Document name: Maintenance & Operational Procedures for the control of Legionella, water hygiene, ‘safe’ hot water, cold water, drinking water and non-drinking water. Document type


Maintenance Checks for Other Water Systems



Download 1.43 Mb.
Page15/32
Date02.02.2017
Size1.43 Mb.
#15867
1   ...   11   12   13   14   15   16   17   18   ...   32

3.4 Maintenance Checks for Other Water Systems


Below is a short check list for other systems that may cause risk of Legionella breeding and dispersion. If any of these systems are present, then a more comprehensive maintenance and testing regime and records will need to be created.

System/Service

Task

Frequency

File Section

Ultrasonic humidifiers/

foggers and water misting systems



If equipment fitted with UV lights, check to ensure effectiveness of lamp [check to see if within working life] and clean filters

Six monthly or according to manufacturer’s instructions

To be defined as req’d

Ensure automatic purging of residual water is functioning

As part of machinery shut down

To be defined as req’d

Clean and disinfect all wetted parts

As indicated by risk assessment

To be defined as req’d

Sampling for Legionella

As indicated by risk assessment

To be defined as req’d

Spray humidifiers, air washers and wet scrubbers

Clean and disinfect spray humidifiers / air washers and make-up tanks including all wetted surfaces, descaling as necessary

Six monthly

To be defined as req’d

Confirm the operation of non-chemical water treatment [if present]

Weekly

To be defined as req’d

Water softeners

Clean and disinfect resin and brine tank – check with manufacturer what chemicals can be used to disinfect resin bed

As recommended by manufacturer

C

Emergency showers and eye wash sprays

Flush through and purge to drain

Weekly

C

Sprinkler, wet riser and hose reel systems

When witnessing tests of sprinkler blow down, wet risers and hose reels ensure that there is minimum risk of exposure to aerosols

As directed

To be defined as req’d

Spa baths

Check filters – sand filters should be backwashed daily

Daily

Users

Check water treatment – pools should be continuously treated with an oxidising biocide

Three times daily

Users

Clean and disinfect entire system

Weekly

Users


3.4.1 Strainers


Strainers should be positioned so as they are accessible, they should be cleaned, maintained and disinfected on a regular basis.

3.4.2 Cleaning Water Systems within Buildings


Installations within buildings - All visible debris and scale shall be removed from the cistern. The cistern and distribution pipework shall be filled with clean water and then drained until empty of all water. The cistern shall then be filled with water again and the supply closed. A measured quantity of Sodium Hypochlorite solution of known strength shall be added to the water in the tank in order to give a free residual chlorine concentration of 50mg/l [ppm] in the water. The cistern shall be left to stand for one [1] hour, this being the minimum time period for existing cistern, ideally, it should be left for sixteen [16] hours for new installations. After this time period, each draw-off point shall be successively opened working progressively away from the cistern. Each tap and draw-off point shall be closed when the water discharge begins to smell of chlorine. The cistern shall not be allowed to become empty during this exercise. If necessary it shall be refilled and chlorinated as above. The cistern and pipes shall remain charged with chlorinated water for a further one [1] hour.
On completion of this period, the tap furthest from the tank shall be opened and the level of free residual chlorine in the water discharged from this tap shall be measured. If the concentration of free residual chlorine is less than 30 mg/l [30ppm] the disinfection process shall be repeated.
Distribution systems fed directly off the mains water supply shall have a chemical injection point fitted by others, then thoroughly flushed out with clean water until the free residual chlorine concentrations measured at the taps are no greater than that present in the supplier's mains water.
On completion of the cleaning exercise, a certificate of cleaning and chlorination shall be issued stating that the system has been cleaned and chlorinated in accordance with BS 8558 & BS EN 806.
It should be noted that in areas which are in use, the time scales detailed about maybe unachievable. As such any variations in time scales shall be agreed on site between the Contractor and Supervising Officer.
Full tank cleaning procedures are detailed in section 3.1.1.1.

3.4.3 Minor Plumbing Alterations


Where small alterations or maintenance tasks on water systems have been carried out, then re-commissioning may require no more than thorough flushing of the systems. This can be followed by sampling and analysis of the water if considered necessary by the Supervising Officer, although this is not expected to be required after minor maintenance-related works such as replacement of individual water fittings.

Disinfection should be completed for:



  • New installations (except private dwellings occupied by a single family); or

  • Major alterations (except private dwellings occupied by a single family); or

  • Underground pipework (except localised repairs or insertion of junctions); or

  • Where it is suspected that contamination may have occurred, e.g. fouling by sewage, drainage, animals or physical entry by site personnel for interior inspection, painting or repairs; or

  • Where a system has not been in regular use and not regularly flushed.

All fittings and pipe used on the installation are new and EITHER taken from the manufacturer’s sealed packing just before use, OR pre-chlorinated immediately before use.


Pre-chlorination can be simply achieved by immersing and agitating the fittings for 5 minutes in a 1,000ppm solution of sodium hypochlorite / chlorine dioxide. The COSHH Regulations apply to the use of such solutions at work – a Risk Assessment should be prepared and the appropriate physical precautions must be taken.
To avoid the need to disinfect large systems following relatively minor extensions and alterations, it is recommended that biocide injection points are provided at the point where the new pipework joins the existing system. Biocide injection points take the form of valves, tees and a drain valve or physically removable section of pipe. This enables biocide to be injected into the new section of pipework and circulated or drawn through all new fittings. The removable section must be taken out or the drain valve locked open to prevent any possibility of biocide [a Class 5 fluid] from contaminating the existing fresh water pipework during the disinfection process.
Work should only be undertaken by properly trained, experienced and qualified operatives or Contractors.

3.4.4 Major Plumbing Alterations [including work done through Procure21]


On larger installations or where fittings have been re-used and are not new and sealed, the new or altered section of pipework must be cleaned and disinfected by a specialist Contractor using an approved biocide, in accordance with BS EN 806 & BS 8558.
Major extensions and new buildings must be disinfected before being brought into use, and in many cases it may be more convenient for a specialist Contractor to disinfect the entire buildings systems from the tank or source.
Notification must be made to the Water Undertaker in accordance with the Water Supply [Water Fittings] Regulations 1999. Work should only be undertaken by a competent person. A competent person is an ‘approved contractor’ who is accredited to the WRAS ‘Approved Plumbers Scheme’.

3.4.4 Certification

In accordance with standard conditions of contract, the following Certificates should be obtained from the Contractor before new or significantly altered water systems are accepted at hand-over:


Certificate of Disinfection in accordance with BS EN 806 & BS 8558.

Results of water analysis from UKAS-accredited Laboratory.


3.4.5 Notifications

Under the Water Supply [Water Fittings] Regulations 1999 if any of the following are to be done or installed, the Water Undertaking must be notified before commencing the work:




  • Erection of a building or other structure;

  • Extension or alteration of a water system [other than in a dwelling];

  • Change of premises use;

  • Installation of any of the following, other than as a like-for-like replacement;

  • Bath of over 230 litres capacity;

  • Bidet;

  • Shower unit of a specified type;

  • Pump or booster;

  • Reverse osmosis unit;

  • Water treatment unit;

  • RPZ valve or other mechanical device [category 4 or 5 fluids];

  • Garden watering system;

  • Water system laid outside a building;

  • Construction of a pond or swimming pool;

The Water Undertaking has 10 days to grant or withhold consent and/or impose conditions. After 10 days have expired and nothing has been heard, consent is deemed to have been given.


Approved contractors [members of WRAS ‘Approved Plumbers Scheme’] are exempt from certain of the above, but on completion of the work they must send a copy of the Contractors Certificate to the Water Undertaker.

APPENDIX 1: LEGIONELLA RECORDS DOCUMENT MAP


FILE

(location)



DESCRIPTION

PART

CONTENT

A

AP [Water] Office



MANAGEMENT FILE

1

Letters of appointment

2

Policy & Procedures

  1. Current

  2. Development document [work in progress]

3

Management and Communication

  1. Audit reports

  2. Minutes of management review meetings

  3. Communications e.g. emails to and from service providers

4

  1. Incident Report Forms

  2. Microbiological / Legionella sample results

5

Contracts

6

Competence

  1. External Contractors

  2. Internal Training

B

AP [Water] Office



RISK ASSESSMENT AND SCHEMATICS

1

Current Risk Assessment

2

Risk minimisation scheme and evidence of works completed

3

Current Site Schematics

C

(Schematics / Drawing office)



INDIVIDUAL PROPERTY FILE

LEG48

DHW generator blow down record sheet

Quarterly

LEG45

DHW generator monthly temperature record sheet

Monthly

LEG28

DHW generator internal inspection sheet

Annually

LEG01

DHW plate heat exchanger strip down

Annually

LEG29

DHW calorifier insurance inspection sheet

Every 2 years

LEG02

DHW generator de-stratification checks record sheet

Every 2 years

LEG37

Incoming mains water temperature record sheet

Every 6 mths

LEG32

Tank inspection record sheet

Every 6 mths

LEG07

Cold water tank pre maintenance authorisation sheet and cleaning record sheet

As necessary

LEG39

Sentinel outlet monthly temperature [mixed and non-mixed] monitoring record sheet

Monthly

LEG04

20% Representative tap temperatures record sheet

Annual

LEG26

Outlet flushing – Little used outlet / Vacant areas (<60 days) record sheet

2x Weekly

LEG41

Shower head & hose clean and descale record sheet

Quarterly

LEG08

Outside connections record sheet

Annually

LEG09

Inside connections record sheet

Annually

LEG11

Ward / Dept. indefinite closure record sheet

As necessary

LEG12

New TMV installation record sheet

As necessary

LEG43

TMV / shower maintenance record sheet

Every 6 mths

LEG47

TMV / shower maintenance record sheet

Annually

LEG06

Non critical AHU ventilation supply plant cleaning and inspection record sheet

Every 6 mths

LEG10

Split unit clean and inspection record sheet

Every 6 mths

D

AP [Water] Office



OTHER RECORDS & TECHNICAL REFERENCES

1

Templates [letters / forms etc.]

2

Guidance Documents

3

Other Technical Information

E

(Schematics / Drawing office)



ARCHIVE FILE

N/A

Previous documents e.g. Procedures manuals and letters of appointment.





Download 1.43 Mb.

Share with your friends:
1   ...   11   12   13   14   15   16   17   18   ...   32




The database is protected by copyright ©ininet.org 2024
send message

    Main page