Md anderson project No. XX-XXXX md anderson project name



Download 0.87 Mb.
Page7/7
Date09.06.2018
Size0.87 Mb.
#54203
1   2   3   4   5   6   7
EXECUTION

      1. INSTALLATION OF UPS SYSTEM

        1. General. Install UPS where shown, in accordance with the manufacturer's written instructions and recognized industry practices to ensure that the conditioners comply with the requirements and serve the intended purposes.

        2. Standards. Comply with the requirements of NEMA and NEC standards and applicable portions of NECA's "Standard of Installation", for installation of switchgear.

        3. Tightness. Torque terminals and tighten mechanical fasteners.

        4. UPS Modules and Related Equipment Mounting. This equipment shall be mounted directly on the raised floor. Coordinate additional raised floor pedestals required to support equipment, if any, with the General Contractor.

        5. Adjustment. Adjust operating mechanisms for free mechanical movement.

        6. Finish. Touch-up scratched or marred surfaces to match original finish.

      2. FIELD QUALITY CONTROL

        1. The following inspections and test procedures shall be performed by factory-trained field service personnel during the UPS system start-up.

            1. Visual Inspection.

              1. Inspect equipment for signs of damage.

              2. Verify installation per drawings.

              3. Inspect cabinets for foreign objects.

              4. Verify neutral and ground conductors are properly sized and configured.

              5. Inspect all cell cases.

              6. Inspect each cell for proper polarity.

              7. Verify all printed circuit boards are configured properly.

            1. Mechanical lnspection.

              1. Check all control wiring connections for tightness.

              2. Check all power wiring connections for tightness.

              3. Check all terminal screws, nuts, and/or spade lugs for tightness

            1. Electrical Inspection.

              1. Check all fuses for continuity.

              2. Confirm input and bypass voltage and phase rotation is correct.

              3. Verify control transformer connections are correct for voltages being used.

              4. Assure connection and voltage of the battery string(s).

        1. UNIT START-UP

          1. Energize control power.

          2. Perform control/logic checks and adjust to meet specification.

          3. Verify DC float and equalize voltage levels.

          4. Verify DC voltage clamp and overvoltage shutdown levels.

          5. Verify battery discharge, low battery warning and low battery shutdown levels.

          6. Verify fuse monitor alarms and system shutdown.

          7. Verify inverter voltages and regulation circuits.

          8. Verify inverter/bypass sync circuits and set overlap time.

          9. Perform manual transfers and returns.

          10. Simulate utility outage.

          11. Verify proper recharge.

        2. MANUFACTURER'S FIELD SERVICE

          1. Service Personnel.

            1. The UPS manufacturer shall directly employ a nationwide service organization, consisting of factory trained field service personnel dedicated to the start-up and maintenance of UPS and power equipment.

            2. The manufacturer shall provide a national dispatch center to coordinate field service personnel schedules. One toll-free number shall reach a qualified support person 24 hours/day, 7 days/week, 365 days/year. If emergency service is required, telephone response time shall be 20 minutes or less and on-site response time shall be four hours or less.

            3. Two local customer engineers shall be assigned to the site with a regional office as a backup. Daily automated reports shall be supplied to the regional office to document failed equipment. Automatic escalation procedures shall notify the national support manager if a site is not functioning within 24 hours.

          1. Automated Site Monitoring.

            1. The UPS manufacturer shall provide as an option an automated site monitoring service. This service shall be staffed by a qualified support person 24 hours/day, 7 days/week, 365 days/year. At the detection of an alarm within the UPS, the SCC (System Control Cabinet) shall initiate communications with the monitoring service. The monitoring service shall be capable of downloading all existing UPS system alarms to allow dispatch of a service engineer with repair parts.

          1. Replacement Parts Stocking.

            1. Parts shall be available through an extensive network to ensure around-the-clock parts availability throughout the country.

            2. Recommended spare parts shall be fully stocked by local field service personnel with back- up available from national parts center and the manufacturing location. The national parts center Customer Support Parts Coordinators shall be on-call 24 hours a day, 7 days a week, and 365 days a year for immediate parts availability. Parts from the national parts center shall be shipped within 4 hours on the next available flight out and delivered to the customer's site within 24 hours.

        1. UPS MAINTENANCE TRAINING

          1. Maintenance training courses for customer employees shall be available by the UPS manufacturer. This training is in addition to the basic operator training conducted as a part of the system start-up.

          2. The training course shall cover UPS theory, location of subassemblies, safety, battery considerations and UPS operational procedures. The course shall include AC-to-DC conversion and DC-to-AC inversion techniques as well as control, metering, and feedback circuits to the Printed Circuit Board (PCB) level. Troubleshooting and fault isolation using alarm information and internal self-diagnostics shall be stressed.

        2. MAINTENANCE CONTRACTS

          1. A complete offering of preventive and full-service maintenance contracts for both the UPS system and battery system shall be available.

        3. OPERATOR TRAINING

          1. The manufacturer's startup representative shall provide minimum of (8) hours of operating and maintenance training to the Owner's maintenance personnel. Training shall be provided at times convenient to the Owner. Approved Operating and Maintenance Manuals shall be available to the Owner prior to the training session.

END OF SECTION 26 33 53



Download 0.87 Mb.

Share with your friends:
1   2   3   4   5   6   7




The database is protected by copyright ©ininet.org 2024
send message

    Main page