Develop Operate phase performance standard The Operate phase performance standard templates shall be applied as follows to develop the performance standard contents for the specific Asset. Select the applicable performance standard template and copy those elements (including tasks) which are relevant. Note that in exceptional cases, a suitable performance standard template may not be available. In this case, additions or changes shall be notified to, and authorised by, the owner of this document. EP 2009-9009 Restricted 21 Figure 9: Example Operate phase performance standard template PS004 FIREWATER PUMPS PERFORMANCE STANDARD OWNER Review By email 06/08/2008 Signed off Date Function no. Functional criteria Minimum assurance task Assurance measure Fire pump starts on demand Robert Baraciolli BARRIER REFERENCE SAFETY CRITICAL ELEMENT GROUP PROTECTION SYSTEMS Y/N Assurance value Y/N Y/N Each fire pump shall operate in accordance with its design characteristic. Each fire pump shall start on demand from initiation signals. Each pump shall be capable of running without interruption for the duration of a defined emergency event. Control Room Fire and Gas Panel shall indicate Fire Pump status. To supply combustion and cooling air to the diesel drivers associated with fire pumps.