Hello again yuem, may you should check your optional long word parameters, mine are set as:
#1 = 00011011
#3 = 10011010
#4 = 01100001
#12 = 10100010
#15 = 10100011
My NClink settings to send to control are:
Baud rate 2400
Data bits 7
Parity Even
Stop bits 1
XON/OFF - ticked
Start at computer - ticked
First line - leave blank
Last line - %
Timing - 0
Remove spaces - Not ticked
Something I did forget to mention is that with these settings the program transfers across as A.MIN, I then have to rename it.
PIP READ CN0: is the correct command to use. It is giving you the error due to either cable or settings for the ready signal. Use XON/XOFF and disable the DTR and RTS. Either baud rate should work, but must match on both sides.
if you want to rename the file on the way in use:
PIP READ CN0:,ABC.MIN
ABC will be the new file name.
I would not change settings on the machine since they worked before, but if you do, wait at least 3 minutes before power down and then turn off the control and the main breaker for at least 1 minute to let the RS board reset properly.