Doc PS Rev R (5) The test rig
willprovide the following facilities as a minimum
1 Two S central processor units (CPUs), both must have an Ethernet port and at least one of them must have a second
Profinet interface port for interfacing to remote IO
2
A din rail mounted, standard Ethernet switch networking the two
CPUs
3 A din rail mounted, Profinet compatible switch connecting the remote IO to the appropriate CPU
4 A single direct online (DOL) drive with suitable starter and overload protection and rotation sensor
5 A single variable speed drive (VSD) with suitable inverter control and speed feedback (either inverter derived or separate instrument A single normally closed isolating valve with individually wirea- ble open and closed limit switches
7 A single normally open isolating valve with individually wireable open and closed limit switches
8 A single modulating valve with position feedback
9 A single thermocouple temperature sensor suitable for ambient
temperature measurement 10 A single resistance temperature detector (RTD) suitable for ambient temperature measurement
11 A single 4 to +20 mA current source with fully variable output
12 A single 0 to +10 V voltage source with fully variable output
13 An emergency stop, locking push-button and suitable safety relay to deactivate all drives and valves
Doc PS Rev R 29-71
(6) The S controllers, the associated cards,
starters, inverters and associated wiring
willbe provided in a lockable electrical panel.
(7) The panel will be of sheet steel construction with powder coated exterior and will be protection category IP or higher.
(8) All instruments, current and voltage sources
willbe calibrated at the time of delivery.
(9) All instruments, drives, valves, starters, inverters, panel
and panel wiring elements willbe commercial, off-the-shelf, standard components that are classified as category 1 hardware under the GAMP 5 hardware classification system, seethe
Good Automation Manufacturing Practice (GAMP) classificationSection of the Project Validation Plan VP,
[Ref. 002](10) The two Simatic Controllers will be equipped with a suitable range of input and output IO) cards that can read and control the above devices
and instruments listed in § 3.1-(5). Each Controller will, as a minimum, have one of each of the following cards
1 A channel 24 VDC digital input card
2 A channel 24 VDC digital output card
3 An channel general purpose analogue input card capable of reading the voltage, current, RTD and thermocouple signals produced by the devices and instruments listed in § 3.1-(5)
4 An channel general purpose analogue output card equipped with
voltage and current outputs (11) A third S rack
willbe provided, this
willbe equipped with a Profinet Interface Module (IM) and, as a minimum, will have at least 8 digital inputs, 8 digital outputs,
2 analogue inputs and 2 analogue outputs
(12)
All local IO cards willbe of the ET200MP type, for remote IO types see § 4.7.4.
(13) Remote IO can be of any type supported by the Simatic S range of controllers) All IO card connections
willbe wired to terminals.
30-71 Doc PS Rev R
(15) The emergency stop push-button
mustbe mounted on the panel door. If the panel is not sufficiently close to the drive and valve equipment, an additional standalone push- button
shallbe mounted in close proximity to the valves and drives.