and used throughout the control logic. Examples of tunable variables and/or constants, referred to generally as “Engineering Parameters”, include:

  • Scaling constants and alarm limits,

  • Deadbands and delays,

  • Controller tuning constants,

  • Dispensing pre-action limits and tolerances, and

  • Conversion constants (e.g., material specific gravity).

III.1.8.Modes of Operation

III.1.8.1.Startup


System documentation shall include detailed procedures for starting the PCS (in total) and for starting individual PCS components, as appropriate. On startup, the PCS shall maintain controlled process equipment in its pre-defined safe (typically de-energized) state until specific user commands are applied to begin process control.

To the extent possible, PCS event log(s) shall record events indicating the startup of PCS components. The ability to restart the PCS components after an abnormal shutdown (e.g., power interruptions) shall, in general, be available to any user with a valid PCS user account.


III.1.8.2.Shutdown


System documentation shall include a detailed procedure for performing a controlled and complete shutdown of the PCS. PCS shutdown shall cause controlled process equipment to revert to a pre-defined safe (typically de-energized) state.

The ability to shutdown the PCS shall be restricted to Supervisors, System Administrators, Engineering, and Maintenance personnel. PCS event log(s) and/or alarm log(s) shall indicate the normal shutdown of any PCS component. Where possible, PCS event log(s) and/or alarm log(s) shall indicate abnormal PCS component shutdowns (e.g., power interruptions).


III.1.8.3.Normal Operation


On PCS restart according to the PCS startup procedure(s), normal operation shall be enabled. System documentation shall include detailed procedures for normal PCS operation (e.g., display elements and navigation, starting batches, using control modules, etc.). The ability to perform normal PCS operations shall be based on privileges associated with the user’s account.

III.1.8.4.Simulation


The PCS shall include process simulation capability including:

  • The ability to temporarily force any discrete or analog input to any valid value, and

  • The ability to set individual control modules feedback simulation to “auto-respond” to control module states (e.g., Open feedback energizes and closed feedback de-energizes whenever the valve stat is OPEN).

The ability to enable simulation shall be restricted to Supervisors, System Administrators, Engineering, and Maintenance personnel. PCS event log(s) and/or alarm log(s) shall indicate transitions to/from simulation mode.

III.1.8.5.Disaster Recovery


System documentation shall include detailed procedures for a complete re-install of software on each PCS component. These procedures shall include sufficient detail to completely re-build the PCS from purchased hardware and archived software. Independent electronic copies of all software required to re-build the PCS shall be supplied with the PCS.

III.1.9.Performance and Timing

III.1.9.1.PCS Performance


PCS performance should be adequate to provide a safe, effective, and responsive system. The following guidelines are intended to indicate performance expectations:

Activity/Event

Performance Expectation

Process Monitoring and Basic Control Response

PCS control responses (e.g., PID controller output change in response to a deviation from setpoint) should be commensurate with the potential significance of the process change. For example:

  • Slow-moving regulatory response (e.g., vessel temperature control) should occur within five (5) seconds.

  • Fast-moving regulatory response (e.g., line pressure control) should occur within one (1) second.

Process Input Display

PCS display of process condition changes should be commensurate with the potential significance of the process change. For example:

  • All changes in process conditions (i.e., instrument readings and discrete feedback states) should be reflected in PCS displays within five (5) seconds.

  • For process conditions that can exhibit rapid and significant changes (e.g., pressure and flow readings, vessel rupture disks), changes should be reflected in PCS displays within two (2) seconds.

User Control Command

Evidence of PCS response to user commands (e.g., changing control module states, starting a batch) should be presented to the user within one (1) second (e.g., by changing a “commanded state” indication). Process control response to user commands should be commensurate with the potential significance of the requested change. For example:

  • A valid user command to start a batch should activate the first equipment phase within ten (10) seconds.

  • A valid user command to change the state of a control module should change the appropriate control output within two (2) seconds.

Display Navigation

Evidence of PCS response to a user command to change displays should be presented to the user within one (1) second. The target display should be completely painted, with up-to-date data values, within five (5) seconds.

Workstation Synchronization

When a process attribute is changed from one workstation, the attribute change must be reflected on other workstation displays. Such attribute changes should be reflected on all workstations within three (3) seconds.

PCS Startup

In general, it should be possible to bring the PCS from a de-energized state to a full working state within fifteen (15) minutes.

PCS Shutdown

In general, it should be possible to bring the PCS from a full working state to a fully de-energized state in a controlled manner within fifteen (15) minutes.


III.1.9.2.Date and Time


The PCS shall be designed to minimize and, as necessary, compensate for differences in date and time values among PCS components. The following is a description of the recommended date/time compensation procedure for a networked PCS:

A single “timekeeper node” shall be designated for the PCS. The date/time value for the timekeeper node will be periodically reconciled to a known accurate date/time source. Timekeeper node date/time value should not normally deviate from the known accurate date/time source value by more than ten (10) seconds between periodic reconciliations. If manual intervention is required to reconcile the timekeeper node date/time value, reconciliations should not be required more frequently than once per week.



PCS nodes that base any activity, log, or display on the local date/time value should automatically (i.e., without user intervention) reconcile their date/time value with the timekeeper node date/time value periodically (typically once per day). Node date/time values should not normally deviate from the timekeeper node date/time value by more than ten (10) seconds between periodic reconciliations. All date/time reconciliations (including the timekeeper node reconciliation) shall be recorded in the PCS event log(s) in a way that allows determination of the pre-reconciliation date/time value offset.

III.1.10.Response to Failures


PCS components should include self-diagnostic capabilities for detecting:

  • Hardware failures and anomalies,

  • Software (application and services) failures and anomalies,

  • Operating System failures and anomalies, and

  • Communication failures and anomalies.

All such PCS failures and anomalies should be treated as process alarms (i.e., annunciated and subjected to alarm management functions). PCS fault conditions that potentially impact data quality should be propagated and accommodated, as appropriate, in data processing, collection, and display.

III.1.11.Security


All PCS components and networks shall be designed to protect against deliberate and/or accidental activities that could potentially compromise personnel, product, equipment, and electronic records. Physical controls should include protection of all PCS components (through locking individual enclosures and/or through isolation in protected areas such as locked rooms) from reasonable attempts to disrupt or modify the component. Logical controls should include user authentication for any process control or PCS modification activity. Refer to the User Interfaces section for additional descriptions related to logical PCS controls.

III.1.12.Safety


The PCS must be designed to both mitigate process hazards and to prevent introduction of any new hazards related to the PCS components. The following process hazards should be considered in PCS design:

Process Hazard

Description



















The following PCS component hazards should be considered in PCS design:

PCS Hazard

Description

Repetitive Stress Injury

Components that require routine use (e.g., user interface hardware) should be ergonomically designed. All PCS components should allow for easy access to facilitate cleaning, preventive maintenance, and replacement.

Electrical

PCS equipment should comply with site electrical and construction standards including appropriate grounding and fusing.

Explosive

PCS equipment should comply with regulations and standards related to the explosive hazard classification of the installation area.

Tripping

PCS equipment should not block normal entry and egress pathways or other personnel traffic areas.









Download 396.6 Kb.

Share with your friends:
1   2   3   4   5   6   7   8   9




The database is protected by copyright ©ininet.org 2024
send message

    Main page