(b) Are they tapered to not less that 28 ft for multi-vehicle stations?
|
|
|
|
|
|
(c) Are they tapered to not less that 12 ft for single vehicle stations?
|
|
|
|
|
|
(4) Apron Strength
|
|
|
|
|
|
(a) Is the apron strength that same as the apparatus bay?
|
|
|
|
|
|
(5) Gradient – Is the apron slope a minimum of 2-4 degrees and is it directed away from the apparatus bays?
|
|
|
|
|
|
(6) Markings – Is floor and apron striping provided? Is it at least 1.5 times the vehicle length for the apron?
|
|
|
|
|
|
(7) Lighting – Is exterior lighting provided? Is it mounted to prevent view obstruction?
|
|
|
|
|
|
(8) Apron Canopy – Is an apron canopy provided?
|
|
|
|
|
|
(9) Are concrete bollards provided on each side of bay doors to prevent structural damage from backing vehicles?
|
|
|
|
|
|
(10) Apron Heating – Has consideration been given to apron heating in locations that experience extremely low temperatures?
|
|
|
|
|
|
4. Watch/Alarm Room
|
AC 150/5210-15
|
|
|
|
|
a. Is a watch/alarm provided for the receipt and dissemination of alarms, dispatch of equipment, and directing support resources?
|
|
|
|
|
|
b. General Design – Is the watch/alarm room provide for maximum surveillance of the airfield and apparatus bays? If deemed necessary, is the room elevated?
|
|
|
|
|
|
(1) Is the room a minimum of 130 sq ft? Does it have sufficient storage space and wall space for maps, reference materials, and dispatch equipment?
|
|
|
|
|
|
(2) Is the room equipped with a CCTV for security purposes?
|
|
|
|
|
|
(3) Minimum Equipment
|
|
|
|
|
|
(a) Alternate emergency back up power
|
|
|
|
|
|
(b) Accessibility to controls for electronic or electrical servicing/maintenance personnel
|
|
|
|
|
|
(c) Computer systems with LAN access
|
|
|
|
|
|
(d) Radio equipment – ARFF and tunable radio capability
|
|
|
|
|
|
(e) Room dimmer switches and non-glare lighting
|
|
|
|
|
|
(f) Tinted glass, frost free windows (if warranted due to climatic conditions – windows may be heated), shades, retractable sun screens
|
|
|
|
|
|
(g) A lavatory (Note: If watch/alarm employees are disabled – meet requirements of ADA )
|
|
|
|
|
|
(h) Backlit clock with 12 and 24 hour display
|
|
|
|
|
|
(i) Sound suppression to offset ARFF and aircraft sound levels
|
|
|
|
|
|
b. Alarms
|
AC 150/5210-7
AC 150/5210-15
|
|
|
|
|
(1) Are chimes/alert tones provided throughout the station and satellite stations?
|
|
|
|
|
|
(2) Is an audible alarm provided when auxiliary firefighters supplement emergency response personnel?
|
|
|
|
|
|
(3) Are all watch/alarm room controls easily accessible and with in reach of operators?
|
|
|
|
|
|
c. Communications
|
AC 150/5210-7
AC 150/5210-15
|
|
|
|
|
(1) Has AC 150/5210-7 been reviewed for communications requirements?
|
|
|
|
|
|
(2) If multiple stations are at the airport – has a central dispatch center been established?
|
|
|
|
|
|
5. Medical Decon Room
|
AC 150/5210-15
|
|
|
|
|
a. Is a room dedicated for medical cleanup and decontamination of ARFF personnel?
|
|
|
|
|
|
b. Is the room equipped with double sinks, a shower, and drying area?
|
|
|
|
|
|
c. Is the space a minimum of 150 sq ft?
|
|
|
|
|
|
6. Gear Washing/Drying Room
|
AC 150/5210-15
|
|
|
|
|
a. Is the room equipped with a commercial extractor washer and a heated drying rack?
|
|
|
|
|
|
b. Is the space a minimum of 200 sq ft?
|
|
|
|
|
|
7. First Aid and Medical Storage
|
AC 150/5210-15
|
|
|
|
|
a. Is a room dedicated for medical treatment of personnel seeking medical treatment?
|
|
|
|
|
|
b. Is the room lockable and equipped with a sink and cabinets for medical storage?
|
|
|
|
|
|
c. Is the space a minimum of 120 sq ft?
|
|
|
|
|
|
8. Complimentary Agent Storage
|
AC 150/5210-15
|
|
|
|
|
a. Is a storage room dedicated for the storage of dry chemical, halogenated, powder fire fighting agents, and nitrogen cylinders?
|
|
|
|
|
|
b. Are doors of sufficient width to accommodate a fork lift for the delivery of 4x4 pallets?
|
|
|
|
|
|
c. Is the space a minimum of 225-350 sq ft?
|
|
|
|
|
|
9. SCBA and Fire Extinguishers
|
AC 150/5210-15
|
|
|
|
|
a. Is a room dedicated for the servicing and repair of SCBA and fire extinguishers?
|
|
|
|
|
|
b. Is the room provided with storage cabinets and a workbench to perform tasks and store materials and parts?
|
|
|
|
|
|
c. Is the space a minimum of 200 sq ft?
|
|
|
|
|
|
d. Is an air filtration system available for re-servicing of SCBA
|
Compressed Gas Association Specification G-7.1
|
|
|
|
|
e. Is an air compressor provided?
|
|
|
|
|
|
f. Is the power supply for the compressor – 230 VAC 1-phase or 230 VAC/460 VAC 3-phase?
|
|
|
|
|
|
g. Is a cascade system used?
|
ASME Code for Unfired Pressure Vessels
|
|
|
|
|
h. Are all components properly marked with labels/placards or signs that identify nomenclatures?
|
AC 150/5210-15
|
|
|
|
|
i. Are tags and warning labels affixed to equipment for safety and operation?
|
|
|
|
|
|
10. ARFF Administrative Offices
|
AC 150/5210-15
|
|
|
|
|
a. Is office space of sufficient size and features provided for the following:
|
|
|
|
|
|
(1) Fire Chief – 200 sq ft
|
|
|
|
|
|
(a) Conference table
|
|
|
|
|
|
(b) Cabinetry and shelving
|
|
|
|
|
|
(2) Deputy Fire Chief - 160 sq ft
|
|
|
|
|
|
(a) Desk/Filing spaces
|
|
|
|
|
|
(b) Cabinetry and shelving
|
|
|
|
|
|
(3) Lieutenant/Captain – 200 sq ft
|
|
|
|
|
|
(a) Desk/Filing spaces
|
|
|
|
|
|
(b) Cabinetry and shelving
|
|
|
|
|
|
(c) Sleeping space
|
|
|
|
|
|
(4) Conference Room – 100 sq ft
|
|
|
|
|
|
(5) Inspector Office – 160-200 sq ft
|
|
|
|
|
|
(a) Desk/Filing spaces
|
|
|
|
|
|
(b) Cabinetry and shelving
|
|
|
|
|
|
(c) Plans Review Table
|
|
|
|
|
|
(6) Entry/Lobby/Reception Area
|
ADA Compliant
|
|
|
|
|
(a) Administrative Assistant Space
|
|
|
|
|
|
(1) Desk/Filing spaces
|
|
|
|
|
|
(2) Cabinetry and shelving
|
|
|
|
|
|
(3) Visitor Seating
|
|
|
|
|
|
(7) Training Officer – 250 sq ft
|
|
|
|
|
|
(a) Desk/Filing spaces
|
|
|
|
|
|
(b) Cabinetry and shelving
|
|
|
|
|
|
(c) Classroom Training Layout
|
|
|
|
|
|
(d) Validate number of staff members to determine seating capacity for conducting internal training
|
|
|
|
|
|
(e) Training aid storage space
|
|
|
|
|
|
(8) Filing System storage space – 250-500 sq ft
|
|
|
|
|
|
(9) Janitorial Closet
|
|
|
|
|
|
(10) Small kitchenette to support the administrative space (microwave, coffee maker, small refrigerator, cabinetry, small sink, etc)
|
|
|
|
|
|
|