Develop Operate phase performance standard
The Operate phase performance standard templates shall be applied as follows to develop the performance standard contents for the specific Asset. Select the applicable performance standard template and copy those elements (including tasks) which are relevant.
Note that in exceptional cases, a suitable performance standard template may not be available. In this case,
additions or changes shall be notified to, and authorised by,
the owner of this document.
EP 2009-9009
Restricted
21
Figure 9: Example Operate phase performance standard template
PS004 FIREWATER PUMPS
PERFORMANCE STANDARD OWNER Review By email
06/08/2008
Signed off
Date
Function no. Functional criteria
Minimum assurance task
Assurance measure Fire pump starts on demand Robert Baraciolli
BARRIER REFERENCE
SAFETY CRITICAL ELEMENT GROUP
PROTECTION SYSTEMS
Y/N
Assurance value
Y/N
Y/N
Each fire pump shall operate in accordance with its design characteristic.
Each fire pump shall start on demand from initiation signals.
Each pump shall be capable of running without interruption for the duration of a defined emergency event.
Control Room Fire and Gas Panel shall indicate Fire Pump status.
To supply combustion and cooling air to the diesel drivers associated with fire pumps.