shall be broadcastvia terminaland modemcommunicationchannels and a completelistingofallrecords(inorder ofoccurrence)shall be sentto the terminal port.Once the bufferisfilled,newdatawillreplacethe oldona First-In-First-Out basis as newcycles occur.
InformationScreens. The UPSoperatorshall be abletoselecteitherthe BCM Summaryscreen or one offour screensshowingdetailedinformationonanyoneofthe four categoriesofdischarge(0-30seconds,31-90seconds,91-240seconds and Over 240 seconds).
SummaryScreen. The Summaryscreen will ordinarilyshowTotal NumberofDischarge Cycles,AccumulatedBattery Time,AccumulatedBatteryAmpHours (AH),Accumulated Battery KilowattHours (kWh)and the currenttemperatureat thespotwhere the Battery TemperatureSensorhasbeenpositioned.Duringa battery dischargeevent, thescreen shall changetoshowinformationabout the currentdischargecycle.The screenshall display ActiveCycleTimeinplaceofAccumulatedBatteryTimeandsubstitutesActive Battery AHand ActiveBattery kWhfor their accumulatedcounterparts. Remote DataGathering.The UPSshall allowthisinformationto be collectedremotely, through the appropriate communications interface. Modbus (serial communications protocol), BACnet (Building Automation and Control protocol), TCP/IP (Transmission Control Protocol/Internet Protocol) shall be standard protocols. Interface with existing monitoring system that is compatible with MD Anderson current UPC monitoring system (Foreseer by DataTrax Systems), is expected. Contractor is responsible to complete final terminations, programming, alarming, and updating the graphics.
Alarms. Alarmconditionsshall bereportedatthe UPSmoduleunit.The control panelshall reportthe alarmslistedbelow.Each alarmshall bevisuallydisplayedintext formand an audiblealarmwillsound for each alarmdisplayed. InputFail
Battery CBOpen
Battery Discharging
LowBatteryWarning
LowBattery Shutdown
DCOver-voltageShutdown
InverterFault
OverloadShutdown
HardwareShutdown
AmbientOver-temperature
EquipmentOver-temperature
BlowerFailed
InputCurrentUnbalanced
InverterNon-synchronized
LoadOnBypass
OutputUnder-voltage
OutputOver-voltage
OutputOver/UnderFrequency
OverloadTransfer
Manual Reset/Retransfer
StaticSwitch Unable
AutoTransferto Bypass
Bypass Not Available
ModuleSummaryAlarm
EmergencyOff
UPSModuleAlarm. Wheneveranalarmcondition occursat any multi-moduleunit,the control panel at the SystemControl Cabinetshall activatethe audiblealarmand display the faultedmodulenumber.
Controls. Provide the following functions.
UPS/Bypass transfer pushbuttons
ACoutputvoltageadjust±5%
Battery circuitbreakertrip
Emergencyshutdown pushbuttonwithprotectivecover
HornOffpushbutton
Control Enablepushbutton
Display control pushbuttons.Up, Down,Select
AlarmResetpushbutton
OutputTrip pushbutton(M)
Manual Procedures.Start-up,loadtransfers,andshutdown proceduresshall bedetailedon the displaypanelintext and graphicform. Self-Diagnostics.
PresentStatus Screen. The controlsystemshall monitor and displayall ofthe following parametersina PresentStatus screen:
InputVoltage,Line-to-Linefor allthreephases
InputCurrentfor allthreephases
Bypass Voltage,Line-to-Linefor allthreephases
OutputVoltage,Line-to-Linefor allthreephases
OutputCurrentfor allthreephases
OutputFrequency
Battery Voltage
Battery Amps
LoadkVA
All threephasesofthe three-phaseparametersshall bedisplayedsimultaneously.All voltageand curr